Basic Documentation

Table Of Contents
Project Name 230900 - 7 BAS AND CONTROL FOR HVAC
Date
2. Provide valves 2" and smaller with screwed end bodies and provide valves 2-1/2" and
larger with flanged ends.
3. Sizing:
a. Differential pressure service for Constant Volume systems: Cv shall be calculated
using 70% of design flow and 50% of pump head.
b. Differential pressure service for Variable Volume systems: Cv shall be calculated
using minimum flow requirement of equipment plus 10% and pump head at the
minimum allowable pump speed.
F. Butterfly Valves
1. Furnish automatic butterfly valves for isolation requirements as shown on the drawings or
required herein.
2. Butterfly valves shall have body ratings in accordance with the piping specifications.
3. Valves that are in high static locations or where flanges are ANSI300 per the piping
design shall be high performance, fully lugged with carbon steel body ANSI 300 as
required by pipe specifications.
4. Valves that are in locations where ANSI150 flanges are allowed shall be ANSI 150
valves.
5. Valves shall be bubble tight with 316 stainless steel disc, stainless steel shaft and
reinforced Teflon seat.
6. Actuators shall be fail in place with factory mounted open and closed position limit
switches mounted.
7. Provide fail in place, electric actuators with waterproof enclosure and crankcase heater
for actuator and accessories mounted outside.
8. Provide manual override hand wheels for each valve.
9. Butterfly valves will only be approved for cooling tower bypass and all two-position
(open or close) applications.
10. Valves must have full lug type body connections.
G. Steam Valves:
1. Steam control valves shall be of linear flow characteristics for modulating service.
2. Sizing Criteria:
a. 15 psig or less; pressure drop 80% of inlet psig. [off]
b. 16 to 50 psig; pressure drop 50% of inlet psig. [off]
c. Over 50 psig; pressure drop as scheduled on plans. [off]
3. Steam valves shall fail normally open or closed, as scheduled on plans, or as follows:
a. Heating coils in air handlers: normally open.
b. Steam to hot water heat exchanger: normally closed.
c. Other applications: as required by sequences of operation.
4. Low leakage rate (ANSI Class IV)
5. Direct mount actuators
a. Actuators shall be designed to connect directly to the valve stem without the use of
a linkage or gear box. Linkages or gear boxes are not acceptable.
b. Brushless motors, microprocessor controlled, for longer life. Brushed motors not
allowed because of wear and erosion.
c. Reinforced nylon gears occluding with steel or die cast aluminum gears on metal
pinion.
d. Electronic overload or stall protection in both directions.
e. Adjustable mechanical range of rotation shall be adjustable between 90deg and
45deg. The control signal shall self-adapt such that the 0-10Vdc control signal is
scaled within the adjusted mechanical range.