Climatix™ C600 HVAC&R controller POL648.x0, POL688.x0, POL69x.
Application and features Field of application Climatix products are designed for use in heating, ventilation, air conditioning and refrigeration machines and provide a broad range of control and monitoring functions. The number and type of I/Os on the controller and extension modules are optimized for these application types. Modular design The product range is of modular design and primarily comprises controllers and various addon I/O and communication modules.
Design The Climatix C600 product range consists of three controller types with 21, 27, and 29 physical inputs and outputs. The design and configuration of the inputs/outputs and interfaces are conceptually equal for all controller types. The controllers are available with and without integrated HMI. The following figures display the three basic types, each with integrated HMI.
POL688 - 27 inputs and outputs POL69x - 29 inputs and outputs 4 Siemens Smart Infrastructure A6V10990076_en_c 2020-04-20
Additional interfaces on the bottom of the devices Type Stock number Inputs Outputs POL648.10/STD S55396-C481-A100 3 UI, 8 UIO, 4 DI 6 relays POL648.80/STD S55396-C488-A100 3 UI, 8 UIO, 4 DI 6 relays POL688.10/STD S55396-C881-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs POL688.80/STD S55396-C888-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs POL698.10/STD S55396-C981-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs, 2 stepper motors POL698.
Input/output signal types POL648 - Input/output configuration X9 N Ni Pt DI X10 N Ni Pt DI DS Q1 X11 N Ni Pt DI DS Q2 X1 N Ni Pt R V in mA in DIx V out mA out DO Q3 X2 N Ni Pt R V in mA in DIx V out mA out DO Q4 X3 N Ni Pt R V in mA in DIx V out X4 N Ni Pt R V in mA in DIx V out DO Q5 DO Q6 X5 N Ni Pt R V in mA in DIx V out DV VM X6 N Ni Pt R V in mA in DIx V out DV VM X7 N Ni Pt R V in mA in DIx V out DV X8 N Ni Pt R V in mA in DIx V out DV D1 DI D2 DIp DU1 DG DU2 DG X7 N Ni Pt R V in
POL69x - Input/output configuration X9 N Ni Pt DI DS Q1 X10 N Ni Pt DI X11 N Ni Pt DI DS Q2 X1 N Ni Pt R V in mA in DIx V out mA out DO Q3 X2 N Ni Pt R V in mA in DIx V out mA out DO Q4 X3 N Ni Pt R V in mA in DIx V out X4 N Ni Pt R V in mA in DIx V out X5 N Ni Pt R V in mA in DIx V out DV VM X6 N Ni Pt R V in mA in DIx V out DV VM DO Q5 DO Q6 DO Q7 DO Q8 X7 N Ni Pt R V in mA in DIx V out DV X8 N Ni Pt R V in mA in DIx V out DV D1 DI DT DO1 DT DO2 D2 DIp DU1 DG DU2 DG M4/3 SMv DA D
Technical data Housing and weight Housing Color ● ● Base plate: Pigeon blue (RAL 5014) Housing: Light gray (RAL 7035) Dimensions See "Dimensions [➙ 31]" Weight Type Weight POL648.10/xxx 453 g POL648.80/ xxx 492 g POL688.10/ xxx 468 g POL688.80/ xxx 506 g POL698.10/ xxx 552 g POL698.80/ xxx 593 g POL69U.10/ xxx 611 g POL69U.
Power data Power, T8 Operating voltage POL648, POL688 AC 24 V -20%...+20%; DC 24 V ±10% POL698, POL69U AC 24 V -15%...+20%; DC 24 V ±10% Frequency 45…65 Hz Protection class III (SELV / PELV) UL Class 2 External fuse in the supply line max. 4 A non-renewable fuse or circuit breaker, type B, C or D Power consumption, without connected extension modules POL648, POL688 39 VA / 24 W POL698, POL69U 60 VA / 43 W Current consumption AC, without extension modules POL648, POL688 max. 1.
Inputs/outputs Universal inputs (T1) Analog inputs X9, X10, X11 Typical sensor Range Resolution Accuracy NTC10k (@ 10 kΩ) 500 Ω…670 kΩ < 43 Ω ± 215 Ω NTC100k (@ 100 kΩ) 500 Ω…670 kΩ < 856 Ω ± 2996 Ω Ni1000 / Pt1000 (@ 1100 Ω) 740 Ω…2000 Ω < 560 mΩ ± 2250 mΩ Universal inputs (T1) Digital inputs X9, X10, X11 0/1 digital signal (binary) For potential-free inputs Sensing voltage/current Typical DC 18 V / 7 mA Contact resistance Max. 200 Ω (closed) Min.
Universal I/Os (T2, T3) Analog outputs X1, X2 Type Range Resolution Accuracy Output 0…20 mA 0…20 mA < 22 μA < 243 μA @ 20 mA Input resistance: < 500 Ω Universal I/Os (T2, T3) DC outputs, e.g. for relay control X5…X8 Switching voltage Typical DC 24 V Switching current Max. 25 mA Universal I/Os (T2, T3) PWM outputs X5, X6 Output voltage (high) DC 8…12 V Output voltage (low) DC 0…1 V Output current Max. 10 mA PWM frequency 0.5…2.
Supply power for active / ratiometric sensors with 5 V, 24 V, 2 x 2 outputs (T2, T3) Sensor power output for active sensors Output voltage DC 24 V (-25 %…15 %) Output current Max. 2 x 40 mA (short-circuit proof) Reference potential System zero ⊥ Reference voltage output for ratiometric measurements NOTICE! Not designed for sensors with pulse-like energy demand. Output voltage DC 5 V (±2.5 %) Output current Max.
Outputs Relay outputs T9…T11 Q1, Q2 (T9, T10) and Q3…Q8 (T10, T11) Relay: Type, contact Switching voltage range ● Q1, Q2, monostable, NO/NC ● Q3…Q8, monostable, NO ● AC 12 V…250 V (45…65 Hz) ● DC 12 V…30 V Switching current range NO contact AC 0.01…4 A DC 0.01…4 A NC contact AC 0.01…2 A DC 0.
NOTICE The following applies for relay and triac outputs: ● Do not mix SELV / PELV and mains power on the same terminal block. ● Use external protection circuits for inductive loads. ● The outputs are not fused internally. An external fuse is required.
Stepper motor control SMc (T16) SMv (T7) Principle Current controlled PWM Voltage controlled Uni/bipolar Bipolar Unipolar or bipolar mode can be configured over software Modes Half or full step mode can be configured over software LED displays Two green LEDs indicate movement and state of the stepper motor control Switching capacity Max. 7.2 W Overall switching power Max. 12 W Output voltage Max. DC 24 V Max. DC 12 V Output current Max. 600 mA Max. 375 mA Peak current Max.
Interfaces The device interfaces are depicted in "Design [➙ 3]". Interface Symbol/ Location Use Technical data Service/tool interface T-SV Engineering and commissioning ● USB 2.0 device ● ● Plug: Type Micro-B ● Data rate: 1.5 Mbps and 12 Mbps SAPRO and SCOPE tool ● Off-the-shelf USB cable (not included) NOTICE! No galvanic separation to ground. Equalization currents are limited to the system zero.
Interface Symbol/ Location Use Technical data Third-party bus T6, T14 Connect field devices ● Plug: 3-pin connection for all interfaces ● ● RS-485 (EIA-485) interface ● ● Galvanically separated (T6 only) Data rate: max. 600 Baud…115 kBaud (can be set over software) 'Building automation system' ● Maximum connectable devices: Up to 31 devices ● Modbus RTU ● ● BACnet MS/TP (T6 only) Bus termination (can be set over software): 120 Ω + 1 nF (T6 only) e.g.
Cable types Interface Specification Ethernet Always screened: ● 100 BASE-TX, cable category 5 ● 10 BASE-T, cable category 4 Process bus Shielded, twisted pair: 0.5…1.5 mm2 (as per KNX specification) Peripheral bus 4-wire (2 wires as twisted pair), shielded, if >3 m Third-party bus 2 or 3-wire, twisted, shielded, if >3 m Signal lines (Inputs/outputs) ● Wire: 0.5…2.5 mm2 ● Stranded wire (twisted, terminating sleeves required): 0.5…1.
Conformity Ambient conditions and protection classification Classification as per EN 60730 Operation of automatic controller Type 1 Degree of pollution 2 Overvoltage category III Design type Device suited for use with equipment of safety classes I and II Degree of protection of housing to EN 60529 IP20 Climatic ambient conditions Transport (in transport packaging) Class 2K3 as per EN 60721-3-2 ● Temperature -25...
Functions LED indicators "BSP" and "BUS" LED Color Flash response Function BSP Red/green Changes at 1 Hz Software update mode: Download application or new firmware Green Continuous Application loaded and operational Orange Continuous Application loaded but is not operational Orange Flashing, 50 ms on / 1000 ms off Application not loaded Red Flashing at 2 Hz Firmware error Red Continuous Hardware fault BUS The application sets the response and function.
Download button Along with an SD card, the download button provides a simple and fast method for loading firmware and application files to the controller without additional tools. Additional information on the download button is available in the SCOPE tool online help. Integrated HMI (for ".80" controller types) See "Design [➙ 3]". An integrated HMI provides the following operating elements: ● Turn/press button ● Alarm button ● Info button ● ESC button The LCD has blue background lighting.
Order data Climatix controllers Type Stock number Description POL648.10/STD S55396-C481-A100 Climatix C600 controller POL648.80/STD S55396-C488-A100 Climatix C600 controller with HMI POL688.10/STD S55396-C881-A100 Climatix C600 controller POL688.80/STD S55396-C888-A100 Climatix C600 controller with HMI POL698.10/STD S55396-C981-A100 Climatix C600 controller with EEV drivers POL698.80/STD S55396-C988-A100 Climatix C600 controller with HMI, EEV drivers POL69U.
Phoenix terminal plug The following overview of compatible types assist you in selecting and ordering the Phoenix type: Controller connectors Compatible Phoenix connector types Color T1 1 x 5 pos - MVSTBW, FKCVW or FKCT 2,5/5-ST Gray T2 1 x 8 pos - MVSTBW, FKCVW or FKCT 2,5/8-ST Gray T3 1 x 8 pos - MVSTBW, FKCVW or FKCT 2,5/8-ST Gray T4 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray T5 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray T6 1 x 3 pos - MCVW 1,5/ 3-ST-3,5 Green T7 1 x 5 pos
Product documentation Document ID Title Description A6V10990076 Datasheet C600 Climatix controller Functions, use, technical data, terminal concept, and dimensions for the C600 controller product range A6V10990056 Installation C600 Climatix controller Mounting and wiring the Climatix controller M3910 Climatic mounting instructions Connecting extension modules. Power variants.
WARNING Electric shock on plug-in terminal blocks The distance to parts potentially under power is very small when using plug-in terminal blocks. ● Ensure the device is not connected to power before using plug-in terminals. Engineering NOTICE Unintended program response caused by changed timing on migrated, old projects The timing response of Climatix controllers depends on the hardware and therefore changes with the introduction of this controller series.
Connection terminals POL648.10, POL648.80 POL648.10 POL648.
Slot T11 T14 Terminal Description Q33 Input for Q3 Q34 NO (normally open) contact Q3 Q43 Input for Q4 Q44 NO (normally open) contact Q4 Q53 Common input for Q5 and Q6 Q54, Q64 NO (normally open) contacts for Q5 and Q6 A1+, B1-, REF1 Third-party bus, RS-485 NOTICE! Not galvanically separated T15 Siemens Smart Infrastructure CE-, CE+ Process bus (based on KNX TP1) 27 A6V10990076_en_c 2020-04-20
POL688.10, POL688.80 POL688.10 POL688.
Slot T11 T12 T13 T14 Terminal Description Q43 Input for Q4 Q44 NO (normally open) contact Q4 Q53 Common input for Q5 and Q6 Q54, Q64 NO (normally open) contacts for Q5 and Q6 Q73 Common input for Q7 and Q8 Q74, Q84 NO (normally open) contacts for Q7 and Q8 C Actuator voltage AC 24..230V DO1, DO2 Switching output 0.5A, triac DL1, DL2 115...230V active digital input DN Reference potential 115...
POL698.10, POL69U.10, POL698.80, POL69U.80 POL698.10 POL698.10 oder POL69U.
Slot T11 T12 T13 T14 Terminal Description Q43 Input for Q4 Q44 NO (normally open) contact Q4 Q53 Common input for Q5 and Q6 Q54, Q64 NO (normally open) contacts for Q5 and Q6 Q73 Common input for Q7 and Q8 Q74, Q84 NO (normally open) contacts for Q7 and Q8 C Actuator voltage AC 24..230V DO1, DO2 Switching output 0.5A, triac DL1, DL2 115...230V active digital input DN Reference potential 115...
124.2 74.0 168.5 4.
7.5 4.5 110.0 134.9 35.3 45.0 ( 3.0 ) 5.5 43.0 72.0 83.5 86.
113.0 56.5 4.9 114.4 125.7 4.9 4.9 4.9 42.5 93.5 Rear view POL648 and POL688 POL698 and POL69U (all dimensions in mm) 243.0 4.5 234.
74.0 124.2 231.5 4.
7.5 4.5 134.9 110.0 45.0 35.3 ( 3.0 ) 5.5 43.0 72.0 83.5 86.
170.5 4.9 114.5 125.7 4.9 4.9 4.9 88.0 ( 5.5 ) 176.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 38 Siemens Smart Infrastructure Document ID A6V10990076_en_c Edition 2020-04-20 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.