Climatix™ S300 Heat Recovery Ventilation Controller POS3.5715/100 S300 configurable OEM controller for HVAC controlling, switching and monitoring. Delivered with user interfaces, peripherals and pre-engineered applications, and optimized for heat recovery ventilation.
Features The controller is configurable and is delivered with a pre-loaded, pre-engineered and fully tested application developed for heat recovery ventilation applications. Inputs and outputs (I/Os) The controller’s I/O mix is dedicated for heat recovery ventilation (HRV).
Peripherals S300 range comes with a full set of peripherals: OEM customization of range peripherals is possible upon request.
System overview POL903.00 Order data Type number (ASN) Stock number (SSN) Product description, Inputs application POS3.5715/100 S55393-C571-F100 Controller with heat recovery ventilation, standard application 10 Outputs Modbus KNX PLLink MOQ 8 1 master, 2 slave 1 20 Note: ● MOQ = Minimum order quantity. The number of devices in one package equals MOQ. ● When ordering, specify type, stock number and quantity.
Room units with sensors With POS3.5715/100 Type number Document ID Product description, application Sensor element Display Com MOQ QMX2 POS8.4420/109 A6V11519429 Room unit with temperature sensor 1 temperature 1 LCD with backlight KNX PL-Link 20 Room sensors With POS3.3515/100 and POS3.5715/100 Type number Document ID Product description, application Sensor element Display Com MOQ QFA20..
Damper actuators With POS3.3515/100 and POS3.5715/100 Type number Document ID Product description, application Output Com MOQ GSD.. CE1N4606 Damper actuator 2 Nm without spring return DC 0…10 V - 20 Note: the GSD.. damper actuators can only be used for heat exchanger (bypass). WLAN stick Type number Document ID Product description, application Use MOQ POL903.00/100 A6V11937426 WLAN stick Temporary for WLAN connection to mobile device during commissioning and servicing.
Type number Stock number POS0.3365/100 Product description, application Pole Area Phoenix type MOQ S55844-Z336-F100 6-pole connector 6 SELV FK-MC 0,5/6-ST-2,5 1881367 100 POS0.3375/100 S55844-Z337-F100 7-pole connector 7 SELV FK-MC 0,5/7-ST-2,5 1881370 100 POS0.
Mounting Clearance requirement At least 10 mm clearance to the PCB edge is required. Dimensions in mm Mounting screws Use metallic screws (M3.5) to mount the controller in a cabinet. ● Diameter of screw head and nut is no more than 10 mm. ● Screws are not included in the delivery package.
CAUTION No protection against incorrect wiring on 230 V The device is damaged ● Do not connect the mains power to the low voltage side. Configuration, parameter setting and CSV file creation with ABT site PC tool ABT Site is the PC based tool to engineer and commission building automation systems from Siemens.
Maintenance The controller is designed as a maintenance-free device. Disposal The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations.
Technical data LED indication LED status Function Red LED Error Green LED blink (once / sec) System running Green LED blink (twice / sec) WLAN stick connected Green and red LED blink (once / sec) Software not loaded or not running Green and red LED blink ( > 3 times / sec) Firmware loading Power supply Power supply Operating voltage AC 230 V (+10% / -15%) Frequency 50/60 Hz. Max. power consumption 46 VA NOTICE! M or Ref must be connected to earth by metal screw installation.
DC 0…10 V inputs X1, X2, X3 (T2) DC 0…10 V Operating range 0…10 V Resolution 10 mV Accuracy at 0 V Accuracy at 5 V Accuracy at 10 V 50 mV 80 mV 100 mV Internal resistance > 100 KΩ Avoid negative voltages at the analog inputs, as conversion leads to undetermined results. Digital inputs: pulse measurement X1, X2 (T2) Pulse measurement For open collector sensor Contact resistance For fan speed visualization and error detection 12 Siemens Smart Infrastructure ● Max.
Digital inputs: potential-free X3 (T2), X8 (T1) 0/1 digital signal For potential free contacts Contact resistance Max. 200 Ω (closed) Min. 50 KΩ (open) Pulse frequency Max. 20 Hz Contact sensing voltage DC19.5…24 V Contact sensing current 2.0 mA (initial current 8 mA) Digital inputs: AC/DC 24 V D1, D2 (T3) Active digital input 24 V 24 V AC or DC signal operating range Low / high detection AC or DC 0...
Power supply for field sensors Reference potential Terminals ┴ Connection Short-circuit protected NOTICE! The drive’s capacitive load of DC output 24 V and HMI 24 V is less than 100 μF. Digital outputs Q13, Q14, Q23, Q24 (T7) Q33, Q34 (T14) Digital relay outputs Contact Monostable, NO (normally open) contacts, SPST (single pole, single throw) Switching voltage AC 24...230 V (-20 % / +10 %) Rated current (res./ ind.) AC 0.02...3 A (res.) / 2 A (ind. cosφ=0.6) Switch on current Max.
Onboard Triac output Endurance Max. 4’000’000 cycles for 1 A resistive load Min. cycle time (configurable) of PWM signal ≥ 1 s / 1 Hz Max. external supply line fusing 2.5 A circuit breaker Digital (binary) / analog output triac VAC signal On/Off, signal PWM (constant period)) Analog outputs A1 (T2) A2, A3, A4 (T18) Analog output Siemens Smart Infrastructure Configurable voltage range 0...5 V or 0...
Connections Interfaces Ethernet Plugs: RJ45, top entry. Interface type: 10BASE-T/100BASE-TX. Bit rates: 10/100 Mbps, auto-sensing. Protocol: BACnet/IP over Ethernet. CAT5 shielded twisted pair Length: Max. 30 m USB 2.0 Plug: USB type A. Data rate: full speed. 5 V/500 mA power supply with over-current limiting. KNX (only for POS3.5715/100) Type: KNX PL-Link, galvanic isolation. DPSU: 40 mA rated current Short-circuit proof. Protection against faulty wiring at max. AC 24 V.
Ambient conditions and protection classification Degree of protection of housing to EN 60529 Without housing Climatic ambient conditions ● Transport (packaged for transport) as per IEC 7213-2 ● Storage as per IEC 721-3-1 ● Operation as per IEC 721-3-3 Mechanical ambient conditions Transport as per EN 60721-3-2 Operation as per EN 60721-3-3 IP00 Transport / Storage ● Temperature -40...70 °C (-40... 158 °F) ● Air humidity: 5-90% r.h. (non-condensing). Operation: ● Temperature -40...50 °C (-40...
Diagrams Connection terminals T15 Ref KNX- - L + T4 SELV Area KNX+ HV Area T12 Ref - T11 + N Ref - T16 + 24V= 24V= 5V= D1 T3 T7 Ref1 D2 X1 X2 Q13 X3 A1 T2 Q14 A2 Q23 T18 Q24 A3 A4 X8 Q34 B1 B2 C T19 T1 B3 Y1 B4 Heat Sink T6 T5 A6V11417931Z06 T14 Q33 Use Socket Connector type KNX bus connection (only on POS3.
Use Siemens Smart Infrastructure Socket Connector type T18 Phoenix: FK-MC 0,5/ 6ST-2,5 1881367 T1 Phoenix: FK-MC 0,5/ 7ST-2,5 – 1881370 USB interface T6 USB type A RJ45 interface for Ethernet switch T5 L Phase wire AC 230 V T4 N Neutral conductor Phoenix:1773879 MVSTBW 2,5/2-ST OG D1 AC/DC 24 V input signals DI 1 T3 Ref1 Measuring neutral for input signals (reference voltage G0) Phoenix:1792537 MVSTBW 2,5/3-ST D2 AC/DC 24 V input signals DI 2 Q13 Digital output T7 Q14 Digital
Dimensions Unit: mm Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 20 Siemens Smart Infrastructure Document ID A6V11417931_en--_b Edition 2020-07-08 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.