Operation Manual
127/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Configuration 23. August 2007
• Example of relative room humidity 10V
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.
•
Example of room temperature 10V
TR [°C]
UHx
U2=10VU1=0V
F
1=0
0.15V
F2=100
F2=50
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.
rF relative humidity
UHx Voltage on Hx
U1 Voltage value 1
F1 Function value 1
U2 Voltage value 2
F2 Function value 2
TR Room temperature
UHx Voltage on Hx
U1 Voltage value 1
F1 Function value 1
U2 Voltage value 2
F2 Function value 2