User Manual

9
Siemens A6V10990076_en_c
Smart Infrastructure 2020-04-20
Power data
Power, T8
Operating voltage
POL648, POL688
POL698, POL69U
AC 24 V -20%...+20%; DC 24 V ±10%
AC 24 V -15%...+20%; DC 24 V ±10%
Frequency 45…65 Hz
Protection class III (SELV / PELV)
UL Class 2
External fuse in the supply line max. 4 A non-renewable fuse or circuit breaker, type
B, C or D
Power consumption,
without connected extension modules
POL648, POL688
POL698, POL69U
39 VA / 24 W
60 VA / 43 W
Current consumption AC, without extension modules
POL648, POL688
POL698, POL69U
max. 1.6 A @ AC 24 V
max. 2.5 A @ AC 24 V
Current consumption DC, without extension modules
POL648, POL688
POL698, POL69U
max. 1.0 A @ DC 24 V
max. 1.8 A @ DC 24 V
Current consumption AC, for extension modules*
POL648, POL688
POL698, POL69U
max. 2.4 A @ AC 24 V
max. 1.5 A @ AC 24 V
Current consumption DC, for extension modules*
POL648, POL688
POL698, POL69U
max. 3.0 A @ DC 24 V
max. 2.2 A @ DC 24 V
* For calculation, see Q3900