Installation Instructions
Document No: 129-553 
Installation Instructions 
December 22, 2011 
8.  Fasten the cover with the screws. See 
Figure 8. 
EA1344R1
M30 x 1.5
2
2
1
1
Figure 8. 
The installation is now complete. 
Wiring 
All wiring must conform to NEC and local codes and 
regulations. 
Use earth ground isolating, step-down Class 2 
transformers. Do not use auto transformers. 
Determine the supply transformer rating by adding 
the total VA of all actuators used. The maximum 
rating for Class 2 step-down transformer is 100 VA. It 
is recommended that no more than 10 actuators be 
powered by one transformer. 
SQD65U 
To use a 0 to 1000 ohm input signal on terminal R, 
the circuit board jumper R—M must be cut. 
CAUTION: 
If the circuit board jumper R–M is cut, you 
cannot wire the R and M terminals on the 
terminal block to re-establish the 
connection. 
The 0 to 1000 ohm signal is additive to the 0 to 10 
Vdc control signal. For example, a controller 
commanded to 2 Vdc (20%) plus a remote override 
input to 300 ohms (30%) results in a position of 50% 
stroke. 
Figure 9. SQD65U Terminal Connections. 
G, G0  24 Vac operating voltage 
   G  System potential 
   G0  System neutral 
Y  0 to 10 Vdc control signal 
R  Input for 0 to 1000 Ohm remote setting unit or 
low temperature detection unit 
M Measuring neutral 
U  Output for 0 to 10 Vdc position indication 
WARNING:  
Terminal connection G is 24 Vac HOT, not 
ground. 
CAUTIONS: 
•  G0 and G must be properly wired for 
correct function and full life of the 
actuator. 
•  If the actuator makes a buzzing noise 
upon reaching setpoint, G and G0 are 
improperly wired and should be 
reversed. 
SQD85.03U 
NEUT
CONTROLLER
ACTUATOR
EARTH GROUND
ISOLATING CLASS 2
TRANSFORMER FOR
24 Vac POWER
120 Vac
1
0
Y2
Y1
G
24
Vac
EA0795R1
Figure 10. SQD85.03U Wiring. 
G  24 Vac operating voltage (system potential) 
Y1  Output shaft extends, valve opens 
Y2  Output shaft retracts, valve closes 
Siemens Industry, Inc.  Page 3 of 4 