User Manual

3 / 6
Siemens PXX-L11, PXX-L12 Extension modules CM1N9282en_06
Building Technologies 2015-12-23
The PXX-Lxx extension modules support Extended Command Set (ECS) to EIA-
709.1-B protocol. If a L
ONWORKS node is written with an ECS command (e.g.
installation by NL220), several legacy commands will be refused by the module
from this moment on. A module configured in this manner will only allow restricted
communication with older tools that do not support ECS (e.g. the diagnostic tool
NLUtil).
Mechanical design
The compact construction enables the extension module to be used in highly
confined spaces.
1
Plastic housing
2
LED display for device and system status
3
Interface to automation station
4
Service button
5
Tool interface
6
FW download button
7
Plug-in terminal block with screw
terminals (LONWORKS bus)
8
Slider for mounting on DIN rail
LED
Color
Activity
Meaning / Corrective action
RUN Green Continuously off No power supply.
Check power supply.
Continuously on
Power supply ok; firmware functions ok.
FLT
Red
Continuously off
Everything ok.
Continuously on
Hardware fault detected during self-test.
PXX-Lxx must be replaced.
Fast flashing No valid firmware present.
Reload firmware.
TX
Yellow
Flashing
Sending LonWorks® data packets
RX
Yellow
Flashing
Receiving LonWorks® data packets
SVC Red Continuously off Everything OK.
LonWorks® node configured
Continuously on
Faulty LonWorks® chip or service pin is being
pressed.
Flashing LonWorks® node not configured Configure
with LNS
Service button
Press with pointed object
FW download button
Press with pointed object
Extended Command
Set (ECS)
Housing
LED display,
service button