Mixing valve control
Line no. Operating line
5544 Actuator running time
Setting the running time of the actuator used with the mixing valve.
6.19 Configuration
Heating circuits
Line no. Operating line
HC1 HC2
5710 5715 Heating circuit 1, 2
Using this setting, the heating circuits can be switched on and off.
Line no. Operating line
5711
Cooling circuit 1
Off
4-pipe system
2-pipe system
5712
Use of mixing valve 1
Heating
Cooling
Heating and cooling
Off
The cooling circuit is deactivated.
4-pipe system
The cooling and heating circuits draw their
cooling/heating energy from separate
primary circuits.
2-pipe system
The cooling and heating circuits draw their
cooling/heating energy from the same
primary circuit.
A
ctuator running time
Cooling circuit 1
RVS43.. only