Operation Manual

128/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Configuration 23. August 2007
Input H1 and H3 for RVS63..
The following settings for input H1 apply specifically to RVS43..
Input H.. for RVS63..
Line no. Operating line
5950 function input H1
Optg mode changeover
HCs+DHW
Optg mode changeover HCs
Optg mode changeover HC1
Optg mode changeover HC2
Optg mode changeover HCP
Heat generation lock
Error / alarm message
Min flow temp setpoint
Excess heat discharge
Release swimming pool
Heat request 10V
Pressure measurement 10V
5951 Contact type input H1
NC
N/O
5952 Min flow temp setpoint H1
5954 Temp value 10V H1
5956 Pressure value 3.5V H1
5960 Function input H3
Optg mode changeover
HCs+DHW
Optg mode changeover HCs
Optg mode changeover HC1
Optg mode changeover HC2
Optg mode changeover HCP
Heat generation lock
Error / alarm message
Min flow temp setpoint
Excess heat discharge
Release swimming pool
Heat request 10V
Pressure measurement 10V
5961 Contact type H3
NC
N/O
5962 Min flow temp setpoint H3
5964 Temp value 10V H3
5966 Pressure value 3.5V H3
Changeover of operating mode
Heating circuit
The operating modes of the heating circuits are switched to Protection mode via the
H… terminals (e.g. using a remote telephone switch).
DHW
DHW heating is locked only when using setting 1: HCs+DHW.
Heat generation lock
The heat source is be locked via the H… terminals. All temperature requests from the
heating circuits and DHW are ignored. Frost protection for the boiler is maintained.
The chimney sweep function can be activated although the heat generation lock is
switched on.
Error / alarm message
Input H1 generates a controller-internal error message.
If the “Alarm output” (relay outputs QX2-4, operating lines 5891 – 5894) is appropriately
configured, the error message will be forwarded or displayed by an additional contact
(e.g. an external lamp or horn).
Function of input H...