Project Name 230900 - 4 BAS AND CONTROL FOR HVAC
Date
d. Valves shall contain a mechanical, spring-loaded pressure independent regulator to
maintain a consistent differential pressure across the control port of the valve.
e. Valves shall contain an actuated flow control portion that responds to the
modulating signal from the controller. This control valve portion shall have a
linear flow characteristic.
f. Valves shall contain a field adjustable flow limiter. The flow limiter shall be
easily adjustable in the field without the use of special tools. The adjustment dial
shall be set for and indicate maximum flow. It shall be possible to manually limit
the flow to the required value with the flow limiter and then modulate the flow
with the control valve and actuator.
1) The dial shall show settings in GPM.
2) No mechanical devices besides the valve and actuator shall be permitted to
adjust the maximum flow setting. Flow limiting port shall be integrated into
the valve body.
3) The valve shall always maintain full nominal stroke regardless of the
maximum flow setting of the flow limiter.
4) The flow limiter shall be lockable and tamper resistant when the actuator is
installed correctly.
g. At any given actuator setting the flow accuracy across the entire pressure
independent operating range of the automatic differential pressure regulator shall
be ±10% or less.
h. Pressure ports shall be an optional accessory that can be added to threaded valves.
Pressure ports shall provide a means for a balancer to test the differential pressure
across the valve control port to ensure the PICV is operating within the pressure
independent range.
i. Valves 2 inch and smaller shall be provided female NPT piping connections.
j. Close-off and leakage
1) Normally open valves ¾ inch and smaller line size shall meet or exceed
ANSI Class IV (0 to 0.01% of nominal maximum) leakage rating at 200 psi
close off.
2) Normally closed valves 1-1/4 inch and smaller line size shall meet or exceed
ANSI Class IV (0 to 0.01% of nominal maximum) leakage rating at 45 psi
close off.
3) Valves 1-1/2 and 2 inch line sizes shall meet or exceed ANSI Class III (0 to
0.1% of nominal maximum) leakage rating at 50 psi close off.
k. Differential pressure ranges:
1) The start-up differential pressure of the automatic differential pressure
regulator shall be between 2.3 and 4.6 psi, depending on valve size and flow
rate for ½ to 2 inch valves.
2) The maximum operating differential pressure of the automatic differential
pressure regulator shall be 58 psi for ½ to 2 inch valves.
3) In no instance shall the minimum effective pressure differential for effective
pressure independent operation exceed 4.6 psi for valves less than or equal
to 2 inch line size.
l. Valve materials shall meet or exceed the following:
1) Valve body: DZR brass
2) Stem, spring: Stainless steel
3) Seat: brass
4) Plug: Brass and EPDM
5) Seals: EPDM (peroxide cured)