User Manual
20
Siemens A6V10990076_en_c
Smart Infrastructure 2020-04-20
Functions
LED indicators "BSP" and "BUS"
LED Color Flash response Function
BSP Red/green Changes at 1 Hz Software update mode:
Download application or new firmware
Green Continuous Application loaded and operational
Orange Continuous Application loaded but is not operational
Orange Flashing, 50 ms on / 1000 ms off Application not loaded
Red Flashing at 2 Hz Firmware error
Red Continuous Hardware fault
BUS The application sets the response and function. Additional notes are available in the SAPRO online help.
LED indicators (green) "O" and "C" for stepper motor control
LED "O" (open) LED "C" (close) Status
Off Off Valve is not moving
On Off Valve is fully open (if referenced*)
Off On Valve is fully closed (if referenced*)
Off Flashing, 250 ms on / 250 ms off Valve is closing
Flashing, 250 ms on / 250 ms off Off Valve is opening
Off Flashing, 50 ms on / 450 ms off Valve moving to the close-failsafe position
Flashing, 50 ms on / 450 ms off Off Valve moving to the open-failsafe position
Flashing, 250 ms on / 250 ms off Flashing, 250 ms on / 250 ms off Error
* "If referenced" means a reference deployment was made. So that the program knows the position of the valve