Operation Manual

32/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Wireless components 23. August 2007
3.8.4 Radio repeater AVS14.390
To establish the radio connection, the device must be provisionally connected to
power prior to mounting, enabling the radio connection to be opened and tested.
The radio repeater must be fitted inside the building.
Mounting method
1
2359Z30
2
2359Z33
4
2359Z31
Connections
Power is supplied via the enclosed power pack. The wires are interchangeable.
Radio connection
Make the radio connection in the vicinity of the radio module prior to mounting so that
all system are within easy reach.
Prerequisite for the radio connection is that all components receive power, which
means that the radio module must be correctly connected to the basic unit and power
must be correctly supplied to the radio repeater.
1. Press the button on the radio module for at least 8
seconds until the LED on the radio module starts
flashing at high frequency.
2. Press the button on the installed radio repeater until
the LED start flashing at high frequency.
3. The connection is established when the LED on the
radio module extinguishes.
The test is made to check the quality of the radio link.
The test can be aborted by pressing the ESC button.
While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
1. Press button 3 on the radio repeater for a maximum of 8 seconds until the LED
starts flashing at low frequency.
2. When radio communication works, the LED on the radio module flashes briefly at
10-second intervals.
3. After the test, press the button on the radio repeater again briefly until the LED
extinguishes.
Dimensions and drilling plan
90
100
32
2359Z16
12
2359Z27
4,2
56
60
56
60
Establishing the link
Testing
2359Z56
LED
Button