Interfaces
The device interfaces are depicted in "
Design [
➙
3
]
".
Interface Symbol/
Location
Use Technical data
Service/tool
interface
T-SV Engineering and commissioning
● SAPRO and SCOPE tool
● USB 2.0 device
● Plug: Type Micro-B
● Data rate: 1.5 Mbps and 12 Mbps
● Off-the-shelf USB cable (not included)
NOTICE! No galvanic separation to ground. Equalization
currents are limited to the system zero.
USB host T-SP Auxiliary energy via USB
● Power to WLAN routers powered by USB
● Plug: Type A
● Provides supply current of max. 500 mA
NOTICE! No galvanic separation to ground.
NOTICE! The interface currently does not provide
communications.
SD card left, from
top
Loading and archiving
● Load application programs
● Download the firmware
● See SCOPE online help
● Cards: SD, SDHC
● Memory card size: 128 MB up to 32 GB
● File system: FAT16, FAT32
CAUTION! Switching off the controller during a read/write
action may result in a loss of data.
HMI interface T-HI Commissioning and operation
● Climatix HMIs
● Plug: RJ45, screened
● Communication: RS485 (Modbus)
● Power: 24 V, max. 100 mA
● Compatible cables are included with the HMIs
Ethernet T-IP Engineering and commissioning
● SAPRO and SCOPE tool
Cloud services
● Climatix IC integration
Integration
● Modbus, BACnet IP or OPC
Touch panels
● via Modbus IP or IP
● Plug: RJ45, screened
● Interface type: 10 BASE-T and 100 BASE-TX, IEEE
802.3 compatible
● Bitrates: 10/100 Mbps
● Auto sensing
● Multiple, simultaneous connections are possiblewhen
using a switch
Process bus T15 Process bus
● Connection of CLIMATIX controllers and
room units
● KNX-LTE, PL-Link
● Type: KNX TP1, galvanic separation
● Baud rate: 9.6 kbps
● Bus power: 50 mA
● Bus load: 5mA
● Short-circuit proof