User Manual

36 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Temperature display (QAX913 only)
The QAX913 central apartment unit can display 3 freely selectable tempera-
tures. The following types of temperature sensors can be used:
Room temperature sensors QAA910 via RF.
Receive temperature as S-mode object via KNX TP1 *.
The 3 temperatures displayed cannot be used for control purposes
(display only).
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Activate the required temperatures and enter the names to be used for their
display.
Main menu > Commissioning > Basic configuration
> Temperature display > Temperature X > Temperature X:
Main menu > Commissioning > Basic configuration
> Temperature display > Temperature X > Function:
--- Inactive – no temperature display required
(factory setting).
Active Temperature display active.
Display fault status message bus
Specify if only the controller-internal faults lead to fault status messages on
the central apartment unit or, in addition, the faults received via bus as well.
This setting also impacts any fault output that may be activated.
Main menu > Commissioning > Basic configuration
> Faults > Display fault bus:
No Only the controller-internal faults result in fault status
messages (factory setting).
Yes Both controller-internal faults and faults received via
bus result in fault status messages.