Outputs
Relay outputs T9…T11
Q1, Q2 (T9, T10) and Q3…Q8 (T10, T11)
Relay: Type, contact ● Q1, Q2, monostable, NO/NC
● Q3…Q8, monostable, NO
Switching voltage range ● AC 12 V…250 V (45…65 Hz)
● DC 12 V…30 V
Switching current range
NO contact AC 0.01…4 A DC 0.01…4 A
NC contact AC 0.01…2 A DC 0.01…2 A
Contact load rating
NO contact AC 4 A @ 250 V DC 3 A @ 30 V
NC contact AC 2 A @ 250 V DC 1 A @ 30 V
Maximum inrush current
NO contact 10 A (for ≤ 1 sec)
NC contact 3 A (for ≤ 1 sec)
Minimum load for reliable switching ● 10 mA @ AC/DC 12…30 V
● 1 mA @ AC 230 V
Electrical endurance (operations)
NO contact ● Q1, Q2:
100000 @ 3 A @ AC 230 V (resistive load)
● Q3…Q8:
100000 @ 4 A @ AC 230 V (resistive load)
● Q1…Q8:
500000 @ 300 mA @ AC 230 V (resistive load)
100000 @ 2 A @ AC 230 V (inductive load, cosφ≥0.6)
100000 @ 2 A @ DC 30 V
NC contact Q1, Q2:
● 100000 @ 2 A @ AC 230 V (resistive load)
● 100000 @ 1 A @ AC 230 V (inductive load, cosφ≥0.6)
● 100000 @ 1 A @ DC 30 V
Dielectric strength:
Insulation on low voltage 2900 V
External fuse in the supply line max. 6.3 A non-renewable fuse or
circuit breaker, type B, C or D
Triac outputs (T12)
DO1, DO2
Switching voltage AC 19…250 V
Switching current (resistive) Max. 500 mA / Min. 30 mA
Maximum switch-on current 1.5 A (for ≤ 1 sec)
Cos Phi 1…0.8
Dielectric strength:
Insulation on low voltage 2900 V
External fuse in the supply line max. 2.0 A non-renewable fuse or
circuit breaker, type B, C or D