Universal inputs (T1)
Analog inputs X9, X10, X11
Typical sensor Range Resolution Accuracy
NTC10k (@ 10 kΩ) 500 Ω…670 kΩ < 43 Ω ± 215 Ω
NTC100k (@ 100 kΩ) 500 Ω…670 kΩ < 856 Ω ± 2996 Ω
Ni1000 / Pt1000 (@ 1100 Ω) 740 Ω…2000 Ω < 560 mΩ ± 2250 mΩ
Universal inputs (T1)
Digital inputs X9, X10, X11
0/1 digital signal (binary) For potential-free inputs
Sensing voltage/current Typical DC 18 V / 7 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Universal I/Os (T2, T3)
Analog inputs X1…X8
Type Range Resolution Accuracy
NTC10k (@ 10 kΩ) 100 Ω…760 kΩ < 43 Ω ± 215 Ω
NTC100k (@ 100 kΩ) 100 Ω…1280 kΩ < 437 Ω ± 2166 Ω
Ni1000 (@ 1100 Ω) 100 Ω…3800 Ω < 396 mΩ ± 1980 mΩ
Pt1000 (@ 1100 Ω) 100 Ω…3800 Ω < 378 mΩ ± 1890 mΩ
Resistance input 0 Ω…2500 Ω < 1000 mΩ < 4000 mΩ
Input DC 0…5 V,
ratiometric sensor
0…5 V < 1 mV < 25 mV @ 5 V
Input resistance: > 100 kΩ
Input DC 0…10 V 0…10 V < 1 mV < 50 mV @ 10 V
Input resistance: > 100 kΩ
Input 0…20 mA 0…20 mA < 1 μA < 120 μA @ 20 mA
Input resistance: < 500 Ω
Universal I/Os (T2, T3)
Digital inputs X1…X8
0/1 digital signal (binary) For potential-free inputs
Sensing voltage/current Typical DC 24 V / 6 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Universal I/Os (T2, T3)
Analog outputs X1…X8
Type Range Resolution Accuracy
Output DC 0…10 V 0…10 V < 11 mV < 124 mV @ 10 V
Output current: Max. 1 mA (short-circuit proof)
Capacitive load: < 200 nF