s Synco™ living Mounting and commissioning Edition 1.0 QAX9x3 Series A CE1C2740en 13.12.
Congratulations … … on choosing the Siemens Synco™ living system and thank you for purchasing the central apartment unit! The present document describes how to mount and commission the central apartment unit and the other system components. First, please familiarize yourself with the operating philosophy of the central apartment unit. Operation itself is covered by the operating instructions (CE1B2740en).
Table of contents Safety notes................................................................................................... 11 Mounting and installation............................................................................. 12 Mount the central apartment unit .............................................................. 12 Mounting rules.................................................................................... 12 Mounting location ......................................................
Configure cold water meter.......................................................... 33 Configure electricity meter ........................................................... 34 Configure gas meter .................................................................... 34 Configure other meters ................................................................ 34 Configure light state display (QAX913 only) ...................................... 35 Temperature display (QAX913 only)...............................
Fireplace mode ............................................................................ 52 Ventilation contacts 1 and 2......................................................... 53 HR bypass ................................................................................... 53 Meters ................................................................................................ 53 Due date ...................................................................................... 54 Synergyr apartment ......
Connect water detector QFP910 (QAX913 only) ........................ 75 Connect fault outputs 1 – 2 (QAX913 only) ....................................... 75 Connect supervision components (QAX913 only) ............................. 76 Connect supervision contact........................................................ 76 Connect supervision state ........................................................... 76 Connect water shutoff valve ........................................................
Function settings .......................................................................................... 95 General ..................................................................................................... 95 Buzzer volume.................................................................................... 95 Password expert level ........................................................................ 95 Apartment ..............................................................................
Startup delay .................................................................................... 110 Locking time ..................................................................................... 110 Rundown time .................................................................................. 110 DHW (QAX913 only) .............................................................................. 111 Frost protection setpoint...................................................................
Communication ........................................................................................... 124 Protocol...................................................................................... 124 Maintenance/service ................................................................................... 124 Peripheral devices .................................................................................. 124 Restore factory settings.................................................................
Safety notes Product liability • Use these products only in building services plant and only for the applications described. • Comply with all local safety regulations (installation, etc.). • Do not open the devices. Opening the devices will void warranty by Siemens. • If a device is defective or damaged, disconnect it from power immediately and replace it. • Application-related technical data are only guaranteed in connection with the Siemens Synco™ living system.
Mounting and installation Mount the central apartment unit Mounting rules • The central apartment unit is designed in compliance with safety class II and must be mounted accordingly. • Power may be applied to the unit only when completely mounted. Otherwise, there is a risk of electric shock by the connection terminals. • Do not expose the unit to dripping water. • Adhere to the permissible ambient conditions as stated in the technical data (see data sheets N2740en (QAX913) or N2741en (QAX903)).
of house or building and the materials used, the effective range can be considerably greater or smaller. If greater distances are to be covered, RF repeaters should be used. Central apartment unit QAX913 dimensions Dimensions in mm Dimensions of the base Dimensions in mm 13 / 134 Siemens Building Technologies Synco™ living Mounting and installation CE1C2740en 13.12.
Mounting procedure Mounting method / knockout holes The base of the central apartment unit can be mounted directly on the wall or on a recessed conduit box. It has an opening at the rear and 2 knockout holes (one at the top and one at the bottom). If required, the hole(s) must be knocked out before securing the base to the wall. Holes Secure the base to the wall with at least 3 screws.
Swing the electronics section 45° upward and pull it towards you to remove it. Fit the base Secure the base to the wall using at least 3 fixing screws. Wiring Wiring is described under “Connection terminals/wiring“ (see page 16). Replace the electronics section Insert the electronics section at an angle of about 45° in the base (left and right). Then, swing it downward until it engages. The central apartment unit is now ready for commissioning.
Electrical installation of the central apartment unit Installation rules • • • • Comply with all local safety regulations (installation, etc.). Only qualified staff may carry out electrical installations. Prior to installation, disconnect the central apartment unit from power! The connection terminals for low-voltage and mains voltage are arranged on different sides of the unit. • When wiring the unit, satisfy requirements of safety class II. • Provide cable strain relief.
N L CEKNX CE+ M B 2707Z24 Q13 Q14 230 V Detail view Key Mains voltage or protective extra low-voltage Q13, Q14 Potential-free, universal relay output Mains voltage N Operating voltage, neutral conductor AC 230 V L Operating voltage, live conductor AC 230 V Protection by extra-low voltage CE-, CE+ Connection data bus KNX TP1- and KNX TP1+ M Ground for universal input B Universal input F Strap for cable ties 17 / 134 Siemens Building Technologies Synco™ living Mounting and installation
Commissioning the system Prerequisites Prior to commissioning the system, check to ensure that the following prerequisites are met: • You are familiar with the different operating elements and operating levels of the central apartment unit. • All system components are correctly installed. • Mains-powered components are connected to power. • New batteries are ready to be inserted in the battery-powered devices *. • Wired devices are connected to the KNX TP1 data bus.
The unit switches on as soon as power is supplied. A brief function test is carried out while the hourglass is displayed. When you first commission the central apartment unit, you must select the language, time of day, year, and date. The display then changes to the default picture. You can also select both language and time format during operation. See the operating instructions for a description. 01:32 Tuesday 16.11.2010 1013 hPa 20°C 5°C If the central apartment unit was operated previously (e.g.
Select the Commissioning menu From the “Main menu“ of the central apartment unit, select submenu “Commissioning“ and confirm the selection by pressing the Menu/ok button. Caution! Plant stops Commissioning Basic configuration… RF connections… Device list… Bus communication… You are notified that the plant is being stopped. Confirm by pressing the Menu/ok button to shut down the plant and go to the ”Commissioning“ menu. You are now in the “Commissioning “ menu – the plant has been stopped.
Main menu > Commissioning > Basic configuration > Rooms > Room X > Cooling type: --- Inactive – all relevant room cooling information and operating lines are hidden. (Factory setting) Release output For rooms with externally controlled cooling triggered via a release output. Air conditioner (S-mode) For rooms with an air conditioner used for cooling. Radiator/floor cooling For rooms with radiators or floor heating used for cooling.
Configure room groups Any number of rooms can be combined to form one room group. Two independent room groups can be formed. The flow temperature can be controlled, a room group pump defined, and the return temperature limited for each room group.
--- Inactive – room group not available. No primary controller Room group available without precontroller function. With primary controller Room group available with precontroller function. Prim controller + return sensor Room group with precontroller and additional return flow temperature sensor available for return flow temperature limitation.
Room group pumps and DHW charging pump: M1 B1 K E T M2/M3 B2/B3 U1 U2 T Y1 Y2 DHW pump/diverting valve DHW sensor Electric immersion heater Consumer (radiator or floor heating) Room temperature sensor or room unit Room group pumps 1 and 2 Flow sensors room groups 1 and 2 Mixing valve for room group 1 (radiators) Mixing valve for room group 2 (floor heating) Room unit or room temperature sensor Radiator control actuator Heating circuit valve (2-position) Specify if room group pumps are installed and how t
Minimum limitation of the return temperature Minimum limitation of the return temperature (maintained boiler return temperature) ensures protection of the boiler by preventing the return temperature from falling below a certain level. Minimum limitation is accomplished by reducing the flow temperature setpoint. As a result, a smaller volume of boiler water is supplied to the room group and more to the return via the bypass.
The type of DHW heating depends on the installed DHW components according to the following table: DHW sensor DHW pump/ valve Electric Resulting type of DHW heating immersion --- --- --- Inactive: No local DHW heating. Installed Installed --- Controlled storage tank charging with DHW pump/valve only. Installed Installed Installed Controlled alternating storage tank charging: DHW pump/valve in winter, electric immersion heater in summer.
--- Inactive – no DHW charging pump/diverting valve installed (factory setting). Via RF DHW charging pump/diverting valve connected to relay output Qx of an RRV91… heating circuit controller or RRV934 multi-controller. Q1 (local) DHW charging pump/diverting valve connected to relay output Q1 of the central apartment unit. Electric immersion heater Specify if an electric immersion heater is used and how it is controlled.
Configure ventilation The central apartment unit facilitates control of apartment ventilation via the multi-controller. For the other settings, see page 50 as well as the operating instructions in section “Ventilation“.
Configure switching groups (QAX913 only) Lighting and blinds control as well as scenes and info pages are operated via switching groups. 8 switching groups are available. Switching groups 1 – 4 can also be operated via softkey pairs 1 – 4 of the QAX913 central apartment unit. Switching groups 5 – 8 are always operated via the relevant operating lines.
Switching group 1 - 4 Switching group 5 - 8 Factory setting Info --- (Inactive) Prior to changing an already defined switching group function, all RF devices connected to the switching group must be disconnected (see page 86). Disconnect and deactivate any connected switching group relay before switching group function "Switch" can be changed. Per default, info pages 1 – 8 are assigned to the 4 pairs of softkeys. Changes to info page numbers are possible at the user level.
--- Inactive – no switching group relay required (factory setting). Via RF Relay output Qx of an RRV91… heating circuit controller or RRV934 multi-controller used as a switching group relay. Q1 (local) Relay output Q1 of the central apartment unit used as a switching group relay. Configure doors (QAX913 only) The QAX913 central apartment unit can monitor up to two doors and display their status on the info page. A name can be assigned to each door.
Allocation The following allocation types are available for each meter: Apartment The consumption values from the meter are billed to the apartment user. (Factory setting) General General meter whose consumption data are acquired via this central apartment unit. Consumption data from general meters are visible only at the expert level and are not directly billed to the apartment user.
Heat (inlet) Heat meter installed in flow. Heat (outlet) Heat meter installed in return. (Factory setting) Cooling energy (inlet) Cooling energy meter installed in flow. Cooling energy (outlet) Cooling energy meter installed in return. Heat and cooling energy Combine heat/cooling energy meter. This setting makes sense only if an M-bus capable meter is used. When using M-bus meters, it is important that the set metering medium agrees with the metering medium sent by the M-bus meter.
Configure electricity meter You can record up to 3 electricity meters with the central apartment unit. An allocation type and name is assigned to each electricity meter. Main menu > Commissioning > Basic configuration > Meter > Electricity > Electricity X > Electricity X: Main menu > Commissioning > Basic configuration > Meter > Electricity > Electricity X > Allocation: An electricity meter is activated as soon as the source is set to unequal "---".
Enter the desired metering medium. Main menu > Commissioning > Basic configuration > Meter > Other > Other X > Metering medium: Other Other medium if no specific medium applies. (Factory setting) Oil This meter is used for oil consumption. Steam This meter is used for steam consumption. (e.g. in district heating). When using M-bus meters, it is important that the set metering medium agrees with the metering medium sent by the M-bus meter.
Temperature display (QAX913 only) The QAX913 central apartment unit can display 3 freely selectable temperatures. The following types of temperature sensors can be used: • Room temperature sensors QAA910 via RF. • Receive temperature as S-mode object via KNX TP1 *. The 3 temperatures displayed cannot be used for control purposes (display only). * Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode devices on KNX TP1 via commissioning tool (ETS).
Configure fault input/output (QAX913 only) Fault inputs 1 – 8 The fault contact of an external component can be connected to an appropriately defined fault input. Typical components are water detectors (e.g. defective water line), an alarm output of an intrusion alarm system, or a thermal switch. Activate a fault input by assigning the corresponding fault type. Main menu > Commissioning > Basic configuration > Faults > Fault input X: --- Inactive – Fault input not required (factory setting).
Supervision (QAX913 only) Supervision contact Closing the related input terminal (e.g. via key switch) switches over the supervision state from "Inactive“ to "All monitored" or from "All monitored" to "Inactive". Specify if an external supervision contact is used and from where the central apartment unit receives its status. Main menu > Commissioning > Basic configuration > Supervision > Supervision contact: --- Inactive – no input terminal available (factory setting).
Water shutoff valve Relay output for water shutoff valve is switched over from Off to On when the corresponding water detector detects water. Specify if a water shutoff valve is available and how it is controlled. Main menu > Commissioning > Basic configuration > Supervision > Water shutoff valve: --- Inactive – water shutoff valve output not needed (factory setting). Via RF Water shutoff valve connected to: • Relay output Qx of an RRV91.. heating circuit controller or RRV934 multi-controller.
Status output 1 – 4 When the appropriate output terminal closes, the central apartment unit indicates the occurrence of events via an external component (e.g. signal lamp or horn). The events (smoke, window/door supervision, water leak, gas leak, CO alarm, panic, emergency, fault 1 - 3) leading to closure of the status output can be defined via parameter “Events status output“. For a description of this parameter, see the Operating Instructions, section “Supervision“.
Operating mode contact When the respective input terminal closes, the current operating mode for the apartment and for DHW changes. The desired operating modes can be defined when closing the contact using parameters "Apartment operating mode contact" and "DHW operating mode contact “. (See section "Service level" in the operating instructions.) Specify if an external operating mode contact is used and from where the central apartment unit receives its status.
Cooling enable Cooling is enabled by closing the contact, or disabled when the contact opens. Specify if an external cooling enable contact is used and from where the central apartment unit receives its status. Main menu > Commissioning > Basic configuration > Inputs > Cooling enable: --- Inactive – cooling enable contact not available (factory setting).
Dew point Radiator/floor cooling is disabled by closing the contact of an external dew point monitor, or enabled when the contact opens. The dew point monitor closes the room group mixing valve if a room group precontroller is installed. If only a room group pump is installed, the dew point monitor shuts off the room group pump. If there is neither a precontroller nor a room group pump, the dew point monitor closes the room valves. The dew point monitor always acts on both room groups.
--- Inactive – absence contact not available (factory setting). Via RF/S-mode • Absence contact connected to universal input B of an RRV91… heating circuit controller or to universal input Xx of an RRV934 multi-controller. • Absence signal of an S-mode object is received via KNX TP1 *. B (local) Absence contact connected to universal input B of the central apartment unit.
Heat demand relay When the appropriately defined output terminal closes, a heat demand signal is transmitted to the heat source. Specify if a heat demand relay is used and how it is controlled. Main menu > Commissioning > Basic configuration > Outputs > Heat demand relay: --- Inactive – heat demand relay not needed (factory setting). Via RF Relay output Qx of an RRV91… heating circuit controller or RRV934 multi-controller used as a heat demand relay.
--- Inactive – refrigeration demand relay not needed (factory setting). Via RF Relay output Qx of an RRV91… heating circuit controller or RRV934 multi-controller used as a refrigeration demand relay. Q1 (local) Relay output Q1 of the central apartment unit used as a refrigeration demand relay. Refrigeration demand DC 0..10 V The current refrigeration demand can be transmitted to the refrigeration source in the form of a DC 0..10 V signal.
Cooling enable When the respective output terminal closes, the cooling enable created by the central apartment unit can be communicated to external components/controllers. Specify if a cooling enable relay is used and how it is controlled. Main menu > Commissioning > Basic configuration > Outputs > Cooling enable: Inactive – cooling enable relay not needed (factory setting). Via RF/S-mode Cooling enable state issued via: • Relay output Qx of an RRV91.. heating circuit controller or RRV934 multi-controller.
Specify if a relay should be used to release the exhaust hood and how it is controlled. Main menu > Commissioning > Basic configuration > Outputs > Exhaust hood: --- Inactive – release of exhaust hood not required (factory setting). Via RF/S-mode Release of exhaust hood via: • Relay output Qx of an RRV91.. heating circuit controller or RRV934 multi-controller. • S-mode object on KNX TP1 *. Q1 (local) Use relay output Q1 of the central apartment unit for release of the exhaust hood.
Progression of outside temperature Specify if the progression of the outside temperature (info page) should be displayed. Main menu > Commissioning > Basic configuration > Info pages > Progress OT: No Do not show info page (factory setting). Yes Show info page. Progression of air pressure Specify if progression of the atmospheric pressure (info page) should be displayed. Main menu > Commissioning > Basic configuration > Info pages > Progress air press: No Do not show info page (factory setting).
Extra configuration As the basic configuration does not cover all required settings, more detailed entries are required for the following topics via the "Extra configuration" menu: • • • • Rooms Ventilation Meters Faults Rooms Assign rooms to room groups Per default, all 12 rooms are assigned to room group 1. For this room group, a common flow temperature is calculated. You can assign individual rooms to a second room group for which an independent flow temperature is calculated.
Configure ventilation Step selector These settings define which relays are to be controlled in which order/combination to put the respective ventilation stages into operation. This way, the switching order can be matched to the brand-specific connection diagrams of the ventilation equipment used. The relay to control the ventilation stages are available in the RRV934 multicontroller. This controller contains the coding for stages of the central apartment unit.
Indoor air quality sensor An indoor air quality sensor helps control the ventilation plant based on the adjusted indoor air quality setpoints. Specify if an indoor air quality sensor is installed and from where the central apartment unit receives the measured value. Main menu > Commissioning > Extra configuration > Ventilation > Inputs > IAQ sensor: --- Inactive – indoor air quality sensor not available (factory setting). Via RF/S-mode • Indoor air quality sensor (DC 0..
Ventilation contacts 1 and 2 You can set the ventilation plant to a define stage using the ventilation contacts. Two ventilation contacts are available. The plant operates at the defines stage for as long as at least one of the two contacts is closed. Specify if ventilation contacts are installed and from where the central apartment unit receives their state.
Due date This setting allows you to specify the date (day.month) when the meter values each year are saved on a due date for billing purposes. The due date applies to all meters. Main menu > Commissioning > Extra configuration > Meter > Due day date: Factory setting 31.12 Synergyr apartment In a partial migration of a Synergyr plant, the unit (---, 1..96) must be set to the value of the address plug for the WRV8x or WRI80 you want to replace.
Main menu > Commissioning > Extra configuration > Meter > … > Impulse sensor type: Reed contact with namur Meter is connected via Reed contact with Namur wiring. Impulse sensor contacts with Namur wiring offer the advantage of monitoring the meter for interruption or shortcircuit. Reed contact Meter is connected via Reed contact (factory setting). Unit factor The unit for the conversion factor required for correct meter display is set via the unit factor when connecting the meter via an impulse input.
Main menu > Commissioning > Extra configuration > Meter > … > Unit factor: Factory setting Wh Heat/cooling energy Electricity Hot/cold water Gas Other ml Pulse valency numerator and denominator Each pulse corresponds to a specific amount of consumption when connecting meters via a pulse input. Pulse valency is printed on the meter. The pulse valency (numerator and denominator) and unit factor must match. Procedure for entry: If pulse valency (e.g. liters/pulse) and the unit factor (e.g.
Start value When connecting meters via a pulse input, the meter value must be entered as start value to match the central apartment unit display to that of the meter. Entry is in digits without commas. Eight digits are available (see page 54). For the start value, you can only enter as many decimals as start value as displayed on the central apartment unit. The decimal places displayed on the central apartment unit are visible when setting the unit factor (see page 55). Example: 3 Meter display = 2.
Meter 4 Meter connected to the 2nd pulse input of the 1st pulse adapter AEW2.1 of the apartment. Meter 5 Meter connected to the 1st pulse input of the 2nd pulse adapter AEW2.1 of the apartment. Meter 6 Meter connected to the 2nd pulse input of the 2nd pulse adapter AEW2.1 of the apartment. General meter 1 Meter connected to the 1st pulse input of the pulse adapter AEW2.1 with plug 121. General meter 2 Meter connected to the 2nd pulse input of AEW2.1 with plug 121 or to the 1st pulse input of AEW2.
Fault input normal position Specify the normal position for the fault inputs. Main menu > Commissioning > Extra configuration > Faults > Fault input X > Normal position: Open An open contact is detected as "Not faulty" (factory setting). Closed A closed contact is detected as "Not faulty". When using water detector QFP910, keep the normal position on "Open". Connect RF components Notes RF components are assigned to rooms or functions.
You can connect all devices of the same room, one after the other, with having to enter additional information on the central apartment unit. Continue by switching on all RF devices to be connected to the room and connect them. The order of connection is free.
After successful connection, the room unit restarts and changes to normal operation. The binding symbol on the display disappears. If the binding process with the central apartment unit is unsuccessful, the room unit switches to unbound state display after 1 minute. Connect room temperature sensor QAA910 The room temperature sensor is automatically switched on as soon as the batteries are inserted. When switching on (power-up), the battery charge is tested.
After the battery charge test, an actuator previously connected checks its settings as a lead controller (master) or lag controller (slave). For lead controller settings, the LED blinks 3 times red/green, for lag controller settings, the LED remains dark. Afterwards, the device assumes Normal operation. Press the function button on the radiator control actuator. The LED lights up in accordance with the battery charge (green: Bat. ok, red: Bat not ok). Release the button when the LED starts blinking.
If at this point none of the heating controller channels is connected, the binding LED flashes. Pressing the binding button displays the state of the individual channels. LEDs for connected channels are lit. The LEDs of the channels not connected remain dark. When releasing the button, the heating circuit controller returns to normal operation after 7 seconds. When a channel is selected, the binding LED indicates the status of the respective channel.
To connect a heating circuit controller channel, press the channel selection button (CH) to select a suitable channel (channels Y1 and Y2 with the RRV912, channels Y1 - 8 with the RRV918). The LED of the selected channel blinks. If the selected channel is not yet connected, the binding LED flashes. If no button is pressed for 10 minutes, the heating circuit controller returns to normal operation. Press the function button on the heating circuit controller. The LED lights up green.
The DELTA reflex smoke detector is automatically switched on as soon as the inserted batteries supply power. Insert the batteries on site and when the smoke detector has assumed its future operating temperature. For detailed information, see the documentation supplied with the smoke detector. The smoke detector is connected by pressing the test button on the front of the detector for at least 2 seconds and then pressing the binding button at the rear for at least 1 second.
Connect a channel Use the channel selection button (CH) to select a suitable channel (channels U1..2, X1..4, Q1..4) to integrate a multi-controller channel. The LED of the selected channel blinks. If the selected channel is not yet connected, the binding LED flashes. If there is no user intervention for 10 minutes, the multi-controller returns to normal operation. Press the binding button on the multi-controller. The LED lights up green. Release the button when the LED starts blinking.
• Universal relay output Qx of a heating circuit controller (see page 62). • Universal relay output Qx of a multi-controller (see page 65). • RF adapter plug KRF960 (see page 72). Successful connection is displayed on the central apartment unit and confirmed with a beep. Press the Menu/ok button to exit the binding process.
Connect output for room group pump Inform the central apartment unit that you want to use an output to connect a room group pump: Main menu > Commissioning > RF connections > Room groups > Room group X > Room group pump > Connect device: The following device channels can be connected: • Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62).
The following device channels can be connected: • Universal input B of a heating circuit controller (see page 62). • Universal input Xx of a multi-controller (see page 65).
Connect outputs for the HR bypass Inform the central apartment unit that you want to use the potential-free relay contacts to connect the HR bypass: Main menu > Commissioning > RF connections > Ventilation > Outputs > HR bypass > Connect device: The following device channel can be connected: • Channel group Q4/Q5 of a multi-controller (see page 65). Connect DHW components (QAX913 only) The following DHW plant components are assigned appropriate inputs or outputs: • DHW sensor • DHW pump/valve • El.
Connect the output for the electric immersion heater Inform the central apartment unit that you want to use an output to connect an electric immersion heater: Main menu > Commissioning > RF connections > DHW > Electric immersion heater > Connect device: The following device channels can be connected: • Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62).
Connect lighting and blinds control (QAX913 only) RF adapter plugs and GAMMA wave lighting and blinds actuators can only be assigned to switching groups set up for the respective function. See page 29. The lighting and blinds actuators are switched on as soon as power is applied. When commissioning GAMMA wave light actuators, a lamp must be connected. Otherwise, the actuators are not correctly powered, i.e. they cannot be connected.
Main menu > Commissioning > RF connections > Switching group relay > Switching group X > Connect device: The following device channels can be connected: • Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62).
The consumption data interface is connected individually to each required channel. To connect a channel, select a suitable channel (P1..2 (pulse inputs), M1..3 (M-bus inputs) with the channel selection button (CH)). The channel type must match the basic meter configuration source. The LED of the selected channel blinks. If the selected channel is not yet connected, the binding LED flashes. If no button is pressed for 10 minutes, the consumption data interface returns to normal operation.
The following devices or device channels can be connected: • • • • Universal input B of a heating circuit controller (see page 62). Universal input Xx of a multi-controller (see page 65). Door/window contact wave AP 260 (see page 64). Water detector QFP910 (see page 75). Connect water detector QFP910 (QAX913 only) The water detector is automatically switched on as soon as the batteries are inserted. When switching on (power-up), the battery charge is tested.
Connect supervision components (QAX913 only) The following supervision components are assigned appropriate inputs or outputs: • • • • • Supervision contact Supervision state Water shutoff valve Gas shutoff valve Status output 1 – 4 Connect supervision contact Inform the QAX913 central apartment unit that you want to connect an input to connect a supervision contact: Main menu > Commissioning > RF connections > Supervision > Supervision contact > Connect device: The following device channels can be connec
Connect gas shutoff valve Inform the QAX913 central apartment unit that you want to connect an output to control a gas shutoff valve: Main menu > Commissioning > RF connections > Supervision > Gas shutoff valve > Connect device: The following devices or device channels can be connected: • Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62). • RF adapter plug KRF960 (see page 72).
Connect inputs Connect inputs for operating mode contact Inform the central apartment unit that you want to use an input to connect an operating mode contact: Main menu > Commissioning > RF connections > Inputs > Operating mode contact > Connect device: The following device channels can be connected: • Universal input B of a heating circuit controller (see page 62). • Universal input Xx of a multi-controller (see page 65).
Connect input for dew point Inform the central apartment unit that you want to use an input to connect a dew point monitor contact: Main menu > Commissioning > RF connections > Inputs > Dew point > Connect device: The following device channels can be connected: • Universal input B of a heating circuit controller (see page 62). • Universal input Xx of a multi-controller (see page 65).
Connect heat demand relay Inform the central apartment unit that you want to connect a heat demand output: Main menu > Commissioning > RF connections > Outputs > Heat demand relay > Connect device: The following device channels can be connected: • Universal relay output Qx of a heating circuit controller (see page 62). • Universal relay output Qx of a multi-controller (see page 65). Connect output for refrigeration demand DC 0..
Connect output for cooling enable Inform the central apartment unit that you want to connect a cooling enable output: Main menu > Commissioning > RF connections > Outputs > Cooling enable > Connect device: The following device channels can be connected: • Universal relay output Qx of a heating circuit controller (see page 62). • Universal relay output Qx of a multi-controller (see page 65).
Main menu > Commissioning > RF connections > Hager Tebis > Switching groups > Switching group X Successful dispatch of the respective telegrams is displayed briefly on the central apartment unit. For detailed information on commissioning Hager tebis components, see the documentation on Hager tebis products. Connect RF repeaters You can connect up to 3 RF repeaters. An RF repeater (1 – 3) must previously have been activated in the basic configuration to be connected (see 48).
Assign devices to RF repeaters You can specify for every individual device connected to the central apartment unit via which repeater the respective RF signals are to be forwarded. Main menu > Commissioning > Device list > Device X > RF repeater: --- No signal repetition (factory setting). RF repeater 1 Repeat signals by RF repeater 1. RF repeater 2 Repeat signals by RF repeater 2. RF repeater 3 Repeat signals by RF repeater 3. Signals from GAMMA wave devices (e.g.
Test radio connections The radio connections between the central apartment unit and the following devices can be tested at any time: • • • • • • • • • • Room temp sensor Room unit Radiator control actuator Heating circuit controller (per channel) Multi-controller (per channel) RF repeater Meteo sensor Water detector (QAX913 only) Handheld control (QAX913 only) Consumption data interface (per channel) Press briefly the binding or the multifunction button on the device.
Room groups 1 and 2 (flow sensor, return sensor, mixing valve, room group pump): Main menu > Commissioning > Wiring test > Room groups > Room group X > … Cooling release output (rooms 1 - 12): Main menu > Commissioning > Wiring test > Cooling release output > Room X Ventilation inputs (humidity sensor, indoor air quality sensor, fireplace mode, ventilation contacts 1 - 2): Main menu > Commissioning > Wiring test > Ventilation > Inputs > … Ventilation outputs (step selector, HR bypass): Main menu > Commissi
Disconnect devices Using function “Disconnect device“, devices connected to the central apartment unit can be removed again from the central unit. Disconnecting also deletes any binding information contained in the device.
Main menu > Commissioning > RF connections > RF repeater > Other RF devices > Disconnect device: You are prompted to press the binding button on the device to be disconnected. The action required on the device is the same as that required for connecting. Successful disconnection is displayed on the central apartment unit and confirmed with a beep. Close the disconnection process by pressing the Menu/ok button.
In addition, check the following settings when partially migrating a Synergyr plant: Main menu > Commissioning > RF connections > Meter > … > Replace device > Calibration date: Main menu > Commissioning > RF connections > Meter > … > Replace device > Calibration year: Changing the calibration date is not recorded as meter change.
Main menu > Commissioning > RF connections > Ventilation > Outputs > … > Device list: Main menu > Commissioning > RF connections > DHW > … > Device list: Main menu > Commissioning > RF connections > Meteo sensor > Device list: Main menu > Commissioning > RF connections > Switching group relay > Switching group X > Device list: Main menu > Commissioning > RF connections > Meter > … > Device list: Main menu > Commissioning > RF connections > Doors > Door X > Device list: Main menu > Commissioning > RF connect
Delete devices from the device list If you want to remove a device, select if possible function ”Disconnect device“ (see page 86). Defective devices may not be able to be disconnected. In this case, proceed as follows to remove the faulty device from the device list of the central apartment unit: Main menu > Commissioning > Device list > Device X > Delete device: Use function “Delete device“ only if you cannot remove the device with function ”Disconnect device“.
Programming mode If you want to assign the device address in KNX system mode (with ETS), activate programming mode via the following operating line. Main menu > Commissioning > Bus communication > Basic settings > Programming mode: Off Programming mode off (factory setting). On Addressing mode on. Clock time operation If the system should use a common time of day, one of the devices must be defined as the clock time master and the others as slaves.
In plants with consumption data acquisition, we recommend setting the clock time remote setting to "Yes" only on the caretaker's central apartment unit. This prevents changes to the due data and monthly value generation due to changes to the clock time of any other central apartment unit.. Calendar zone (holidays and special days) If several devices in the system are to use a common calendar, holiday/special day operation must be set to ”Master” on every such device, and to ”Slave” on the other devices.
Autonomous The central apartment unit DHW time switch runs autonomous. No DHW time switch data is received or sent. (Factory setting). Slave The central apartment unit uses the time switch data of the DHW time switch master. Master The central apartment unit contains the DHW time switch master and provides the time switch data to the DHW time switch slaves. When using setting “Master“, the time switch data is distributed in the DHW zone for common usage.
Setting “Refrigeration distribution zone“ is visible only when ”Yes” was selected with parameter ”2-pipe system heating/cooling“ in the basic configuration, or "Radiator/floor cooling" was selected in a room for parameter "Cooling type". Setting the refrigeration distribution zone enables the central apartment unit to respond to H/C changeover forwarded by a refrigeration source. Exit the "Commissioning" menu Press the Esc button to exit the “Commissioning” menu after commissioning.
Function settings General You must be at the expert level to enter function settings (see page 19). Change these settings only if you are fully aware of their impact. Wrong settings can impair or even disable plant operation. Buzzer volume The volume of the buzzer (piezzo loudspeaker) integrated in the central apartment unit can be adjusted to suit individual needs (0..100%).
Heating setpoint limitation Specifies the maximum permissible room temperature heating setpoint (5..35 °C) during an active setpoint limitation period. Main menu > Apartment > Settings > Heat setp limit: Factory setting 35 °C Cooling setpoint limitation Specifies the maximum permissible room temperature cooling setpoint (0..50 °C) during an active setpoint limitation period.
This way, long heating up times when changing from Economy to Precomfort or Comfort setpoint can be prevented at low outside temperatures. In the case of night setback to Economy setpoint, this function leads to outside temperature-compensated night setback. If the settings for start and end point coincide, the function is deactivated. An Economy setpoint raised through Economy increase is displayed on the central apartment unit.
Valve position cooling mode / summer operation Specifies the position to which the valve of a room is driven (0..100%) when the plant is switched to cooling mode or summer operation. The amount of cooling energy drawn by the individual rooms can thus be influenced. Rooms with high humidity levels also have a risk of condensation.
Room controller settings These settings are visible only if the user-defined heating type is set. (See page 20). P-band Xp The room controller’s P-band can be set for every room to suit individual needs.
Derivative action time Tv The room controller’s derivative action time can be set for every room. Main menu > Rooms > Room X > Room controller > Der action time Tv: For your guidance, see the default settings (factory setting 450 s): Room type Guide value Tv Radiator heating slow 450 s Radiator heating fast 540 s Floor heating slow 540 s Floor heating fast 540 s Neutral zone For rooms using 3-position actuators, the room controller’s neutral zone (0..20 K) can be set for every room.
Actuator runtime This defines the runtime of the actuator used. This is the time the actuator requires to travel from one end position to the other. The setting only acts on 3-position actuators. It has no impact on 2-position actuators and SSA955 radiator control actuators. The actuator running time (1..600 s) can be set separately for every zone valve.
TVL TVLmax TVLmin TVLmin1 TVLmin2 TAgem TAgem1 TAgem2 Flow temperature Flow temperature – maximum limitation Flow temperature – minimum limitation Flow temperature – minimum limitation (curvepoint 1) Flow temperature – minimum limitation (curvepoint 2) Composite (effectively acting) outside temperature Composite outside temperature (curvepoint 1) Composite outside temperature (curvepoint 2) Main menu > Room groups > Room group X > Limitations space heating > Flow temp min The curvepoints of the minimum f
Room group 1: [Curvepoint 1] outside temp [Curvepoint 1] flow temp min [Curvepoint 2] outside temp [Curvepoint 2] flow temp min Factory setting -20 °C 20 °C 10 °C 20 °C Room group 2: [Curvepoint 1] outside temp [Curvepoint 1] flow temp min [Curvepoint 2] outside temp [Curvepoint 2] flow temp min Factory setting -20 °C 20 °C 10 °C 20 °C If the minimum flow temperature heating setpoints at both curvepoints are set to the same value (factory setting), the composite outside temperature has no impact on th
Cooling curve The central apartment unit determines a flow temperature cooling setpoint for room cooling for each room group based on the cooling curve. The cooling curve determines the flow setpoint for room cooling based on the composite outside air temperature. The cooling curve in the central apartment unit depends on the room setpoints and thus requires parameterization as per the required cooling setpoints. Five curvepoints are available for each room group to set the cooling curve.
[Curvepoint 1] outside temp [Curvepoint 1] flow temp [Curvepoint 2] outside temp [Curvepoint 2] flow temp [Curvepoint 3..5] outside temp [Curvepoint 3..5] flow temp Factory setting 25 °C 20 °C 35 °C 20 °C --- (inactive) --- (inactive) If the minimum flow temperature cooling setpoints of the active curvepoints are set to the same value (factory setting), the composite outside temperature has no impact on the minimum flow temperature cooling setpoint.
Continuously In winter operation, the heat request is constantly valid. Switching If the averaged valve position falls below a certain level, the heat request is set invalid. (Factory setting). Valve position temperature request On/Off If ”Temperature request winter operation“ is set to “Switching“, the central apartment unit checks the averaged valve position of the respective room group. If the averaged valve position is above the value set for “Valve position temp request On“ (1..
Integral action time Tn You can set the primary controller’s integral action time Tn for each room group depending on demand (0..600 s). Main menu > Room groups > Room group X > Primary controller > Int action time Tn: Factory setting 60 s Ventilation Indoor air quality control The indoor air quality controller calculates a positioning signal based on the current setpoint (in accordance with the ventilation level) and the current indoor air quality.
Humidity limitation This function monitors the relative humidity of the air and compares it with the set ”Humidity limit value“. If the relative humidity exceeds the limit value, the ventilation system is switched on at the preselected stage to remain on until the humidity has dropped one switching differential below the limit value. The relative humidity level (r.h.) is displayed on the central apartment unit.
Main menu > Ventilation > Humidity limitation > Running time: Factory setting 30 min Pause time humidity limitation When the “Running time“ has elapsed, the ventilation system is switched off for the pause time set here (0..720 min) before it resumes operation. Main menu > Ventilation > Humidity limitation > Pause time: Factory setting 60 min Air humidity at 0 V/10 V Connect a humidity sensor (DC 0..10 V) to limit humidity.
Outside temperature limit value night cooling This setting defines the lowest outside temperature (0..50 °C) at which night cooling is allowed. Below this temperature level, night cooling is locked. Main menu > Ventilation > Night cooling > OT limit: Factory setting 12 °C Room outside temperature delta night cooling Set here the by how much as a minimum the outside temperature must lie below the room temperature (0..20 K) for night cooling to be switched on.
DHW (QAX913 only) Frost protection setpoint Set the DHW setpoint to be used in Protection mode. Main menu > DHW > Setpoints > Frost prot setp: Guide value 5 °C Legionella setpoint Set the setpoint the DHW storage tank should maintain during the time the legionella function is performed. Main menu > DHW > Legionella function > Legionella setpoint: Guide value 70 °C Legionella protection frequency Specify how often the legionella function should be activated. It can be performed daily or weekly.
Main menu > DHW > Legionella function > Legio prot period: Guide value 00.30 h.min DHW priority With DHW priority, preference can be given to DHW storage tank charging by reducing the amount of heat delivered to the heating circuits. Main menu > DHW > Settings > Priority: None No priority (factory setting): During DHW heating, there is no restriction with regard to the amount of heat delivered to the heating circuits.
Forced charging Normally, DHW storage tank charging is started only if the storage tank temperature drops below the switch-on point (DHW storage tank setpoint minus switching differential). Forced charging can enforce storage tank charging, even if this switch-on criterion has not been reached. Starting If forced charging is activated and the storage tank temperature lies at least 1 K below the normal setpoint, forced charging is started. Ending Forced charging is ended when the normal setpoint is reached.
System pump required 3131S59 If the system pump is controlled by a KNX TP1-compatible controller, it can be selected whether the system pump should run during DHW charging (depending on the selected type of plant). A Case A Case B B System pump required for DHW charging (system pump: Yes) System pump not required for DHW charging (syst. pump: No) Main menu > DHW > Settings > System pump: No The system pump does not need to run during DHW charging. Yes The system pump must run during DHW charging.
Switching groups (QAX913 only) Scene number The scenes defined during commissioning automatically is numbered (1..16). To prevent scene numbers from overlapping with other existing scene buttons (e.g. GAMMA wave or Hager tebis), or to provoke them, the scene numbers of the central apartment unit can be changed, if required.
Operating hours Shows the number of operating hours on the meter. If a pulse input of the consumption data interface WRI982 is used, the totaled number of operating hours of the WRI982 are displayed here. Main menu > Consumption data > … > Operating hours: ID number Shows the ID of the meter. Main menu > Consumption data > … > Ident number: Metering medium Shows the medium measured by the meter.
vanced from 02:00 (standard time) to 03:00 (daylight saving time), or set back from 03:00 (daylight saving time) to 02:00 (standard time). If both dates coincide on the same day, daylight saving / standard time changeover is deactivated. Main menu > Time of day/date > Summer time start Main menu > Time of day/date > Winter time start Guide value Summer time start 25.03. Winter time start 25.10.
Texts The texts for “Plant name“, “Rooms“, “Switching groups, “Doors“, “Light status“ and “Temperatures“ and "Handheld control“ can be entered at the service level and are thus described in the operating instructions. File name A data set can be created with the ACS service tool and copied to the central apartment unit.
Heat request 0..10 V To be able to transmit a temperature request (for space heating and DHW) to a heat demand controller by means of a 0..10 V signal, the temperature setpoint at 0 V and 10 V must be predefined for the central apartment unit. The values in between are interpolated in a linear way. Temperature requests below the selected temperature request threshold are not forwarded to the heat demand controller (0 V).
Refrigeration request 0..10 V To be able to transmit a temperature request (for room cooling) to a refrigeration request controller by means of a 0..10 V signal, the temperature setpoint at 0 V and 10 V must be predefined for the central apartment unit. The values in between are interpolated in a linear way. Temperature requests above the selected temperature request threshold are not forwarded to the heat demand controller (0 V).
Exhaust hood Impact of window switches For operation of the exhaust hood, at least one of the windows in one of the rooms defined here must be open. Main menu > Settings > Exhaust hood > Imp window switches: Factory setting --- (no influence by window switches) Handheld control (QAX913 only) Buttons of the handheld control can be assigned already at the service level and are described in the operating instructions.
Device list repeater When using RF repeaters, the list of devices to be repeated by the central apartment unit is loaded in the RF repeater. The device list is loaded when the assignment of RF repeaters or the device list is changed. The following display shows if the device list has been loaded successfully in the RF repeater. Main menu > Device information > Device list repeater: Loading.. Loading of the device list in the RF repeater in progress. Up-to-date Device lists are up to date, i.e.
System limits System limitations (TP1 bus) 126 Central apartment units Limitations per central apartment unit 1 12 2 4 3 5 4 4 4 3 3 2 94 Meteo sensor Rooms Door contacts (supervised, QAX913 only) Light actuators with status indication (only on KNX TP1 (S-mode) QAX913 only) RF repeater Handheld control (QAX913 only) Heat meter (heat, cooling energy or combined) Hot water meter Cold water meter Electricity meter Gas meter Other meters (e.g.
Communication Protocol KNX is used as protocol (radio and/or wire). KNX TP1 KNX RF 2-wire bus as per KNX TP1, with additional RJ45 plug connection to connect service tool. RF bus conforming to KNX RF Maintenance/service Peripheral devices Restore factory settings To restore the factory settings of the peripheral devices, press the multifunction or binding button on the device for at least 20 seconds. Press simultaneously the two upper buttons on the handheld control for at least 20 seconds.
Disposal Dispose of the central apartment unit and the associated partner devices as electronic waste in compliance with European directive 2002/96/EEC (WEEE), and not together with general garbage. Observe all relevant national regulations using correct disposal channels. Comply with local and currently valid legislation. Dispose of exhausted batteries in compliance with relevant environmental regulations. 125 / 134 Siemens Building Technologies Synco™ living Disposal CE1C2740en 13.12.
Index 0 0..10 V heat request............... 119 0..10 V Refrigeration demand .. 46 0..10 V refrigeration request... 120 2 2-pipe heating/cooling system ... 49 3 3-position actuator.................... 67 A Absence ................................... 43 Connect ................................ 79 Actuator runtime..................... 101 Precontroller ....................... 106 Air pressure progress............... 49 Air quality sensor...................... 52 Allocation..........................
GAMMA wave act. ............... 72 GAMMA wave actuator ........ 83 Gas shutoff valve ................. 77 H/C changeover ................... 78 Hager tebis........................... 81 Handheld control .................. 77 Heat demand relay............... 80 Humidity sensor ................... 68 Lighting........................... 72, 81 Meteo sensor ....................... 71 Meter .................................... 73 Multi-controller...................... 65 Return sensor.......................
End daylight saving time ........ 116 ERF910 .............................. 48, 82 Exhaust hood ........................... 47 Influence window contact ... 121 Exit commissioning .................. 94 Expert Level..................................... 19 Password.............................. 95 External DHW .......................... 27 Extra configuration ................... 50 F Factory setting.................... 3, 124 Fault history............................ 117 Fault input normal position .......
L Lamps Name............................ 35 Legionella protection Frequency .......................... 111 Period................................. 111 Time ................................... 111 Legionella setpoint ................. 111 Limitation Cooling setpoint ................... 96 Flow temperature ............... 101 Heating setpoint ................... 96 Humidity ............................. 108 Return temp. ........................ 24 Return temperature ............ 103 System ...................
Period Legionella protection... 111 Power supply bus..................... 90 Precontroller Actuator runtime ................. 106 Integral action time Tn........ 107 P-band Xp .......................... 106 Prepare connection .................. 18 Priority DHW .......................... 112 Procedure Commissioning ....... 18 Product liability ......................... 11 Programming mode.................. 91 Progress air pressure............... 49 Progression outside temp. .......
Limitation.............................. 95 Setting room controller............. 99 Simulate outside temperature . 117 Source Fault input ............................ 58 Meter .................................... 32 SSA955.................................... 61 SSA955 manual control ......... 124 Start daylight saving time....... 116 Start value................................ 57 Startup delay Ventilation stages............... 110 Status output............................ 40 Step selector ..................
/ 134 Siemens Building Technologies Synco™ living CE1C2740en 13.12.
© 2006-2010 Siemens Switzerland Ltd Subject to change Siemens Switzerland Ltd Industry Sector Building Technologies Division Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/sbt 0678 7 4 3 1 9 0 7 5 5 0 134 / 134 Siemens Building Technologies Synco™ living 74 319 0755 0a CE1C2740en 13.12.