Universal I/Os (T2, T3)
Analog outputs X1, X2
Type Range Resolution Accuracy
Output 0…20 mA 0…20 mA < 22 μA < 243 μA @ 20 mA
Input resistance: < 500 Ω
Universal I/Os (T2, T3)
DC outputs, e.g. for relay control X5…X8
Switching voltage Typical DC 24 V
Switching current Max. 25 mA
Universal I/Os (T2, T3)
PWM outputs X5, X6
Output voltage (high) DC 8…12 V
Output voltage (low) DC 0…1 V
Output current Max. 10 mA
PWM frequency 0.5…2.5 kHz
NOTICE! Default settings is 500 Hz
Sampling ratio 0…100 %
Resolution 0.5 %
NOTICE
The following applies to all inputs or inputs/outputs (X1…X11):
Can be configured via software
System zero is the reference potential
Maximum contact voltage: DC 24 V
Overvoltage protection: Up to 40 V
Resolution and accuracy are indicated at 25 °C ambient temperature.