Data Sheet for Product
2 / 12
Siemens PXC....D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_18
Smart Infrastructure 2022-01-15
Functions
Modular, freely programmable automation stations for HVAC and building control
systems.
Management functions (alarm management with alarm routing, schedulers,
trend functions, remote management, access protection with individually defined
user profiles and categories).
For stand-alone applications or for use within a device or system network.
BTL-tested BACnet communications on LonTalk, PTP or IP, compliant with
BACnet standard (Rev. 1.12 -for Desigo V6.0 and later) including B-BC profile.
AMEV profiles AS-A and AS-B to recommendation "BACnet 2011 - Version 1.2
(for Desigo V6.0 and later)".
Freely programmable, using the D-MAP programming language (close
resemblance to CEN standard 11312). All function blocks, available in libraries,
can be graphically connected.
Engineering and commissioning using the Desigo Xworks Plus tool.
Connection of field devices to a customized mix of TX-I/O modules.
Connection of installed PTM-I/O modules – the perfect solution to migrate legacy
systems.
Connection of TX Open modules to integrate third-party devices such as
variable speed drives, pumps or energy counters.
Connection of detached I/O islands with integration.
Connection of LonMark® compatible devices
Low voltage protection and start-up management to protect the devices against
fluctuating voltage.
Scalable range of touch panels, Web solutions and operator units.
Modular automation station with connected TX-I/O modules
Overview of automation stations – modular series
Connection of TX-I/O modules, TX Open modules, PTM-I/O modules via PXX-
PBUS and LonWorks devices via PXX-L11/12.
Activation of generic Web operation with PXA40-W1
BACnet/IP PXC00-E.D PXC50-E.D PXC100-E.D PXC200-E.D
BACnet/LonTalk PXC00.D PXC50.D PXC100.D PXC200.D
Number of physical data
points TX-I/O
– 80 200 350
Number of TX Open
Modules for e.g. Modbus,
M-Bus
– 5 5 5
Number of data points
(TX-I/O and TX Open)
– 400 600 1000
Number LonWorks
Devices via PXX-Lx
60 or 120 10 60 or 120
1)
60 or 120
1)
1)
In concurrent use with TX-I/O modules, the number of devices is reduced in
relation to capacity
Extension capabilities of the automation stations