User Manual

30
Siemens A6V10990076_en_c
Smart Infrastructure 2020-04-20
POL698.10, POL69U.10, POL698.80, POL69U.80
POL698.10
POL698.10 oder POL69U.10
Slot Terminal Description
T1 X9, X10, X11 Universal inputs
M System zero
T2 X1, X2, X3, X4 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T3 X5, X6, X7, X8 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T4 D1, D2 Digital inputs (potential-free)
M System zero
T5 DU1, DU2 24 V active digital input
DG Reference potential 24V active digital input
T6 A2+, B2-, REF2 Third-party bus (RS-485)
NOTICE! Galvanically separated
T7 +12V Stepper motor control, M4/3
Voltage controlled
unipolar / bipolar
M4-, M4+, M3-, M3+
Unipolar Control of motor windings
0V
Bipolar Control of motor winding
0V/12V
T8 24V Power AC 24V / DC 24V
0V System zero
T9 Q11 Input for Q1
Q12 NC (normally closed) contact Q1
Q14 NO (normally open) contact Q1
T10 Q21 Input for Q2
Q22 NC (normally closed) contact Q2
Q24 NO (normally open) contact Q2
Q33 Input for Q3
Q34 NO (normally open) contact Q3