Operation Manual

69/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products AVS37.390 23. August 2007
5.2.3 Overview of settings
The table shows all available settings up to the heating engineer level.
E = end user F = heating engineer
BZ = operating line
Operating line
Operating line
clear-text units
User level
Function
Default value
Min
max
Unit
Time of day and date
50 1 E Hours/minutes 01:00 00:00 23:59 hh:mm
51 2 E Day/month 1.01 01.01 31.12 dd.mm
52 3 E Year 2004 2004 2099 yyyy
53 4 F Start of summertime 25.03 01.01 31.12 dd.mm
54 5 F End of summertime 25.10 01.01 31.12 dd.mm
59 6220 F Software version - 0 99.9 -
Time prog heating circuit 1
61 500 E Preselection Mo-Su
-
62 501 E 1st phase on 6:00 00:00 24:00 hh:mm
63 502 E 1st phase off 22:00 00:00 24:00 hh:mm
64 503 E 2nd phase on --:-- 00:00 24:00 hh:mm
65 504 E 2nd phase off --:-- 00:00 24:00 hh:mm
66 505 E 3rd phase on --:-- 00:00 24:00 hh:mm
67 506 E 3rd phase off --:-- 00:00 24:00 hh:mm
Time prog heating circuit 2
71 520 E Preselection Mo-Su
72 521 E 1st phase on 6:00 00:00 24:00 hh:mm
73 522 E 1st phase off 22:00 00:00 24:00 hh:mm
74 523 E 2nd phase on --:-- 00:00 24:00 hh:mm
75 524 E 2nd phase off --:-- 00:00 24:00 hh:mm
76 525 E 3rd phase on --:-- 00:00 24:00 hh:mm
77 526 E 3rd phase off --:-- 00:00 24:00 hh:mm
Heating circuit 1
81 712 E reduced setpoint 16 4 35 °C
82 720 E Heating curve slope 1.5 0.10 4.00 °C
83 721 F Heating curve displacement 0 -4.5 4.5 °C
84 730 E Summer/winter heating limit 18 - - - / 8 30 °C
85 741 F flow temp setpoint max 80 8 95 °C
Heating circuit 2
86 1012 E Reduced setpoint 16 4 35 °C
87 1020 E Heating curve slope 1.5 0.10 4.00 °C
88 1021 F Heating curve displacement 0 -4.5 4.5 °C
89 1030 E Summer/winter heating limit 18 - - - / 8 30 °C
90 1041 F Flow temp setpoint max 80 80 95 °C