s 3 944 ClimatixTM Climatix Extension Modules ECV2 POL98U.00/XXX POL98E.00/XXX The ECV2 extension modules are products of Climatix range. They are designed for driving a broad range of EEV valves with bipolar stepper motors. IOs of ECV2 extension modules can be configured for various applications of chiller and heat pump.
Electronic expansion valve Electronic expansion valves control refrigerant mass flow in evaporators in evaporators for chillers, air-conditioners and refrigerators applications. In addition modulating valves can be used for several control functions such as liquid injection, hot gas bypass and evaporator pressure regulation. ECV2 extension modules are designed as an electronic expansion valves driver, featuring two independently channel drive bipolar stepper motors.
Installation concept Communication concept Disposal The devices are considered electronics devices for disposal in term of European Directive 2012/19/EU and may not be disposed of as domestic waste. Dispose of the device via the channels provided for this purpose. Comply with all local and currently applicable laws and regulations.
Technical data Power supply Operating voltage Frequency Max. AC-Current consumption Max. DC-Current consumption Connection AC 24 V ± 20%; DC 24 V ± 10% 45…65 Hz 2.2 A, 41 W 1.9 A, 39 W Peripheral bus Power distribution Max pass through current 3.15A @ AC 24V / 3.54A @ DC 24V General data Dimensions in mm Weight excl. packaging POL98U.00/XXX POL98E.00/XXX Base Housing 207 x 110 x 75 Analog inputs B1...B3 (T1) NTC 10k (B25/85 = 3977 K) Sensor current 479.2 g 439.
NTC 100k (B25/85 = 3977 K) Sensor current Note 15 μA @ 25 °C These data are acquired under operating temperature of 25 °C.
Universal IOs X1…X12 (T2, T3, T5) Configurable Reference potential Contact voltage Over voltage protection Analog inputs (X1…X8) Ni1000 Sensor current Resolution Accuracy in the range -50…150 °C Pt1000 Sensor current Resolution Accuracy in the range -40…120 °C 0...2.5 kΩ Sensor current Resolution Accuracy DC 0…5 V input for ratiometric sensors Resolution Accuracy at 0 V Accuracy at 5 V Input resistance By software Terminals ┴ Max. DC 24 V (SELV) Max. 40 V Max. 1.4 mA 0.1 K 0.8 K Max. 1.8 mA 0.1 K 0.
NTC 100k (B25/85 = 3977 K) Sensor current Max.
Analog inputs (X9…X10) Ni1000 Sensor current Resolution Accuracy in the range -50…150 °C Pt1000 Sensor current Resolution Accuracy in the range -40…120 °C NTC 10k (B25/85 = 3977 K) Sensor current Note Max. 1.4 mA 0.3 K 0.7 K Max. 1.8 mA 0.3 K 1.0 K Max. 500 μA These data are acquired under operating temperature of 25 °C.
Analog inputs (X1…X8) DC 0...10 V input Resolution Accuracy at 0 V Accuracy at 5 V Accuracy at 10 V Input resistance DC 0…20 mA / 4…20 mA input Resolution Accuracy at 4 mA Accuracy at 12 mA Accuracy at 20 mA Impedance of DC 0/4…20 mA Analog inputs (X11...X12) DC 0...10 V input Resolution Accuracy at 0 V Accuracy at 5 V Accuracy at 10 V Input resistance DC 0…20 mA / 4…20 mA input Resolution Accuracy at 4 mA Accuracy at 12 mA Note 1 mV 10 mV 30 mV 50 mV 100 kΩ 1 μA 40 uA 80 uA 120 uA Typ.
Digital inputs (X1…X8) 0/1 digital signal (binary) Sampling voltage/current Contact resistance Delay Pulse frequency For potential free contacts DC 24 V / 8 mA Max. 200 Ω (closed) Min. 50 kΩ (open) 10 ms Max.
Analog/digital outputs (X5…X8) DC 0…10 V output Resolution Accuracy at 0 V Accuracy at 5 V Accuracy at 10 V Output current DC output for off board loads Switching voltage Switching capacity 11 mV 66 mV 95 mV 124 mV 1 mA (short-circuit proof) DC 24 V Max. 25 mA Voltage output and off board relays from universal IO Powering sensors active/ratiometric 5V, 24V (T2, T3) 3 x 2 outputs Voltage/current Voltage/current DC 5 V, 3 x 20 mA ±2.
Driver for bipolar stepper motor Constant-current mode Switching frequency Full-step mode Programmable current Programmable hold current Motor voltage Programmable speed Programmable traverse path Programmable overdrive Programmable reference point Max. output power for each motor Length of motor cable UPS (POL98U.00) Energy storage Usable energy Charging time Motor driver M1+…COM (T10, T11) 1) Note Short-circuit proof 50 kHz (variable) 4 steps per revolution 0.1…0.5 A1) 0…0.5 A Max. 42 V Max.
Digital inputs voltage free D1...D3 (T4) 0/1 digital signal (binary) Sampling voltage/current Contact resistance Delay Pulse frequency For potential free contacts DC 24 V / 8 mA Max. 200 Ω (closed) Min. 50 kΩ (open) 10 ms Max. 30 Hz Connecting floating contact to digital input Relay outputs Q1...Q8 (T6, T7) Warning Relay: type, contact Contact rating Switching voltage Nominal current (res./ind.) Switching current at AC 19 V Monostable, NO contact AC 24 V…230 V (-20%, +10%) Max. AC 3 A/2 A (cosφ 0.
Triac outputs DO1, DO2 (T8) Warning Triac output values Switching voltage Switching capacity Min. current Max. external supply line fusing AC 24…230 V Max. 0.5 A 10 mA 2.0 A slow wire fuse or circuit breaker Do not mix SELV / PELV and line voltage on the same terminal. Use external protection for inductive load.
Connection terminals Possible plugs for IO signals (not included) Solid wire Stranded wire (twisted and with ferrule) Cable lengths Peripheral bus Power supply Bus termination Board to board (not included) Board to wire (not included) Stranded wire (twisted and with ferrule) Cable lengths Addressing Termination Environmental conditions Operation Temperature Relative humidity Absolute humidity Air pressure Transport Temperature Humidity Air pressure Phoenix FKCVW 2,5 / x-ST Phoenix FKCT 2,5 / x-ST Phoe
The status of the BSP LED is defined as below: BSP LEDs Mode LED Per second flashing between red and green.
internal super capacitor has still power, the internal application starts again and can control the outputs (therefore BSP LED green). Note DIP switches Firmware of POL98X.00/XXX features different diagnostic functions such as disconnection detection, under voltage detection or shorted coil. The function "disconnection detection" is active only during valve / motor positioning, not during hold on. DIP switch is equipped with the extension module to communicate with the controller.
DIP Switch configuration of extension module No. Schematics No. Schematics Notes No. Switch 5 No. 5 13 21 29 6 14 22 30 7 15 23 31 8 16 24 Schematics The same address of extension module must be respectively set in the application program of the controller. Zero cannot be set as the slave address. Order data Extension Module 32 IOs POL98E.00/STD POL98U.
Dimensions (mm) 19 / 20 Siemens Smart Infrastructure Climatix Extension Modules ECV2 CB1N3944en 2021-02-16
Valve settings Manufacturer Unit / Dimension Danfoss Valve Type ETS 12.5, 25, 50, 100, 250, 400 * CurrentSetpoint [mA] 120 Speed [Steps/s] 300 OverdriveOpen [Steps] 0 OverdriveClose [Steps] 300 HoldCurrentSetpoint [mA] 0 DeadTimeSync [Min.] 60 DelayDirection [ms] 200 Step Mode Full Step * (SKUs 034G0000-034G4999) Maximum cable length 8 m. If a longer cable length is used, communication inductors such as the Danfoss AKA211 should be used.