Operation Manual

44/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products QAA75.. / QAA78… / AVS37.. 23. August 2007
5.1.4 Overview of settings
The table shows all available settings up to the heating engineer level. However,
certain operating lines may be hidden, depending on the type of unit.
E = End user I = Commissioning F = Heating engineer
BZ = Operating line
1)
QAA75../78.. only
4)
RVS43.. only
6)
RVS63.. only
Operating line
User level
Function
Default value
Min
Max
Unit
Time of day and date
1 E Hours/minutes - 00:00 23:59 hh:mm
2 E Day/month - 01.01 31.12
dd.MM
3 E Year - 2004 2099
yyyy
5 F Start of summertime 25.03 01.01 31.12
dd.MM
6 F End of summertime 25.10 01.01 31.12
dd.MM
Operator unit
20 E Language
German ¦ …
German
-
22 F Info
Temporarily ¦ Permanently
Temporary
-
26 F Operation lock
Off ¦ On
Off
-
27 F Programming lock
Off ¦ On
Off
-
28 I Direct adjustment
Automatic storage ¦ Save with acknowledgment
Save with acknowledgment
40
1)
I Used as
Room unit 1 ¦ Room unit 2 ¦ Room unit P ¦ Operator unit
1 ¦ Operator unit 2 ¦ Operator unit P ¦ Service unit
Room unit 1
-
42
1)
I Assignment device 1
Heating circuit 1 ¦ Heating circuits 1 and 2 ¦ Heating
circuits 1 and P ¦ All heating circuits
Heating circuit 1
-
44 I Operation HC2
Commonly with HC1 ¦ Independently
Commonly with HC1
-
46 I Operation HCP
Commonly with HC1 ¦ Independently
Commonly with HC1
-
48
1)
I Action presence button
None ¦ Heating circuit 1 ¦ Heating circuit 2 ¦ Commonly
Heating circuit 1
-
54
1)
F Readjustment room sensor 0.0 -3 3 °C
70 F Software version - 0 99.9 -
Radio
120 I Binding
No ¦ Yes
No
121 I Test mode
Off ¦ On
Off
130 I Room unit 1
Missing ¦ Ready ¦ No recept’n ¦ Change batt
- -
131 I Room unit 2
Missing ¦ Ready ¦ No recept’n ¦ Change batt
- -
132 I Room unit P
Missing ¦ Ready ¦ No recept’n ¦ Change batt
-
Legend