User Manual

3
Siemens
A6V10808336_en--_b
Building Technologies
2019-03-27
LEDs
LED
Color
Activity
Function
RUN
Green Steady ON Device is ready for operation
Steady OFF Device is not powered
Flashing Device is starting
FLT
Red Steady OFF OK
Steady ON HW fault
Flashing Wrong or corrupt configuration
COM1
Yellow Flashing Sends Ethernet/IP packets
SVC
Red Steady OFF Configured
Flashing Unconfigured
LED
Color
Activity
Function
Ethernet 1/2
Green Steady ON Link active
Steady OFF No connection
Flashing Sends 10 or 100 Mbps Ethernet IP
packets
Yellow Steady ON Link: 100 Mbps
Steady OFF Link: 10 Mbps
Service button
Button
Press
Description
S
Short Physical identification on the network (Ethernet)
As per description Do the following to delete the device:
1. Switch off the device.
2. Switch on the device.
3. Wait until all LEDs turn on and then off and then
press the S button.
4. Keep the S button pressed until the green RUN
LED starts to flash and then release.
5. Wait until the device has fully started –
unconfigured (RUN LED on, SVC LED flashes).
The device configuration must be reloaded using ABT
Site to perform additional configurations.