Data Sheet for Product

3 / 12
Siemens PXC....D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_18
Smart Infrastructure 2022-01-15
TXM1.. : The flexible range of TX-I/O modules for signaling, measuring,
counting, switching, and positioning. The I/O modules with local manual control
on the module housing permit the operator to control the equipment manually
directly from the cabinet.
TX
I/O devices
1)
Type
Data sheet
Digital input module 8 or 16 I/O points TXM1.8D,
TXM1.16D
CM2N8172
Universal module without / with local
operation and LCD
TXM1.8U,
TXM1.8U-ML
CM2N8173
Super universal mod. without / with local
operation and LCD
TXM1.8X,
TXM1.8X-ML
CM2N8174
Relay module without / with local
operation
TXM1.6R,
TXM1.6R-M
CM2N8175
Resistance measuring module (for Pt100 4-wire) TXM1.8P CM2N8176
Relay module bistable
TXM1.6RL CM2N8177
Triac module TXM1.8T CM2N8179
Power supply module 1.2 A, Fused 10A TXS1.12F10 CM2N8183
Bus interface module, Fused 10A
TXS1.EF10 CM2N8183
1)
TXM1... und TX Open modules require TXS1.12F10 power supply modules.
TX Open : Flexible TX Open platform to integrate third-party systems and
devices such as Modbus or M-Bus. Tested integrations solutions and appli-
cations based on our large know how.
TX Open devices
1)
Type
Data sheet
TX Open module up to 40 data points TXI2-S.OPEN CM1N8187
TX Open module up to 160 data points
TXI2.OPEN CM1N8187
1)
TXM1... und TX Open modules require TXS1.12F10 power supply modules.
PXX-L11/12.. : Extension modules allow for flexibly connecting LonWorks
devices such as room controllers and third- party devices.
PXX
.. devices
2)
Type
Data sheet
Integration of max. 60 devices
(PXC50..D: max. 10 devices)
PXX-L11 CM1N9282
Integration of max. 120 devices
(PXC50..D: max. 10 devices)
PXX-L12 CM1N9282
2)
A high number of LonWorks devices reduces the performance of the PXC for
connected TX-I/O or PTM-I/O data points respectively.