2 inch valves shall be suitable for chilled water to a minimum of 35°F (2°C) and
hot water to a maximum temperature of 230°F (110°C).
b. The control valve shall be suitable for up to 50% ethylene or propylene glycol
solutions, chilled glycol/water solutions to a minimum of 35°F (2°C) and hot
glycol/water solutions to a maximum temperature of 250°F (121°C). 3-way 1-1/2
inch and 2 inch valves shall be suitable for up to 50% ethylene or propylene glycol
solutions, chilled glycol/water solutions to a minimum of 35°F (2°C) and hot
glycol/water solutions to a maximum temperature of 230°F (110°C).
3. General Construction Materials/Applicable Standards
a. Control valve bodies shall be constructed of forged brass according to ASTM
B283 (C37700, CuZn39Pb2 or equivalent), and shall meet requirements of ANSI
250 and 600WOG pressure classes.
b. Inlets and outlets shall be clearly marked on the valve bodies.
c. Valve ball shall consist of nickel-plated brass, chrome-plated brass or stainless
steel.
d. End connections shall be NPT internally threaded according to ANSI B1.20.1.
e. The control valve flow rate (Cv) shall meet the requirements of ANSI/ISA S75.02.
f. The control valve shall have an equal percentage flow characteristic, according to
ANSI/ISA S75.11. A single glass filled PTFE V port insert shall provide both the
ball seal and shall establish the flow coefficient of the valve. The V port insert
shall be retained by the valve body itself, not requiring additional retaining
components. Flow coefficient adapters requiring a retainer clip, or installed after
final assembly of the valve or as inserts in the ball shall not be allowed.
g. 2-way valves and the A-AB path on 3-way valves shall meet the requirements of
ANSI Class IV (0.01% of rated Cv) seat leakage, or better, according to ANSI/FCI
70.2, at the specified close-off pressure. Bypass path (B-AB) on 3-way valves
shall meet the requirements of ANSI Class III (0.1% of rated Cv) seat leakage, or
better, according to ANSI/FCI 70.2.
h. Chilled and Hot water valve shall have a blow-out proof stem with two EPDM
(peroxide cured) O-rings. External stem retainers will not be allowed.
i. Valve stem shall be made of brass or stainless steel.
j. Valve shall have the ability to be manually operated in the event of a power failure.
D. Pressure Independent Control Valves (PICV)
1. Manufacturer
a. Siemens 599 series valves bodies, SSD, SAX, SQV Actuators, Series 230, 231,
232, 233, 238, 239, 371, and 373 assemblies
2. Where to use PICVs
a. Provide PICVs where called for in the specifications, sequences of operations, or
on the drawings.
b. If it is not stated elsewhere, PICV valves should be provided to meet the following
guidelines:
1) Provide in direct return, constant speed pumping systems.
2) Provide in direct return, variable flow water systems where with the system
at full flow the pressure differential between the supply connection and the
return connection is more than double the pressure drop of the circuit or
loop at design flow (including piping, fittings, devices, control valve and
coil).
3) Provide in reverse return, constant speed pumping systems where the
circuits and loop pressure drops differ by more than 50%.