Data Sheet for Product
Pressure Independent Control  Technical Instructions 
SQD Series Electromotoric Actuators  Document Number 155-777 
  December 22, 2011 
Siemens Industry, Inc.  Page 3 
Operation 
SQD85.03U 
3-position control signal 
Voltage at Y1:  Stem extends, valve opens 
Voltage at Y2:  Stem retracts, valve closes 
No voltage at Y1 or Y2:  Actuator holds the current position 
SQD65U 
0 to 10 Vdc or 0 to 1000 
Ω control signal 
•  The valve opens/closes in proportion to the control signal at Y or R. 
•  At 0 Vdc or 0 Ω the valve is closed (A Æ AB). 
•  When the power supply is removed, the actuator maintains its current position. 
Engineering Notes 
The actuators must be electrically connected in accordance with local regulations and the 
connection diagrams. 
CAUTION: 
Safety regulations and restrictions designed to ensure the safety of people and 
property must be observed at all times. 
For admissible temperatures, see Specifications. 
Commissioning 
Notes 
When commissioning the system, check wiring and the functions. 
Manual override 
Switch off the positioning signal. 
The valve can be fully closed (= 0% stroke) by turning the manual adjuster 
counterclockwise. Control is automatically resumed when the positioning signal returns. 
Three-position control 
Every actuator must be driven by a dedicated controller. (See Wiring Diagrams.) 
Troubleshooting 
Check Wiring for proper connections. 
If the actuator does not provide full flow or full close-off, check that the actuator is 
properly attached to the valve. 
If not: 
1.  Turn the power off. 
2.  Turn the override knob to manually retract the output shaft to the zero position. 
3.  Tighten the bonnet ring onto the valve completely. 
4. Power up. 
The actuator must be correctly installed on the valve before commissioning. 
Repair 
The actuator cannot be repaired. It has to be replaced as a complete unit. 