Brochure
VALVES ACTUATORS
Valve
Body
Line Size,
Inch (mm)
ANSI
Class
Maximum
Flow
Non-Spring Return Spring Return
SAX61.03U
0 to 10V
SAX81.03U
Floating
SAV61.00U
0-10V
SAV81.00U
Floating
SQV91P30U
Normally Open
SQV91P40U
Normally Closed
Floating, 0-10V, 4-20mA
Actuator Prex Code
371 372 378 379 238 239
599-07310
2-1/2
(65)
125
110 371-07310 373-07310 - - 238-07310 239-07310
599-07315 154 371-07315 373-07315 - - 238-07315 239-07315
599-07320
250
110 371-07320 373-07320 - - 238-07320 239-07320
599-07325 154 371-07325 373-07325 - - 238-07325 239-07325
599-07311
3
(80)
125
150 371-07311 373-07311 - - 238-07311 239-07311
599-07316 190 371-07316 373-07316 - - 238-07316 239-07316
599-07321
250
150 371-07321 373-07321 - - 238-07321 239-07321
599-07326 190 371-07326 373-07326 - - 238-07326 239-07326
599-07312
4
(100)
125
300 - - 378-07312 379-07312 238-07312 239-07312
599-07317 395 - - 378-07317 379-07317 238-07317 239-07317
599-07322
250
300 - - 378-07322 379-07322 238-07322 239-07322
599-07327 395 - - 378-07327 379-07327 238-07327 239-07327
599-07313
5
(125)
125
485 - - 378-07313 379-07313 238-07313 239-07313
599-07318 595 - - 378-07318 379-07318 238-07318 239-07318
599-07323
250
485 - - 378-07323 379-07323 238-07323 239-07323
599-07328 595 - - 378-07328 379-07328 238-07328 239-07328
599-07314
6
(150)
125
650 - - 378-07314 379-07314 238-07314 239-07314
599-07319 860 - - 378-07319 379-07319 238-07319 239-07319
599-07324
250
650 - - 378-07324 379-07324 238-07324 239-07324
599-07329 860 - - 378-07329 379-07329 238-07329 239-07329
Siemens Industry, Inc.
Building Technologies Division
1000 Deereld Parkway
Buffalo Grove, IL 60089
Tel (847) 215-1000
For more information, or to place an order, please contact your Siemens territory manager.
All rights reserved. Printed in USA 654-3897p10
©2015 Siemens Industry, Inc.
HVAC system inefficiencies and poor occupant comfort
Facility managers continue to focus on improving energy
efficiency to reduce costs. Yet an often-overlooked area is
hydronic heating and cooling systems. Many of these
systems do not respond quickly or accurately to load,
pressure and flow changes. Because hydronic systems are
dynamic, water pressures change continuously in the system
as valves open and close, pumps start, stop, and change
speed, and pump impellers wear. With any change in
pressure, there is a corresponding change in flow through
the control loop, even if the heating or cooling load is
constant. The results are wasted energy and difficulty
maintaining consistent temperature and occupant comfort.
Improve efficiency and comfort through better
hydronic control in HVAC applications
Unlike conventional control valves, Siemens PICVs respond to
unavoidable system pressure fluctuations because the PICV’s
automatic differential pressure regulator constantly adjusts
to pressure changes. The constant flow through the PICV,
regardless of pressure fluctuations in the system, increases
heat transfer through the coils. The result is maximized ∆T
which significantly improves energy usage and cost savings
by preventing an over-supply or under-supply of heating or
cooling energy. Also, more accurate temperature control also
enhances occupant comfort.
Siemens PICV have the unique advantage of always
maintaining their full stroke, regardless of the maximum
adjustable flow setting, to provide better control. Pair them
with SQV spring return actuators and SAX or SAV non-spring
return actuators with all control signal and failure mode
combinations for a wide range of applications.