Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Dew point
Radiator/floor cooling is disabled by closing the contact of an external dew
point monitor, or enabled when the contact opens.
The dew point monitor closes the room group mixing valve if a room group
precontroller is installed. If only a room group pump is installed, the dew point
monitor shuts off the room group pump. If there is neither a precontroller nor a
room group pump, the dew point monitor closes the room valves. The dew
point monitor always acts on both room groups.
Specify if an external dew point monitor is used and from where the central
apartment unit receives its status.
Main menu > Commissioning > Basic configuration
> Inputs > Dew point:
--- Inactive – dew point monitor not available
(factory setting).
Via RF/S-mode Dew point monitor connected to universal input B
of an RRV91… heating circuit controller or univer-
sal input Xx of an RRV934 multi-controller.
Dew point monitor signal received through S-mode
object via KNX TP1 *
B (local) Dew point monitor connected to universal input B of
the central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Absence
“Absence“ is triggered when the respective input terminal closes.
The room temperature setpoints are switched to the respective absence set-
point (per room) and any activated time program for presence simulation
starts via the switching groups.
DHW heating, ventilation and cooling also operate according to the operating
mode selected for the period of absence.
See the operating instructions for a detailed description of ”Absence“.
Specify if an external absence contact is used and from where the central
apartment unit receives its status.
Main menu > Commissioning > Basic configuration
> Inputs > Absence: