POL69x - Input/output configuration
X9 X10 X11 X1 X2 X3 X4 X5 X6 X7 X8 D1 D2 DU1 DU2 M4/3
N N N N N N N N N N N DI DIp DG DG SMv
Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni
Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt
DI DI DI R R R R R R R R
V in V in V in V in V in V in V in V in
mA in mA in mA in mA in mA in mA in mA in mA in
DIx DIx DIx DIx DIx DIx DIx DIx
V out V out V out V out V out V out V out V out
mA out mA out DV DV DV DV
VM VM
DS DS DO DO DO DO DO DO DT DT DA DA SMc
Q1 Q 2 Q3 Q4 Q5 Q6 Q7 Q 8 DO1 DO2 DL1 DL2 M1/2
Key
Signal type Short name Description
Analog inputs N NTC10k/100k
Ni Ni1000
Pt Pt1000
R 0…2.5 kΩ
V in DC 0…5 V for ratiometric sensors or DC 0…10 V
mA in 4…20 mA
Digital inputs DIx Potential-free
DI Potential-free
DIp Potential free, 300 Hz
DG Active, 24 V (AC/DC)
DA Active, AC 230 V
Analog outputs V out DC 0…10 V
mA out 4…20 mA
VM PWM
Digital outputs DV DC 24 V
DS Relay, NO/NC
DO Relay, NO
DT Triac
Stepper motors SMv Voltage controlled, bipolar or unipolar
SMc Current controlled PWM, bipolar