Operation Manual
146/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Input / output test 23. August 2007
Auxiliary functions Alarm output K10 Off
Time program 5 K13 Off
Heat demand K27 On
Refrigeration demand K28 Off
Storage tank transfer
pump
Q11 Off
After manual control has been activated, a change to the basic display must be made.
There, the maintenance / special mode symbol
appears.
Press the info button to switch to info display “Manual mode“, where the setpoint can be
adjusted.
Simulations
Line no. Operating line
7150 Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range from –
50 to +50°C can be simulated. During simulation, the actual, the composite and the
attenuated outside temperature will be overridden by the set simulated temperature.
During simulation, calculation of the 3 mentioned outside temperatures continues and
the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically after a
timeout of 1 hour.
Telephone customer service
Line no. Operating line
7170 Telephone customer service
Setting of phone number that appears on the info display.
6.23 Input / output test
Line no. Operating line
7700…7999
The input / output test is used to check the correct functioning of the connected
components.
When selecting a setting from the relay test, the relevant relay is energized, thus
putting the connected component into operation. The correct functioning of the relays
and wiring can thus be tested.
Important:
During the relay test, limitation of the boiler temperature by the electronic control
thermostat (TR) remains activated. Other limits are deactivated.
Selector sensor values are updated within a maximum of 5 seconds.
The display is made with no measured value correction.
Setpoint adjustment in
manual control