Interfaces
The device interfaces are depicted in "
Design [
3
]
".
Interface Symbol/
Location
Use Technical data
Service/tool
interface
T-SV Engineering and commissioning
SAPRO and SCOPE tool
USB 2.0 device
Plug: Type Micro-B
Data rate: 1.5 Mbps and 12 Mbps
Off-the-shelf USB cable (not included)
NOTICE! No galvanic separation to ground. Equalization
currents are limited to the system zero.
USB host T-SP Auxiliary energy via USB
Power to WLAN routers powered by USB
Plug: Type A
Provides supply current of max. 500 mA
NOTICE! No galvanic separation to ground.
NOTICE! The interface currently does not provide
communications.
SD card left, from
top
Loading and archiving
Load application programs
Download the firmware
See SCOPE online help
Cards: SD, SDHC
Memory card size: 128 MB up to 32 GB
File system: FAT16, FAT32
CAUTION! Switching off the controller during a read/write
action may result in a loss of data.
HMI interface T-HI Commissioning and operation
Climatix HMIs
Plug: RJ45, screened
Communication: RS485 (Modbus)
Power: 24 V, max. 100 mA
Compatible cables are included with the HMIs
Ethernet T-IP Engineering and commissioning
SAPRO and SCOPE tool
Cloud services
Climatix IC integration
Integration
Modbus, BACnet IP or OPC
Touch panels
via Modbus IP or IP
Plug: RJ45, screened
Interface type: 10 BASE-T and 100 BASE-TX, IEEE
802.3 compatible
Bitrates: 10/100 Mbps
Auto sensing
Multiple, simultaneous connections are possiblewhen
using a switch
Process bus T15 Process bus
Connection of CLIMATIX controllers and
room units
KNX-LTE, PL-Link
Type: KNX TP1, galvanic separation
Baud rate: 9.6 kbps
Bus power: 50 mA
Bus load: 5mA
Short-circuit proof