Adjusting the room temperature setpoint
Press the + / - buttons to increase or decrease the
Comfort setpoint .
For the Reduced setpoint
Press OK
Select the operating line for the “Reduced setpoint”
After each readjustment, wait at least 2 hours, allowing the room temperature to adapt.
Adjusting the nominal DHW setpoint
Press the + / - buttons to increase or decrease the
nominal DHW setpoint.
Displaying information
Various data can be displayed by pressing the info button.
The display alternates, showing the value and the info no.
2354Z13
2354Z13
No. 1 Boiler temp
No. 2 Outside temperature
No. 3 DHW temperature
No. 4 Flow temperature 1
No. 5 Flow temperature 2
No. 10 State of heating circuit 1
No. 11 State of heating circuit 2
No. 12 State of DHW
No. 13 State of boiler
No. 14 State of solar
In exceptional cases, the basic display shows one of the following symbols:
Error messages
If this symbol appears, an error in the
plant has occurred. The display shows
letter “c”, followed by the error no.
1
2354Z13
Maintenance or special operation
If this symbol appears, a maintenance
alarm is delivered or the plant has
changed to special mode. The display
shows letter “c”, followed by the message
no.
1
2354Z13
To start the chimney sweep function , press the button for a moment (< 3 seconds).
This function produces the operating state required to make emission measurements
(flue gas).
Exception
Chimney sweep function
OK
+
+