Basic Documentation

Table Of Contents
Project Name 230900 - 3 BAS AND CONTROL FOR HVAC
Date
e. Valves shall contain an actuated flow control portion that responds to the
modulating signal from the controller. This control valve portion shall have a
linear flow characteristic.
f. Valves shall contain a field adjustable flow limiter. The flow limiter shall be
easily adjustable in the field without the use of special tools. The adjustment dial
shall be set for and indicate maximum flow. It shall be possible to manually limit
the flow to the required value with the flow limiter and then modulate the flow
with the control valve and actuator.
1) A table shall be attached to each valve indicating GPM corresponding to
each setting on the dial.
2) No mechanical devices besides the valve and actuator shall be permitted to
adjust the maximum flow setting. Flow limiting port shall be integrated into
the valve body.
3) The valve shall always maintain full nominal stroke regardless of the
maximum flow setting of the flow limiter.
4) The flow limiter shall be lockable and tamper resistant when the actuator is
installed correctly.
g. At any given actuator setting the flow accuracy across the entire pressure
independent operating range of the automatic differential pressure regulator shall
be ±10% or less.
h. Pressure ports shall be standard in the body of the valve for all flanged valves.
Pressure ports shall provide a means for a balancer to test the differential pressure
across the valve control port to ensure the PICV is operating within the pressure
independent range.
i. Valves 2-1/2 inch and larger shall be provided with ANSI 125 or ANSI 250
flanged connections.
j. Valves 2-1/2 inch and larger line size shall meet or exceed ANSI Class IV (0 to
0.01% of nominal maximum) leakage rating at 100 psi close off.
k. The differential pressure range for effective pressure independent operation shall
be 3.6 90 psi or 8 90 psi for 2-½ and 3 inch flanged valves depending on the
maximum gpm flow range of the valve.
l. Valve materials shall meet or exceed the following:
1) Valve body: Cast iron
2) Stem, spring: Stainless steel
3) Seat: Stainless steel
4) Plug: Brass and EPDM
5) Seals: EPDM (peroxide cured)
G. Threaded Valves, line size ½” to 2”
1. Controlled Media Specific Items
a. The control valve shall be suitable for chilled water to a minimum of 35°F (2°C)
and hot water to a maximum temperature of 250°F (121°C).
b. The control valve shall be suitable for up to 50% ethylene or propylene glycol
solutions, chilled glycol/water solutions to a minimum of 35°F (2°C) and hot
glycol/water solutions to a maximum temperature of 250°F (121°C).
2. General Construction Materials/Applicable Standards
a. Control valve bodies shall be constructed of forged DZR brass and shall meet
requirements of ANSI 250 pressure class.
b. Inlets and outlets shall be clearly marked on the valve bodies.
c. Valves shall be constructed with a single chamber and multiple seats to provide
flow limiting, pressure compensation and flow control.