User Manual

21
Siemens A6V10990076_en_c
Smart Infrastructure 2020-04-20
Download button
Along with an SD card, the download button provides a simple and fast method for loading
firmware and application files to the controller without additional tools.
Additional information on the download button is available in the SCOPE tool online help.
Integrated HMI (for ".80" controller types)
See "Design [ 3]".
An integrated HMI provides the following operating elements:
Turn/press button
Alarm button
Info button
ESC button
The LCD has blue background lighting.
Real-time clock
Backup without battery: 3 days
Backup with battery: 4 years
The Mounting and installation instructions (A6V10990056) illustrate how to install or replace
the backup batters for the real-time clock.
Data Matrix Code (DMC)
The controller has a Data Matrix Code (DMC).
You can scan the code using a code reader app. The result is a text string that, for example,
can be helpful on service calls. Example:
1PS55396-C488-A100+31PPOL648.80/STD+S160908Z0000000005+23S00-A0-03-EB-01-
04+3C3WSZHI-2J7SM-ETMN7-I3LO4-VDVNX
The text string is subdivided into code letters:
1P: Siemens stock number (SSN); fixed
31P: Siemens device type (ASN); fixed
S: Date (YYMMDD), series, serial number, variable
23S: MAC address (hex); variable
3C: Climatix IC activation code (password); variable