Albatros2 Boiler controller User Manual Edition 3.0 Controller series B CE1U2354en 23. August 2007 RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55..
/180 Siemens Schweiz AG HVAC Products User Manual CE1U2354en 23.
Contents 1 Summary ......................................................................................................... 9 1.1 Type summary............................................................................................... 10 1.1.1 Topology........................................................................................................ 10 2 Safety notes................................................................................................... 12 2.
3.8.2 Room unit QAA78.610 ...................................................................................27 Engineering....................................................................................................27 Mounting with base ........................................................................................27 Connection / power supply.............................................................................28 Radio connection .....................................................
.2.2 User levels..................................................................................................... 68 5.2.3 Overview of settings ...................................................................................... 69 5.3 QAA55... ........................................................................................................ 70 5.3.1 Operation....................................................................................................... 70 Operating elements ....
Flow temperature setpoint limits ....................................................................90 Room influence ..............................................................................................91 Room temp limitation .....................................................................................91 Mixing valve control .......................................................................................92 Dewpoint monitoring ........................................................
6.17 DHW storage tank ....................................................................................... 110 Charging control .......................................................................................... 110 Overtemperature protection......................................................................... 110 Recooling..................................................................................................... 110 Electric immersion heater ........................................
6.27 List of displays .............................................................................................151 6.27.1 Error code ....................................................................................................151 6.27.2 Maintenance code........................................................................................152 6.27.3 Special operation code ................................................................................152 7 Plant diagrams ................
1 Summary The present User Manual describes the products listed in the following table and covers handling and configuration of the controls for readers ranging from end users to heating engineers. Type reference (ASN) Series Name RVS43.143 RVS63.243 RVS63.283 AVS75.390 AVS37.294 AVS37.390 QAA75.610 QAA75.611 QAA78.610 QAA55.110 AVS16.290 AVS71.390 AVS14.390 AVS13.
1.1 Type summary 1.1.1 Topology Remote Wired Mobile, SMS, Pager, Fax, WEB, Room Unit Service Unit (RU) HMI (RU) Service Tool Telephone Network ACS700 HMI Telephone SMS wired wired wired OCI700 OCI611 BSB-W Extension mod. AVS75… (max. 2) Basic Unit RVSxx LPB BSB : Boiler System Bus Basic Unit RVS...
Operating options Wired Wireless Operation with room unit B B A A Operation with “basic” operator unit D T T (optionally with additional room unit) B E1 D F C B A E1 C 2359Z66 2359Z67 A Operation with “clear-text” operator unit (optionally with additional room unit) B E B A A B C D E E1 F E A Basic unit RVS… Power section AVS16… Room unit QAA75… / 78… / QAA55.. Outside sensor AVS13… Operator unit AVS37.294 (clear-text) Operator unit AVS37.
2 Safety notes 2.1 Product liability • The products may only be used in building services plant and applications as described above • When using the products, all requirements specified in the chapters on "Handling" and "Technical data" must be satisfied • Local regulations (for installation, etc.) must be complied with • Do not open the units. If not observed, warranty becomes void. 12/180 Siemens Schweiz AG HVAC Products User Manual Product liability CE1U2354en 23.
3 Mounting and installation 3.1 Regulations Electrical installation • Prior to installing the controller, the power supply must be turned off • The connections for mains and low-voltage are separated • The wiring must be made in compliance with the requirements of safety class II. This means that sensor and mains cables may not be run in the same duct 3.2 Basic units RVS… Engineering • Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it.
Mounting method On DIN rail Screwed A2 2359Z09 A1 B2 2359Z11 B1 A: Mounting / B: Removal Note: To mount the controller on a DIN rail, a mounting clip is required! Dimensions and drilling plan L L1 2358M01 B B1 Dimensions in mm RVS63… RVS43… Total height required 2359Z10 L 281 181 B 121 121 H 52 52 L1 270 170 B1 110 110 Dimension X: Connectors with tongues minimum 70 mm Connector without tongues minimum 60 mm x 14/180 Siemens Schweiz AG HVAC Products User Manual Basic units RVS…
3.2.1 Connection terminals of RVS43.143 050110A 000020 RVS43.143/109 S050110000020 2354Z08 1PRVS13.143/109 3.2.2 Z Connection terminals of RVS63.243 U U RVS63.243/109 U T S R Q P N L 061107B 000020 S061107000020 2354Z06 1PRVS63.243/109 15/180 Siemens Schweiz AG HVAC Products User Manual Basic units RVS… CE1U2354en 23.
3.2.3 Connection terminals of RVS63.283 RVS63.283/109 061107B 000020 S061107000020 2354Z07 1PRVS63.283/109 16/180 Siemens Schweiz AG HVAC Products User Manual Basic units RVS… CE1U2354en 23.
Terminal markings Mains voltage L N L1 S3 L1 N T1 T2 S3 4 SK1 SK2 N Q3 N Q2 Y1 N Y2 N QX1 N Q6 Y5 N Y6 N QX2 N QX3 EX2 FX4 (T6) QX4 (T7) QX4 (T8) Use Slot Live AC 230 V basic unit Protective earth Neutral conductor Live AC 230 V burner Output burner fault Phase burner Protective earth Neutral conductor Phase 1st burner stage 1st burner stage on Input burner fault Input 1st burner stage operating hours Safety loop Safety loop Neutral conductor Protective earth DHW charging pump / diverting valve Neutral c
Use Slot BSB LPB X60 X50 X30 Service tool OCI700 Service tool OCI700 Radio module AVS71.390 Extension module AVS75.390 Operator unit / boiler control panel - DB MB LPB data LPB ground AGP4S.02H/109 CL+ CL- BSB data BSB ground AGP4S.02A/109 b CL+ CL- Room unit 2 data Room unit 2 ground b CL+ CL- Room unit 1 data Room unit 1 ground b Low voltage Connector type - AVS82.490/109 AVS82.491/109 AGP4S.
3.3 Extension module AVS75.390 For planning, mounting location and mounting method, refer to the information given for the basic modules. Dimensions and drilling plan L L1 2358M01 B1 B Dimensions in mm AVS75.390 Connections L 108.7 B 120.9 H 51.7 L1 98 B1 110 The AVS75.390 extension module is connected to terminal X50 of the basic unit using the AVS83.490/109 connecting cable. The connectors are coded. 3.3.1 Connection terminals of AVS75.390 AVS75.
Terminal markings Mains voltage L N QX21 N QX22 N QX23 Use Slot Live AC 230 V basic unit Protective earth Neutral conductor Assignment according to function Neutral conductor Protective earth Assignment according to function Neutral conductor Protective earth Assignment according to function N Connector type L T AGP8S.04B/109 S AGP8S.03B/109 Connector type AVS82.491/109 AVS82.
3.4 Operator unit AVS37.294 Mounting method Installation 2358Z32 2358Z30 2358Z31 Removal Connections The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded. Ground 90 96 2358M03 27 17 144 Panel cutout 42.4 (144) 138 +1 0 (96) 2358M05 92 +0.8 0 0.5...3.0 21/180 Siemens Schweiz AG HVAC Products User Manual Operator unit AVS37.294 CE1U2354en 23.
3.5 Operator unit AVS37.390 Connections The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded. 2354M01 Dimensions A 0,5 13 A Control panel, front 22/180 Siemens Schweiz AG HVAC Products User Manual Operator unit AVS37.390 CE1U2354en 23.
3.6 Room unit QAA55… Engineering @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
3.7 Room unit QAA75… Engineering @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
Dimensions and drilling plan 60 2359Z50 185 100 56 4,2 56 100 60 80 82 42 2359Z12 25/180 Siemens Schweiz AG HVAC Products User Manual Room unit QAA75… CE1U2354en 23.
3.8 Wireless components The wireless components should be located such that transmission will be as interference-free as possible. The following criteria must be observed: • Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs, TV sets, microwave ovens, etc. • Not near larger metal structures or constructional elements with fine metal meshes such as special glass or special concrete • The distance to the transmitter should not exceed 30 meters or 2 floors 3.8.
3.8.2 Room unit QAA78.610 Engineering @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
2359Z61 Mounting without base Connection / power supply The room unit is powered by 3 pieces 1.5 V alkaline batteries type AA (LR06). Radio connection Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach. Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
Example of a display during the test: The digits on the left shows telegrams that have been sent, the digits on the right telegrams that have been received. The test will be ended after 24 telegrams. The test is considered successful when at least 50 % of the telegrams sent have been received. Bedieneinheit Testmode If the test was not successful, some other mounting location is to be selected or the AVS14.390 radio repeater can be used.
3.8.3 • • Wireless outside sensor AVS13.399 The radio transmitter must be installed inside the building. The radio transmitter’s mounting location should be chosen such that batteries can be easily changed. Mounting method Outside sensor 2359Z53 2359Z31 2359Z59 2359Z32 2359Z30 2359Z54 2359Z33 RF transmitter 2359Z55 AAA AAA Battery Connections Battery transit tab The outside sensor is to be connected to the radio transmitter via a 2-core cable, the connections are interchangeable.
Radio connection 2359Z58 AAA AAA Establishing the link Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach. Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit. 1.
3.8.4 Radio repeater AVS14.390 • To establish the radio connection, the device must be provisionally connected to power prior to mounting, enabling the radio connection to be opened and tested. • The radio repeater must be fitted inside the building. Mounting method 2359Z33 2 4 2359Z30 2359Z31 1 Connections Power is supplied via the enclosed power pack. The wires are interchangeable.
3.8.5 Checking the wireless components To check whether the connections to the required system components are operational, consult operating lines 130 through 135 on operating page “Wireless“ (operating level “Commissioning“). 3.9 Power supply AVS16.290 Mounting notes The boiler control panel is designed for installation in floor-standing or wall-hung oil or gas boilers and may only be used for that purpose.
3B 1A 4B 2A 1A 2358A16 S1 H1 3B1 1 1 Si C 2 STB 2 PE L L N N1 L1 S3 1 2 3 4 Mains supply to 5 RVS… basic unit Si Fuse 6.3AT S1 Mains switch with green glow lamp STB = SLT Safety limit thermostat 110°C H1 Signal lamp‚ SLT has cut out 35 Dimensions 48 96 2358M02 96 90 80 (96) 2358M04 92 (96) 92 +0.8 0 0.5...3.0 +0.8 0 34/180 Siemens Schweiz AG HVAC Products User Manual Power supply AVS16.290 CE1U2354en 23.
4 Prerequisites Commissioning To commission the units, the following working steps must be carried out: • Prerequisite is the correct mounting and correct electrical installation and, in the case of wireless solutions, correctly working radio connections to all required auxiliary units. • Make all plant-specific settings. Special attention must be paid to operating page ”Configuration“.
5 Handling 5.1 QAA75.. / QAA78… / AVS37.. 5.1.
Display options Heating to Comfort setpoint Info level activated Heating to Reduced setpoint Programming activated Heating to frost protection setpoint Heating temporarily switched off ECO function active Process running – please wait Holiday function active Change battery Reference to heating circuit Burner operating (only oil / gas boiler) Maintenance / special operation Error messages Display of all symbols and segments.
• Protective functions active • Automatic summer / winter changeover (ECO functions) and automatic 24-hour heating limit active Selection of cooling mode The "Cooling" mode is selected by use of the Cooling button. The choice made is indicated by a bar which appears below the symbol. Cooling mode Cooling mode controls the room temperature in accordance with the time program.
Presence button If you do not use the rooms for a certain period of time, you can press the presence button to reduce the room temperature, thus saving heating energy. When the rooms are occupied again, press again the presence button to resume heating operation.
A list of possible displays is given on page 150. The reset function for meters and the resettable parameters appears on the bottom line of the display, provided a reset is permitted on the current operating line (end user / commissioning / heating engineer). Reset ? 0 4 yes 8 12 16 20 2359Z140 Reset function 24 yes Reset ? 0 4 8 12 16 20 2359Z140 After activation with the OK button, the display will show a flashing “Yes“.
5.1.2 Programming Setting principle Settings that cannot be made directly with the operating elements require programming. For this purpose, the individual settings are structured in the form of operating pages and operating lines, thus forming practical groups of settings. The following example shows how to set the time of day and the date.
5 The display shows the minutes flashing. Turn the setting knob until the minutes of the time of day are correct. AUTO 2359Z140 Time of day and date Hours / minutes 4 0 8 6 12 16 20 To confirm, press OK. 24 The settings are saved and the displays stops flashing. Now, you can make further settings or you press the operating mode button to return to the basic display.
You are now on the required user level. AUTO 0 4 8 12 2359Z140 Time of day and date Text3 section Operator 16 20 24 To reach the OEM level, the relevant code must be entered. Setting the structure “End user“ The example given here shows that certain user levels do not allow certain settings to be made. The example shows them highlighted. On the unit, they are hidden.
5.1.4 Min Max Unit Function User level Time of day and date 1 E Hours/minutes 2 E Day/month 3 E Year 5 F Start of summertime 6 F End of summertime Operator unit 20 E Language Default value The table shows all available settings up to the heating engineer level. However, certain operating lines may be hidden, depending on the type of unit. E = End user I = Commissioning F = Heating engineer BZ = Operating line 1) QAA75../78.. only 4) RVS43.. only 6) RVS63..
Default value - Unit Function OutsideSens Max User level I Min Operating line 133 - - - Missing ¦ Ready ¦ No recept’n ¦ Change batt 134 I RF repeaters Missing ¦ Ready ¦ No recept’n ¦ Change batt 135 I Operator unit 1 - Missing ¦ Ready ¦ No recept’n ¦ Change batt 136 I Operator unit 2 - Missing ¦ Ready ¦ No recept’n ¦ Change batt 137 I Operator unit P - - - - No - Mo - Su - Missing ¦ Ready ¦ No recept’n ¦ Change batt 138 I Service unit Missing ¦ Ready ¦ No recept’n ¦
Default value 24:00 24:00 24:00 24:00 No Unit Function 2nd phase on 2nd phase off 3rd phase on 3rd phase off Standard values Max User level E E E E E Min Operating line 563 564 565 566 576 00:00 00:00 00:00 00:00 24:00 24:00 24:00 24:00 hh:mm hh:mm hh:mm hh:mm - No ¦ Yes Time program 5 600 E Preselection Mo - Su - Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su 601 602 603 604 605 606 616 E E E E E E E 1st phase on 1st phase off 2nd phase on 2nd phase off 3rd phase on 3rd
Max Unit F F F F F 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Room influence Room temp limitation Boost heating Quick setback -3 − − − / -10 8 8 80 Operating line 740 20 −−−/1 1 − − − / 0.
3-position 20 873 °C s − − − / 10 −−−/1 0 −−−/0 600 10 100 10 min °C % °C Op. line 1012 Op. line 1014 4 Op. line 1010 0.10 -4.5 Operating line 1016 Operating line 1010 Operating line 1012 35 4.00 4.5 °C °C °C °C °C - 18 −−−/8 -3 − − − / -10 8 8 80 Op. line 1040 20 −−−/1 1 − − − / 0.
Default value Yes Unit Function With buffer storage tank Max User level F Min Operating line 1170 - No ¦ Yes 1172 F With primary controller / system pump Yes No ¦ Yes 11826) F 11836) F 1200 F Pump speed min Pump speed max Changeover of operating mode 100 0 100 0 Protection mode 100 100 % % None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic Heating circuit P 1300 E Operating mode Automatically - Protection ¦ Automatic ¦ Reduced ¦ Comfort 1310 1312 1314 1316 1320 1321 1326 E E E F
Unit 55 Op. line 1612 40 8 Time programs HCs Max Default value Nominal setpoint Reduced setpoint Release Min Function User level Operating line DHW 1610 E 1612 F 1620 I Op.
Default value Yes Unit Function With solar integration Max User level F Min Operating line 2080 No ¦ Yes Primary controller / system pump 2150 I Primary controller / system pump After buffer st tank - Before buffer st tank ¦ After buffer st tank Boiler 2203 F 2205 F Release below outside temp Economy mode −−− Off − − − / -50 50 °C Setpoint manual operation BZ 2213 OEM °C Off ¦ On DHW ¦ On 2210 F Setpoint min 40 BZ 2211 OEM 2212 F Setpoint max 80 2270 F 2330 F 2331 F 23406) F
Max Unit Min Default value Function User level Operating line Solid fuel boiler 4102 F Locking other heat sources 120 40 40 °C °C °C On Off ¦ On 4110 4130 4131 4133 F F F F Setpoint min Temperature differential ON Temp diff off Comparative temp 40 8 8 1 4 0 Setpoint min DHW sensor B3 ¦ DHW sensor B31 ¦ Buff st tank sensor B4 ¦ Buff st tank sensor B41 ¦ Flow temp setpoint ¦ Setpoint min Buffer storage tank 4720 F Auto generation lock With B4 - None ¦ With B4 ¦ With B4 and B42/B41 4722 47
Default value No Unit Function With buffer storage tank Max User level F Min Operating line 5090 40 100 0 0 100 100 % % 4 60 0 7.
Unit Max Min Default value Function User level Operating line exch K9 ¦ Solar ctrl elem buffer K8 ¦ Solar ctrl elem swi pool K18 ¦ Collector pump 2 Q16 ¦ H3 pump Q19 ¦ Flue gas relay K17 ¦ Assisted firing fan K30 ¦ Cascade pump Q25 ¦ St tank transfer pump Q11 ¦ DHW mixing pump Q35 ¦ DHW intern circ pump Q33 ¦ Heat request K27 ¦ Refrig. request K28 ¦ Air dehumidif.
Unit Max Min Default value Function User level Operating line ¦ Solid fuel boiler sensor B22 ¦ DHW charging sensor B36 ¦ Buffer sensor B42 ¦ Common return sensor B73 ¦ Cascade return sensor B70 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 5933 6) I Sensor input BX4 None None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return sensor B7 ¦ DHW circulation sensor B39 ¦ Buffer st tank sensor B4 ¦ Buffer st tank sensor B41 ¦ Flue gas temp sensor B8
Default value Heating circuit Unit Function Function mixing group 1 Max User level I Min Operating line 6014 - None - None - Heating circuit 1 ¦ Return temp controller ¦ Prim contr/system pump ¦ DHW primary controller ¦ Instantaneous DHW heater ¦ Return controller cascade ¦ Cooling circuit 14) ¦ Heating circuit / Cooling circuit 14) 6015 6) I Function mixing group 2 Heating circuit 2 ¦ Return temp controller ¦ Prim contr/system pump ¦ DHW primary controller ¦ Instantaneous DHW heater ¦ Ret
Unit Max Min Default value Function User level Operating line Collector pump 2 Q16 ¦ H3 pump Q19 6)¦ Flue gas relay K17 ¦ Assisted firing fan K30 ¦ Cascade pump Q25 ¦ St tank transfer pump Q11 ¦ DHW mixing pump Q35 ¦ DHW interm circ pump Q33 ¦ Heat request K27 ¦ Refrig. request K28 4) ¦ Air dehumidif.
Function Default value Readjustm coll sensor 2 Readjustm outside sensor Sensor type flue gas temp 0 -20 0 -3.0 NTC 10k 20 3.
Default value No Unit Function Reset alarm relay Max User level I Min Operating line Fault 6710 - No ¦ Yes 6740 6741 6743 6745 67464) 6800 F Flow temp 1 alarm F Flow temp 2 alarm F Boiler temp alarm F DHW charging alarm F Flow temp alarm, cooling 1 F History 1 F Error code 1 6802 F History 2 F Error code 2 6804 F History 3 F Error code 3 6806 F History 4 F Error code 4 6808 F History 5 F Error code 5 6810 F History 6 F Error code 6 6812 F History 7 F Error code 7 6814 F History 8 F Error code
No test Unit Max Min Default value Function User level Operating line Input / output test 7700 I Relay test - No test ¦ Everything off ¦ 1st burner stage T2 ¦ 1st + 2nd burn stage T2/QX4 6) ¦ DHW pump Q3 ¦ Heating circuit pump Q2 ¦ Heat circ mix valve op Y1 ¦ Heat circ mix valve cl Y2 ¦ Heating circuit pump Q6 6) ¦ Heat circ mix valve op Y5 6) ¦ Heat circ mix valve cl Y66) ¦ Relay output QX1 ¦ Relay output QX2 6) ¦ Relay output QX3 6) ¦ Relay output QX4 6) ¦ Relay output QX21 module 1 ¦ Relay outp
Min Max Unit Default value Function User level Operating line 0 0 0 0 0 140 140 140 140 990 °C °C °C °C h 8010 I State buffer storage tank 8011 I State swimming pool Diagnostics cascade 8100 I Priority source 1…16 to.. 8130 8101 I State source 1...16 Missing ¦ Faulty ¦ Manual control active ¦ Heat to..
Default value Min Max Unit Function User level Operating line 8531 F Hours run collect overtemp 85436) F Speed collector pump 2 8547 I Collector temp 2 8548 I Collector temp 2 max 8549 I Collector temp 2 min 8550 I dT collector 2/DHW 8551 I dT collector 2/buffer 8552 I dt collector 2/swimming pool 8560 Solid fuel boiler temp 8570 E Hours run solid fuel boiler Diagnostics consumers 8700 I Outside temperature 8703 I Outside temp attenuated 8704 I Outside temperature composite 4) Relative room humidity
Max Unit F F I I I I I I I I I I I I I I I I I I I I I I I I I I I I I Min 88256) 88266) 8830 8831 8832 8835 8836 8850 8851 8852 8853 8900 8901 8930 8931 8950 8951 8952 89574) 8962 8980 8981 8982 8983 9000 9001 90046) 9005 9006 90096) 9031 Default value User level I I I I Function Operating line 8800 8801 8803 8820 Room temp P Room setpoint P Flow temp setpoint P DHW pump Q3 - 0.0 4.0 0.0 50 35 140 °C °C °C - 0 0 0 0 0 0 0 0 24 0 0 0 0 0 8 0 - 0 0 0.0 8.0 0.0 0.0 0 0 0 0 0 0 8 0.0 0.0 0.
Default value - Unit Function Relay output QX21 module 2 Max User level I Min Operating line 9053 - - - - - Off ¦ On 9054 I Relay output QX22 module 2 Off ¦ On 9055 I Relay output QX23 module 2 Off ¦ On 64/180 Siemens Schweiz AG HVAC Products User Manual QAA75.. / QAA78… / AVS37.. CE1U2354en 23.
5.2 AVS37.390 5.2.1 Operation Operating elements Selection of op. mode Displaying information Chimney sweep function STB test + OK - - ESC 2354Z12 + Adjustment of room Comfort setpoint Navigation and settings Adjustment of DHW nominal setpoint Navigation and settings The above illustration shows an example of the front of an operator unit (not supplied as standard).
Adjusting the room temperature setpoint Press the + / - buttons to increase or decrease the Comfort setpoint . For the Reduced setpoint − Press OK − Select the operating line for the “Reduced setpoint” + OK After each readjustment, wait at least 2 hours, allowing the room temperature to adapt. Adjusting the nominal DHW setpoint Press the + / - buttons to increase or decrease the nominal DHW setpoint.
3.1.2 Programming Setting principle Settings that cannot be made directly with the operating elements require programming.
4 The display shows the minutes flashing. Press the "+/-" button until the minutes of the time of day are correct. 1 2354Z13 + Press OK to confirm. 5 2354Z13 1 The settings are saved and the displays stops flashing. Now, you can make further settings or You can press the operating mode button to return to the basic display. 2354Z13 1 6 Now, you see the basic display again. 5.2.2 User levels The user levels only allow authorized user groups to make settings.
5.2.
5.3 QAA55... 5.3.1 Operation 2358Z34 Operating elements Selecting the operating mode Adjustment of room Comfort setpoint Presence button Display options Burner operating (only oil / gas boiler) Heating to Reduced setpoint Error messages Example of basic display: 2354Z09 Display of all displayable symbols and segments. 2354Z09 Display Heating to Comfort setpoint Selection of space heating mode This setting is used to switch between the different operating modes.
Continuous operation or Continuous operation maintains the room temperature at the selected operating level. Heating to Comfort setpoint Heating to Reduced setpoint Characteristics of continuous operation: • Heating mode with no time program • Protective functions active • Automatic summer / winter changeover (ECO functions) and 24-hour heating limit inactive in the case of continuous operation with Comfort setpoint Protection When using Protection, the heating system is off.
5.3.2 Programming Configuration Settings Used as A long press on the presence button enables the service level to be accessed. ru = 1 (factory setting) ru = 2 ru = 3 The room unit is addressed as room unit 1 The room unit is addressed as room unit 2 The room unit is addressed as room unit 3 Direct adjustment P1 = 1 (factory setting) Automatic storage: A setpoint readjustment with the knob is adopted either by pressing the operating mode button or without any further confirmation (timeout).
6 The settings in detail 6.1 Time of day and date The controller has a yearly clock with time of day, weekday and date. To ensure the controller’s functionality, both the time of day and the date must be correctly set. Summer- / wintertime changeover Line no.
Used as Line no. Operating line 40 Used as Room unit 1 Room unit 2 Room unit P Operator unit 1 Operator unit 2 Operator unit P Service unit This operating line is used to select the use of the operator unit. Depending on use, additional settings will then be required under “Heating circuit assignment“. When using several operator units, it is thus possible to match individual units to specific requirements. • In the case several operator units are used, each application may only be used once.
Heating circuit assignment Line no. Operating line 42 Assignment device 1 Heating circuit 1 Heating circuits 1 and 2 Heating circuits 1 and P All heating circuits 44 Operation HC2 Commonly with HC1 Independently 46 Operation HCP Commonly with HC1 Independently 48 Action of presence button None. Heating circuit 1 Heating circuit 2 Jointly Assignment device 1 As room unit 1 (setting 40), the action of the relevant operator unit on heating circuit 1 or on both heating circuits can be assigned.
6.3 Radio Binding Binding Test mode Line no. Operating line 120 121 Binding Test mode For more detailed information, refer to the descriptions of the wireless components in section 3.8. When commissioning the system, the wireless peripheral devices (room unit) are assigned to the basic unit. The test mode is used for checking the wireless communication. The test should be made when the installation is fully completed. List of wireless devices Line no.
Switching points HC1 HC2 500 520 Line no. 3/HCP 4/DHW 5 540 560 600 Operating line Preselection Mo - Su Mo - Fr Sa - Su Mo - Su 501 502 503 504 505 506 521 522 523 524 525 526 541 542 543 544 545 546 561 562 563 564 565 566 601 602 603 604 605 606 1st phase on 1st phase off 2nd phase on 2nd phase off 3rd phase on 3rd phase off Standard program Line no. Operating line 516, 536, 556, 576, 616 Default values All time programs can be reset to their default settings.
Setpoints HC1 710 712 714 716 Room temperature. Line no. HC2 1010 1012 1014 1016 Operating line HCP 1310 1312 1314 1316 Comfort setpoint Reduced setpoint Frost protection setpoint Comfort setpoint max The room temperature can be shifted according to different setpoints. These setpoints become active depending on the selected operating mode, thus producing different temperature levels in the rooms.
Heating curve displacement Heating curve adaption Parallel displacement of the heating curve is used to change the flow temperature evenly across the entire outside temperature range or, in other words, if the room temperature is always too high or too low, a readjustment must be made with the help of the parallel displacement. Adaptation of the heating curve is used by the controller to automatically adapt the heating curve to the prevailing conditions.
• The function is not active in operating mode ”Continuously Comfort temperature“ • The display shows ECO • To incorporate the building's thermal dynamics, the outside temperature is attenuated Example: T TAged °C 20 19 SWHG +1 °C 17 SWHG 16 SWHG -1 °C 2358Z08 18 ON OFF 0 SWHG TAged T t 24-hour heating limit 5 10 15 t Summer/winter heating limit The attenuated outside temperature Temperature Days The 24-hour heating limit is used to switch the heating on and off in the course of the day,
TV TVmax max TVw 2358Z09 Using this limitation, a temperature range for the flow temperature setpoint can be defined. If the flow temperature setpoint demanded by the heating circuit reaches the relevant limit and the heat request increases or decreases, the flow temperature setpoint will be maintained at the maximum or minimum limit.
Room compensation only The flow temperature is controlled depending on the room temperature setpoint, the current room temperature and the progression of the room temperature. For example, a slight increase of the room temperature causes an immediate drop of the following temperature. To activate the function, following must be considered: • A room sensor must be connected. • “Room influence“ must be set to 100 %.
°C TR w DTRSA 2371D03 20 TR x 15 t TRw Room temperature setpoint TRx Actual value of the room temperature DTRSA Increase of the room temperature setpoint Quick setback HC1 780 Line no. HC2 1080 Operating line HCP 1380 Quick setback Off Down to reduced setpoint Down to frost prot setpoint During quick setback, the heating circuit pump is deactivated and, in the case of mixing valve circuits, the mixing valve is fully closed.
Optimum start / stop control HC1 790 791 Line no. HC2 1090 1091 Operating line HCP 1390 1391 Optimum start control max Optimum stop control max Optimum start control max The change from one temperature level to the other is optimized in a way that the Comfort setpoint is reached at the relevant switching time.
TR TRwA1 TRwA2 TRK 2358Z06 TRR -5 -15 TRwA1 TRwA2 TRK TRR TAgem TAgem Reduced setp increase start Reduced setp increase end Comfort cooling setpoint Reduced room temperature setpoint Composite outside temperature Overtemp prot pump circuit HC1 820 Line no.
Floor curing function Line no. HC2 HC1 850 Operating line HCP 1150 1450 Floor curing function Off Functional heating (Fh) Curing heating (Bh) Functional/curing heating Curing heating/ functional heating Manually 851 1151 1451 1455 1456 1457 RVS43.. only Floor curing function Floor curing setp manually Floor curing setp current Floor curing day current Floor curing days complete The floor curing function ensures controlled drying of the floor.
Floor curing setp manual The flow temperature setpoint for the "Manual" floor-curing function can be set separately for each heating circuit. Floor curing setp current Shows the current flow temperature setpoint of the floor-curing process in progress Floor curing day current Shows the current day of the floor-curing process in progress. Excess heat draw HC1 861 Line no.
RVS43.. only 6.7 Cooling circuit For the operation of a cooling circuit, the cooling function must be enabled (operating line 901) and released in accordance with a time program (operating line 907). The system automatically operates in cooling mode when the room temperature rises above the Comfort cooling setpoint (operating line 902).
Cooling curve Flow temperature setpoint Line no. Operating line 908 909 Flow setpoint at outside temperature of 25°C Flow setpoint at outside temperature of 35°C The controller determines the required flow temperature at a specific composite outside temperature. The cooling curve is determined by defining two fixed points (the flow temperature setpoint at 25°C and 35°C). The programmed cooling curve is based on a room setpoint of 25°C.
Start of summer compensation at OT Summer compensation starts to take effect at the outside temperature set here. If the outside temperature continues to rise, the comfort setpoint is raised in parallel. End of summer compensation at OT Summer compensation takes full effect at this outside temperature (920). The comfort setpoint is not affected by any further increase in the outdoor temperature.
Room influence Compensation variants Line no. Operating line 928 Room influence When a room temperature sensor is used, there is a choice of 3 different types of compensation. Setting Type of compensation − − −% 1…99 % Weather compensation only * Weather compensation with room influence Room compensation only 100 % * Outside sensor required. Weather compensation only The flow temperature is calculated via the cooling curve as a function of the composite outside temperature.
The cooling circuit pump is activated again as soon as the room temperature returns to a level above the current room temperature setpoint. While the “Room temperature limitation“ function is active, no cooling request is sent to the heat source. The function is deactivated in the following circumstances: • • • No room temperature sensor "Room temp limitation" = --"Room influence“ (928) = --- (weather compensation only) °C TRx TRx TRKw TRKw-SDR Actual value room temp TRKw Room temp.
Controls The valve is used for control in heating and cooling mode. Open The valve is used for control in cooling mode and is open in heating mode. Dewpoint monitoring Line no. Operating line 946 947 948 950 Dewpt monitor locking time Flow setpt increase hygro Start flow increase at R.H. Flow temp diff dewpoint Dewpt monitor locking time When the connected dewpoint monitor detects the formation of condensation it closes the contact, thereby deactivating the cooling.
T TVKw TTP BZ 950 TA TVKw TTP OT BZ Flow temperature setpoint, cooling Dew point temperature Outside temperature Operating line Buffer storage tank / primary controller Line no. Operating line 962 With buffer storage tank 963 With primary controller / system pump No ¦ Yes No ¦ Yes With buffer storage tank If there is a buffer storage tank, this setting defines whether the cooling circuit can draw cooling energy from it.
6.8 DHW Setpoints Line no. Operating line 1610 1612 Nominal setpoint reduced setpoint The DHW can be heated up according to different setpoints. These setpoints are activated depending on the selected operating mode, thus leading to different temperature levels in the DHW storage tank. TWWN TWWmax 0 10 20 30 40 2358Z11 TWWR 50 60 70 80 90 100 °C TWWR DHW reduced setpoint TWWN DHW nominal setpoint TWWmax DHW nominal setpoint maximum Priority Line no.
1642 Legionella funct weekday 1644 1645 Legionella funct time Legionella funct setpoint 1646 1647 Legionella funct duration Legionella funct circ pump Monday…Sunday Legionella function • Periodically The legionella function is repeated according to the period of time set (operating line 1641). The legionella setpoint is attained via a solar plant, independent of the period of time set, the period of time will be newly started.
Excess heat draw Excess heat draw can be triggered by the following functions: − Inputs H1, H2, H3 or EX2 − Storage tank recooling − Solid fuel boiler excess heat draw When dissipation of excess heat is activated, it can be drawn by space heating. This can be adjusted separately for each heating circuit. With buffer storage tank If there is a buffer storage tank, this defines whether the H1/H2/H3 circuit can draw heat from it.
If the swimming pool is enabled via one Hx input, the swimming pool priority is equivalent to the parameter setting. Solar heating must now be enabled via the Hx input. If two Hx inputs are used to enable the swimming pool, the swimming pool takes priority when both Hx inputs are enabled. If only one Hx input is enabled, the swimming pool priority is determined by the parameter setting. If none of the Hx inputs are enabled, solar heating of the swimming pool is deactivated. Plant hydraulics Line no.
In normal operation, minimum limitation of the boiler temperature is the lower limit value of the controlled boiler temperature setpoint, depending on the boiler’s operating mode. In normal operation, maximum limitation of the boiler temperature is the upper limit value of the controlled boiler temperature setpoint and, at the same time, setpoint of the electronic limit thermostat (TR). The setting range of setpoint minimum and setpoint maximum is limited by the setpoint of manual operation.
2 x 1 cascade RVS63.. only Line no. Operating line 2340 Auto source seq 2x1 casc Automatic changeover of the heat source enables a lead boiler change at certain intervals. The boiler sequence changes when the selected time has elapsed. When switching on automatic changeover, heat source 1 (T2) is always started up as the lead boiler. The time remaining until the next changeover takes place and the current lead boiler are not displayed. 6.13 Cascade Control Line no.
1st changeover 2nd changeover 3rd changeover 4th changeover P [kW] K1 K2 K3 K3 K4 K1 K2 K2 K3 K4 K1 K1 K2 K3 K4 Lag boiler Lead boiler 2379Z07 K4 100 t P Auto source seq exclusion 200 300 400 t [h] = Total number of operating hours of all lead boilers [h] = Total output of cascade [kW] Setting automatic source sequence exclusion is only used in connection with the activated heat source sequence (operating line 3540).
6.14 Solar Charging controller (dT) Line no. Operating line 3810 3811 3812 3815 3818 Temperature differential ON Temp diff off Charg temp min DHW st tank Charging temp min buffer Charging temp min swi pool For charging the storage tank via the heat exchanger, the temperature differential between collector and storage tank/swimming pool must be sufficient, and the collector must have reached the minimum charging temperature for the storage tank/swimming pool.
DHW storage tank During solar charging, preference is given to the DHW storage tank. At every level A, B or C (see below), it is charged with priority. Only then will the other consumers of the same level be charged. As soon as all setpoints of a level are attained, those of the next level are approached, whereby priority is again given to the DHW storage tank. Buffer storage tank During solar charging, preference is given to the buffer storage tank.
Frost protection for the collector Line no. Operating line 3840 Collector frost protection When there is risk of frost at the collector, the collector pump will be activated to prevent the heat-carrying medium from freezing. • If the collector temperature falls below the frost protection temperature, the collector pump will be activated: TKol < TKolFrost.
Yield measurement Line no. Operating line 3880 3881 3884 Antifreeze Antifreeze concentration Pump capacity The 24-hour and total solar energy yield (operating lines 8526 and 8527) is calculated, based on these data. Antifreeze Pump capacity Since the mixing ratio of the collector medium has an impact on heat transmission, the type of antifreeze used and its concentration must be entered in order to be able to determine the energy yield.
T TKx SDon 2359Z138 SDoff Bx On QX Off TKx Bx On / Off SDon SDoff t Boiler temp Actual value of comparison temperature Boiler pump Temperature differential ON Temp diff off 6.16 Buffer storage tank Automatic locks Line no. Operating line 4720 Auto generation lock None. With B4 With B4 and B41 / B42 4722 4723 4724 4726 Temp diff buffer/HC Temp diff buffer/CC Min st tank temp heat mode Max stor temp cooling mode Auto generation lock None Function is deactivated.
2355Z14 T TVLw B4 4722 1K E 4722 B4 TVLw E Temp diff buffer/CC Temp diff buffer/HC Upper buffer or combi storage tank sensor Flow temperature setpoint Heat generation lock t If the temperature differential ∆T between the buffer storage tank and the cooling request from the cooling circuit is sufficiently large, the cooling energy required by the cooling circuit will be drawn from the buffer storage tank. The refrigeration source is locked.
Off: The stratification protection function is switched off. Always: The stratification protection function is active when the source (generator) is enabled. With solid fuel boiler The stratification protection function is active only if the solid fuel boiler is enabled. 2358A42 A common flow sensor B10 must be connected for this function. Overtemperature protection Line no.
return temperature increase or return temperature decrease (to be selected on operating line 4796). This is defined on operating line 4796. In addition, the setting of the respective relay output is to be made as “Buffer diverting valve Y15” in configuration “Relay output QX1, 2 ,3, 4” (operating lines 5890, 5891, 5892 and 5894) and the common return temperature sensor (B73) at BX. Temp diff on/off return div The selected temperature differential defines the switch-on / off point of return diversion.
B4/B42 1 0 Cooling If the buffer storage tank was used to satisfy a heating request, it will be locked to all refrigeration demand signals for 24 hours. 6.17 DHW storage tank Charging control Line no. Operating line 5020 5021 5022 Flow setpoint boost Transfer boost Type of charging With B3 With B3 and B31 With B3, legio B3 and B31 Increase of the flow temperature setpoint The DHW request to the boiler is made up of the current DHW setpoint plus the adjustable charging boost.
Recooling heat gen/HCs Recooling collector • Heating energy can be drawn off either by space heating or the DHW storage tank. This can be selected separately for each heating circuit (operating page heating circuit 1…). • If the collector is cold, the energy can be emitted to the environment via the collector’s surfaces. Electric immersion heater Line no.
2358Z26 Time program 4 / DHW For the electric immersion heater, time program 4 / DHW of the local controller is taken into account. Example: 0 El immersion heater control 6 12 18 24 h External thermostat The storage tank is charged with an external thermostat without setpoint compensation of the controller. DHW sensor The storage tank is charged with an electric immersion heater, with setpoint compensation from the controller.
Mixing valve control Actuator running time Line no. Operating line 5544 Actuator running time Setting the running time of the actuator used with the mixing valve. 6.19 Configuration Heating circuits HC1 Line no. HC2 5710 5715 Operating line Heating circuit 1, 2 Using this setting, the heating circuits can be switched on and off. RVS43.. only Line no.
Use of mixing valve 1 Heating Cooling Heating and cooling HC/CC B1 HC/CC B1 T T Q2 Q2 Y21 Y21 Y1/Y2 H H Y1/Y2 C C The setting is required when a QX… relay output (configuration) is used as a diverting cooling valve Y2. DHW sensor B3 Line no. Operating line 5730 DHW sensor B3 Sensor Thermostat Sensor The collector calculates the switching points including the switching differential from the DHW setpoint and the acquired DHW storage tank temperature.
Separate DHW circuit Line no. Operating line 5736 Separate DHW circuit The separate circuit can only be employed if a boiler cascade is used. OFF: The separate circuit is switched off. Every boiler in use can charge the DHW storage tank ON: The separate circuit is switched on. DHW charging takes place exclusively via the boiler defined for that purpose. For the separate circuit, DHW controlling element Q3 must be set to “Diverting valve”! Boiler Line no.
Connections: L1 N T1 T2 S3 4 EX2 FX4 (T6) QX4 (T7) QX4 (T8) Modulating 3-position Modulating UX Use Space Connector type Phase burner Protective earth Neutral conductor Phase 1st burner stage 1st burner stage on Input burner fault Input 1st burner stage hours run Input 1st burner stage hours run Phase 2nd burner stage P AGP8S.07A/109 Z AGP8S.
Burner control • 3-position control and modulating UX The actuator is controlled in PID mode. By setting the proportional band (Xp), the integral action time (Tn) and the derivative action time (Tv), the controller can be matched to the type of plant (controlled system). Also, the actuator running time is to be set. • Neutral zone For control operation, a neutral zone is used which is at +/- 1K about the current boiler temperature setpoint.
2 x 1 cascade The 2x1 cascade is a special configuration of the basic unit, where the 2-stage boiler is operated as 2 cascaded 1-stage boilers. T 2 QX4 B2 1 T2 QX2 (Q1) QX1 (Q1) Due to the temperature differential between boiler temperature setpoint and boiler temperature sensor B2 (common, mandatory cascade flow temperature sensor), switching on / off of the lag boiler (release and reset integral) takes place according to the control of a 2-stage burner. The same parameters are used.
When using a charging pump, all heat exchangers can be used at the same time. Either parallel or alternative operation is possible. External solar exchanger In the case of solar plants with 2 storage tanks, it must be selected whether the external heat exchanger shall be used jointly for DHW and as a buffer storage tank, or exclusively for one of the two. Output relay QX Line no.
Collector pump Q5 When using a solar collector, a circulating pump for the collector circuit is required. Pump H1 Q15 Pump H1 can be used for an additional consumer. Together with an external request for heat at input H1, it is possible to operate an air heater or similar. Boiler pump Q1 The connected pump is used for circulating the boiler water. Bypass pump Q12 The connected pump serves as a boiler bypass pump for maintaining the boiler return temperature.
Heat gen shutoff valve Y4 If the buffer storage tank holds a sufficient amount of heat, the consumers can draw their heat from it, and the heat sources need not be put into operation. Automatic heat generation lock locks the heat sources and hydraulically disconnects them from the rest of the plant with the help of heat source shutoff valve Y4. This means that the heat consumers draw their energy from the buffer storage tank and wrong circulation through the heat sources will be eliminated.
St tank transfer pump Q11 If the temperature level of the buffer storage tank is high enough, the DHW storage tank can be charged by the buffer. This transfer can be made by means of transfer pump Q11. DHW mixing pump Q35 Separate pump for storage tank circulation during the time the legionella function is active. DHW interm circ pump Q33 Charging pump with DHW storage tank using an external heat exchanger. Heat request K27 As soon as there is demand for heat, output K27 is activated.
Cascade return sensor B70 Swimming pool sensor B13 Collector sensor 2 B61 Solar flow sensor B63 Solar return sensor B64 Depending on the selection made, setting of the sensor input assigns appropriate extra functions to the basic diagrams. For detailed information, refer to section “Application diagrams“. Input H1 for RVS43.. The following settings for input H1 apply specifically to RVS43.. Input H1 for RVS43.. Line no.
Error / alarm message Input H1 generates a controller-internal error message. If the “Alarm output” (relay outputs QX2-4, operating lines 5891 – 5894) is appropriately configured, the error message will be forwarded or displayed by an additional contact (e.g. an external lamp or horn). Minimum flow temperature setpoint TVHw The adjusted minimum flow temperature setpoint will be activated via terminals H1/2 (e.g. an air heater function for a warm air curtain) closes its contact.
Dewpoint monitor The dewpoint monitor detects the formation of condensate. If the dewpoint monitor responds to condensation, the cooling switches off immediately. The cooling is enabled when the monitor is no longer signalling condensation and when a definable "locking time" (operating line 946) has expired. Flow setpoint increase, hygrostat If the hygrostat responds, the flow setpoint is increased by the fixed value defined in "Flow setpt increase hygro" (operating line 947).
Function value, contact H.. The function “Min flow temp setpoint” on operating line 5950 or 6046 is activated via contact H... The generating plant is controlled constantly at the temperature level set here, either until contact H.. opens again or until a higher heating/cooling demand is delivered.
• Example of relative room humidity 10V rF UHx U1 F1 U2 F2 relative humidity Voltage on Hx Voltage value 1 Function value 1 Voltage value 2 Function value 2 If the measured value is below 0.15V it is regarded as invalid and an error message is generated. • Example of room temperature 10V TR [°C] TR UHx U1 F1 U2 F2 F2=100 F2=50 F1=0 U1=0V Room temperature Voltage on Hx Voltage value 1 Function value 1 Voltage value 2 Function value 2 UHx 0.15V U2=10V If the measured value is below 0.
Input H1 and H3 for RVS63.. The following settings for input H1 apply specifically to RVS43.. Input H.. for RVS63.. Line no.
Minimum flow temperature setpoint TVHw The adjusted minimum flow temperature setpoint will be activated via terminals H1/2 (e.g. an air heater function for a warm air curtain) closes its contact. Excess heat discharge Active dissipation of excessive heat enables an external heat source to force consumers (heating circuit, DHW storage tank, Hx pump) to draw excessive heat by delivering a forced signal.
The pressure value at 0.5 V is fixed at 0 bar. The pressure value at 3.5 V can be adjusted with parameter Pressure value 3.5V H… (operating line 5956). Contact type, input H... N/C contact The contact is normally closed and must be opened to activate the selected function. N/O contact The contact is normally open and must be closed to activate the selected function. Min flow temp setpoint H.. The function “Minimum flow setpoint” set on operating line 5950, 5960 or 6046 is activated via contact H...
Pressure value 3.5V H… The voltage signal present at input H… is converted into a linearized pressure value. The pressure value at 3.5 V can be adjusted with parameter Pressure value 3.5V H..”. p Example: D35 = 4bar 4 D35 = 2bar 2 0 p H1 0.5 V 3.5 V H1 2359Z136 D35 = 1bar 1 Pressure value (bar) Voltage at H.. Input EX2 Line no.
Excess heat discharge Active dissipation of excessive heat enables an external heat source to force consumers (heating circuit, DHW storage tank, Hx pump) to draw excessive heat by delivering a forced signal. The parameter “Excessive heat draw“ can be used to determine for every consumer whether or not it should take account of the "forced" signal, and hence whether or not that consumer should participate in the dissipation of heat.
Cooling circuit 1 For this application, the respective settings of operating page “Cooling circuit 1” can be adapted. Heating circuit/cooling circuit 1 For this application, the respective settings of operating page “Heating circuit 1 and cooling circuit 1” can be adapted.
Connections: QX21 * Y5 QX22 * Y6 Multifunction Heating circuit 2 Return temp Y7 Y8 controller Solar DHW * * heating Primary Y19 Y20 controller DHW primary Y31 Y32 controller Instantaneous Y33 Y34 DHW heater Return Y25 Y26 controller cascade Cooling circuit Y23 Y24 1 * Freely selectable in QX…/ BX...
BX extension module Can be configured for freely selectable QX…/ BX... Line no.
10V output UX Line no.
Building and room model Line no. Operating line 6110 Time constant building When the outside temperature varies, the room temperature changes at different rates, depending on the building's thermal storage capacity. The above setting is used to adjust the response of the flow temperature setpoint when the outside temperature varies. • Example: > 20 hours The room temperature responds more slowly to outside temperature variations. 10 - 20 hours This setting can be used for most types of buildings.
Sensor state Line no. Operating line 6200 Save sensors At midnight, the basic unit stores the states at the sensor terminals. If, after storage, a sensor fails, the basic unit generates an error message. This setting is used to ensure immediate saving of the sensors. This becomes a requirement when, for instance, a sensor is removed because it is no longer needed. Parameter reset Line no. Operating line 6205 Reset to default parameters All parameters can be reet to their default values.
No solar * DHW/B x x x DHW+B DHW/B DHW DHW B B x x x x x x x x x x x x x x x x x x x x 31 33 35 37 38 39 40 41 42 44 45 46 48 49 50 51 52 DHW/B x DHW/B DHW+B x DHW/B DHW x DHW B x B * DHW/B 00 x 02 03 x 06 07 Return mixing valve Bypass pump x x x x x x x x x x x x x x x x x 08 09 10 Boiler pump No boiler 01 04 05 Modulating burner 2-stage burner 1-stage burner Check-Numbers External solar heat exchanger, solar pump K9 DHW = dom.
Check-No. storage tank Buffer storage tank No buffer storage tank buffer storage tank Buffer storage tank, solar connection Buffer storage tank, heat source valve Buffer storage tank, solar connection, heat source valve 0 1 2 4 5 0 1 2 4 5 13 14 16 17 19 20 22 23 25 26 28 29 Check-No.
Displays on the operator unit: Check-No. heat source 1 Check-No. storage tank Check-No. heating circuit 1 0 1 5 3 Device data Line no. Operating line 6220 Software version The software version indicated here represents the current version of the basic unit. 6.20 LPB Address / power supply Line no.
6627 Refrigeration demand 6631 Ext source with eco mode Locally¦ Centrally Off ¦ On DHW ¦ On These settings are only relevant for device address 1. Range of action of changeover The range of action of central changeover can be defined. This applies to the following types of limitation: • Summer changeover (when selecting ”Central“ on line 6623) • Summer changeover (with ”Central“ setting on operating line 6621) Entries: • Segment: Changeover takes place with all controllers in the same segment.
Ext source with eco mode Economy mode can be selected from menu ”Special operation / service” (operating line 7139). In Economy mode, external heat sources on the LPB are operated as follows: Off: Remains locked Only DHW: Released for DHW charging On: Always released.
The difference of setpoint and actual temperature is monitored. A control offset beyond the set period of time triggers an error message. Error history Line no. Operating line 6800…6819 History … The basic unit stores the last 10 faults in non-volatile memory. Any additional entry deletes the oldest in the memory. For each error entry, error code and time of occurrence is saved. 6.22 Maintenance/special mode Maintenance functions Line no.
For safety reasons, maximum limitation of the boiler temperature (TKmax) remains active as long as the chimney sweep function is active. The function is deactivated by setting -.- on this operating line, or automatically after a timeout of 1 hour. Manual operation Line no.
Auxiliary functions Setpoint adjustment in manual control Alarm output Time program 5 Heat demand Refrigeration demand Storage tank transfer pump K10 K13 K27 K28 Q11 Off Off On Off Off After manual control has been activated, a change to the basic display must be made. There, the maintenance / special mode symbol appears. Press the info button to switch to info display “Manual mode“, where the setpoint can be adjusted. Simulations Line no.
6.24 State The current operating state of the plant is visualized by means of status displays. Messages State heating circuit Line no.
Frost protection active Cooling limit OT active Off Cooling mode off State of DHW End user (info level) Limit thermostat has cut out Manual control active Draw-off mode Cooling limit OT active Off Room temp lim Flow limit reached Cooling mode off Commissioning, heating engineer Limit thermostat has cut out Manual control active Draw-off mode Recooling via collector Recooling via DHW/HCs Recooling active Discharging protection active Charging time limitation active DHW charging locked Charging lock acti
Charging buffer storage tank In operation for HC, DHW In partial load operation for HC, DHW Released for HC, DHW In operation for DHW In partial load operation for DHW Released for DHW In operation for heating circuit In partial load operation for HC Released for HC Overrun active Released Frost protection active Off State of solar End user (info level) Manual control active Fault.
Charged, forced charg required temp Charged, required temp Charged, min charg temp Charged Hot No demand Frost protection active Hot 72 73 143 75 147 No demand 51 Frost protection active Charging electric, em operation Charging electric, source prot Charging electric, defrost Charging electric, forced Charging electric, substitute 24 64 65 131 164 165 66 81 104 124 Charging el im heater DHW charging locked Restricted, DHW priority Charging restricted Charging active Forced charging active Partial
6.27 List of displays Priorities are assigned to pending errors. From priority 6, alarm messages are delivered, which are used by remote supervision (OCI). In addition, the alarm relay will be set. 6.27.
320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 357 366 367 DHW charging temperature sensor error Instantaneous DHW heater outlet temperature sensor error Upper pressure limit 3 (crossed) Critical lower pressure limit 3 (crossed) BX same sensors BX/extension module same sensors BX/mixing valve group same sensors Extension module same function Mixing valve group same function Extension module / mixing valve group same fu
7 Plant diagrams The various applications are shown in the form of basic diagrams and extra functions. The basic diagrams show possible applications that can be implemented without the use of multifunctional outputs. 7.1 Basic diagrams The basic diagrams are examples of plant that can be implemented with standard outputs requiring only a few settings. 7.1.1 Basic diagram RVS43.
Heating/cooling via diverting valve Y21 B9 Y1/Y2 Q2 B1 RG1 2358A33 H/C C C 7.1.2 Basic diagram RVS63.243 Standard diagram B9 Q3 Y1 B3 Q2 B1 2358A02 RG1 DHW heating with diverting valve B9 Q3 B3 Q2 2358A12 RG1 154/180 Siemens Schweiz AG HVAC Products User Manual Basic diagrams CE1U2354en 23.
7.1.3 Basic diagram RVS63.283 Standard diagram B9 Q3 Y5 B3 Q6 Y1 Q2 B12 RG1 2358A03 RG2 B1 155/180 Siemens Schweiz AG HVAC Products User Manual Basic diagrams CE1U2354en 23.
7.2 Versions of heat sources The heat generation options can be selected via the "Configuration" operating page on operating line 5779 "Source type". 1-stage burner 2-stage burner Modulating 2354A05 2354A05 2354A05 3-point 0…10 V RVS43… RVS63… RVS63… RVS63… 2354A05 Burner without boiler sensor RVS63… 156/180 Siemens Schweiz AG HVAC Products User Manual Versions of heat sources CE1U2354en 23.
7.3 Extra functions in general The extra functions can be selected via operating page “Configuration” and complement the basic diagrams of the respective controllers. The type and number of extra functions that can be applied depend on the multifunctional outputs and inputs QX… or BX… Depending on the type of application, the use of extra functions necessitates a number of appropriate operating line settings.
Solar storage tank and swimming pool charging via diverting valves with 2 collectors B13 Q5 B4 B3 B41 B31 B61 Q16 1 1 0 0 K18 2358A26 B6 K8 Solar storage tank and swimming pool charging via charging pumps with 1 collector B3 B6 Q5 B31 K8 K18 2358Z35 K9 Solar storage tank and swimming pool charging via charging pumps with 2 collectors B13 Q5 B3 B4 B61 Q16 B31 B41 K18 K8 K9 2358A27 B6 158/180 Siemens Schweiz AG HVAC Products User Manual Extra functions in general CE1U23
Boiler Boiler pump Bypass pump B2 B2 T2 Q12 2358A07 Q1 Solid fuel boiler pump 2358A08 T2 Return sensor B22 B2 T2 B7 2358A13 2358A22 Q10 Flue gas temperature sensor B2 B8 Q1 2358A23 T2 159/180 Siemens Schweiz AG HVAC Products User Manual Extra functions in general CE1U2354en 23.
DHW storage tank (DHW) DHW circulating pump Q3 DHW el imm heater B39 Q3 B3 Q4 B3 2nd DHW sensor 2358A05 2358A04 K6 DHW tank with external heat exchanger, charging pump, intermediate circuit pump B36 Q3 B3 B3 Q3 B31 2358A34 2358A11 B31 Q33 Buffer storage tank Heat source shutoff valve buffer Y4 B4 B4 B42 2358A35 2358A21 B41 B41 160/180 Siemens Schweiz AG HVAC Products User Manual Extra functions in general CE1U2354en 23.
Partial tank charging Return diversion B4/B42 2358A36 2358A38 B4/B41/B42 B73 1 1 0 0 Y15 Y15 Storage tank charge transfer Q11 B4 2358A37 B3/B31 Heating/cooling circuit Heating circuit pump HCP Diverting valve for cooling 2358A39 H B9 Q20 Y21 Q2 RG1 B1 RG1 2358A10 H/C H C 161/180 Siemens Schweiz AG HVAC Products User Manual Extra functions in general CE1U2354en 23.
Heat converter 2358A24 System pump Q14 Q14 Swimming pool Swimming pool K18 B6 2358A29 Q5 1 0 K18 Pressureless header Common flow sensor 2358A25 B10 Extra functions H.. Pump 2358A09 Q15/18/19 162/180 Siemens Schweiz AG HVAC Products User Manual Extra functions in general CE1U2354en 23.
7.4 Additional funct. with mix. valve group or extension module AVS75.390 The extra functions can be selected via operating page “Configuration“, operating lines 6020 and 6021, and supplement the basic diagrams of the respective controllers.
Solar DHW heating Q3 B6 B3 Q5 2358A06 B31 Primary controller Y19 B15 2358A19 Q14 Primary DHW controller Y31 Q3 B35 B3 2358A30 B31 Instantaneous DHW heater B39 B38 FS Y33 2358A31 Q34 164/180 Siemens Schweiz AG HVAC Products User Manual Additional funct. with mix. valve group or extension module AVS75.390 CE1U2354en 23.
Return controller cascade 2358A32 B10 B70 Q25 Y25 165/180 Siemens Schweiz AG HVAC Products User Manual Additional funct. with mix. valve group or extension module AVS75.390 CE1U2354en 23.
Legend mains voltage Diagram Function T2 Burner 1st stage Release modulating burner T8 Burner 2nd stage Air damper modulating burner opening Q1 Q2 Q3 Q4 Q5 Q6 Q10 Q11 Q12 Q14 Q15/18/19 Q16 Q20 Q24 Q25 Q33 Q34 Y1 Y4 Y5 Y6 Y7 Y15 Y19 Y21 Y25 Y26 Y31 Y32 Y33 Y34 K6 K5 K8 K9 K18 Boiler pump 1st heating circuit pump DHW charging pump / diverting valve circulating pump Collector pump 2nd heating circuit pump Solid fuel boiler pump Storage tank charging pump Bypass pump System pump H1/2/3 pump Collector pum
Legend low-voltage B1 B12 B13 B2 B22 B3 B31 B35 B36 B38 B4 B41 B42 B15 B39 B6 B61 B7 B70 B73 B8 B9 B10 RG1 RG2 FS Flow temperature sensor HK1 Flow temperature sensor HK2 Swimming pool sensor Boiler temperature sensor TK1 Solid fuel boiler sensor DHW sensor top 2nd DHW sensor bottom DHW flow temperature sensor DHW charging sensor DHW temperature outlet sensor Buffer storage tank temperature sensor Buffer storage tank temperature sensor Buffer storage tank temperature sensor Flow sensor primary controller D
8 Technical data 8.1 Basic units RVS… Power supply Wiring of terminals Functional data Inputs Rated voltage Rated frequency Power consumption Fusing of supply lines Power supply and outputs Software class Mode of operation to EN 60 730 Digital inputs H1 and H2 Analog input H1, H2 Mains voltage S3, 4 and EX2 Outputs AC 230 V (±10%) 50/60 Hz RVS43.143: 8.5 VA RVS63.243: 10 VA RVS63.283: 11 VA max. 10 AT solid wire or stranded wire (twisted or with ferrule): 1 core: 0.5...2.5 mm2 2 cores: 0.5. mm2..
Interfaces, cable lengths Degree of protection and safety class Standards, safety, EMC, etc. Climatic conditions Weight BSB Max. cable length Basic unit – peripheral device Max. total length Min. cross-sectional area LPB 2-wire connection, not interchangeable 200 m 400 m (max. cable capacitance) 60 nF) 0.5 mm2 (copper cable 1.
Outputs Interfaces Degree of protection and safety class Standards, safety, EMC, etc. Climatic conditions Weight Relay outputs Rated current range Max. switch-on current Max. total current (of all relays) Rated voltage range BSB Max. cable length Basic unit – peripheral device Max. total length Min.
Standards, safety, EMC, etc.
Degree of protection and safety class Standards, safety, EMC, etc.
8.7 Radio repeater AVS14.390 Power supply Nominal voltage Nominal frequency Power consumption Interfaces RF transmitter Degree of protection and safety class Degree of protection of housing to EN 60 529 Safety class to EN 60 730 Standards, safety, EMC, etc.
8.8 Sensor characteristics 8.8.1 NTC 1 k T [°C] R[Ohm] T [°C] R[Ohm] T [°C] R[Ohm] -30.0 -29.0 -28.0 -27.0 -26.0 -25.0 -24.0 -23.0 -22.0 -21.0 -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 13,034 12,324 11,657 11,031 10,442 9,889 9,369 8,880 8,420 7,986 7,578 7,193 6,831 6,489 6,166 5,861 5,574 5,303 5,046 4,804 4,574 4,358 4,152 3,958 3,774 3,600 3,435 3,279 3,131 2,990 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.
8.8.2 NTC 10 k T [°C] R[Ohm] T [°C] R[Ohm] T [°C] R[Ohm] -30.0 -25.0 -20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 175203 129289 96360 72502 55047 42158 32555 25339 19873 15699 12488 10000 8059 6535 5330 4372 50.0 55.0 60.0 65.0 70.0 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115.0 120.0 125.0 3605 2989 2490 2084 1753 1481 1256 1070 915 786 677 586 508 443 387 339 130.0 135.0 140.0 145.0 150.0 155.0 160.0 165.0 170.0 175.0 180.0 185.0 190.0 195.0 200.
Index 2 2 x 1 cascade ..........................................................100 24-hour heating limit..................................................79 2nd pump speed......................................................120 A absolute priority .........................................................95 acknowledgements..................................................143 action changeover functions....................................142 action of operation..............................................
heating curve displacement ................................ 78, 79 heating curve slope................................................... 78 heating curve slope................................................... 78 holiday program ........................................................ 77 holidays end....................................................................... 77 start...................................................................... 77 I input / output test .................................
shifting priority ...........................................................95 simulation outside temp...........................................146 simulations ..............................................................146 SLT test .....................................................................40 software version ......................................................141 solar.........................................................................102 storage temp., cooling mode ..................
9 Revision history All changes made to the document since the last issue (see front page) have been registered with the Winword function "Highlight". To show such text, use the following key combinations: Display: Ctrl Shift (Num) + Hide: Ctrl Shift (Num) Or select the same functionality with the following Winword menu: Menu: [¨Tools] - [Options] Command: [Highlight] The revision history is not visible in the print version (PDF). 179/180 Siemens Schweiz AG HVAC Products User Manual CE1U2354en 23.
Siemens Schweiz AG Siemens Switzerland Ltd Building Technologies Group / HVAC Products Gubelstrasse 22 CH -6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.sbt.siemens.com © 2005-2007 Siemens Schweiz AG Subject to alteration 180/180 Siemens Schweiz AG HVAC Products User Manual CE1U2354en 23.