User Manual
Siemens Industry, Inc.
Building Technologies Division
P/N 315-099321-73
24V 12A FAIL- (Yellow) Normally OFF. When illuminated, indicates
that the 24VDC non-power limited output
has a trouble condition or the PSC-12 has
disconnected the 24VDC output due to
current overload or short circuit.
24V 4A FAIL - (Yellow) Normally OFF. When illuminated, indi-
cates that the 24VDC power limited
output has a trouble condition or the
PSC-12 has disconnected the 24VDC
power output due to current overload or
short circuit.
Three rotary dial switches located directly below the LEDs are used to set
the HNET network address of the PSC-12.
The terminal blocks of the PSC-12 are defined as follows (refer to Figure 2):
TB1 Currently NOT USED.
TB2 Relay Outputs. Four user-programmable relays that are set to
NOT USED by default. These outputs are rated 2A @ 30VDC/
120VAC (.6PF). (Refer to Figure 3 for wiring the relays.)
These relays are controlled by the NCC WAN only. NCC WAN
version 6.01.007 or higher is required. The relays can be config-
ured in the NCC WAN as Global Alarm, Global Trouble or
General Output.
A relay configured as Global Alarm changes the respective PSC
relay state to off normal when there is any alarm on the NCC.
When all alarms are cleared on the NCC, the relay state will
restore to normal.
A relay configured as Global Trouble changes the respective
PSC relay state to off normal when there is any trouble on the
NCC. When all troubles are cleared on the NCC, the relay state
will restore to normal.
A relay configured as General Output will change state only
through a manual command from the NCC, using either the
Device Output Control or using the Disable/Enable (DIS/ENA)
and Energize/DeEnergize (ENE/DEE) manual commands.
Figure 2
Terminal Blocks, Controls and Indicators
GND FAULT
24V 12A FAIL
24V 4A FAIL
MODULE FAIL
HNET FAIL
CAN FAIL
RESET
POWER
PSC-12
P5
1
1
19
1
1
+
+
+
_
_
_
2
2
H
N
GND
6
24
12
18
7
13
12
34
TB1
TB2
BATTERY
P9
P12
TB3
TB4
P4
AC
CONNECTION
(INPUT)
NON- POWER
LIMITED OUTPUT
(24VDC @ 12A Max.)
REGULATED
RELAY OUTPUTS
2A @ 30VDC/
120VAC (.6PF)
BATTERY
CONNECTION
TO PSX-12
OR CC-5
CIRCUIT
BREAKER
TO PSX-12
OR CC-5
BATTERY
THERMISTOR
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
OFF
O
—
ON
P10
GROUND
FAULT
SUPERVISION
HNET/CAN
NOTE:
Positive and negative
ground fault datected at: <60K
ohms for TB4 terminals 1,2.
19
24
18
13
TB2
NO
NO
NO
NO
NC
NC
NC
NC
C
C
C
C
PROGRAMMABLE
USER
RELAY 2
OUTPUT
USER
RELAY 1
OUTPUT
USER
RELAY 4
OUTPUT
USER
RELAY 3
OUTPUT
PROGRAMMABLE
Figure 3
TB2 Wiring Diagram