s Synco™ living Mounting and commissioning Edition 3.0 Controller series C CE1C2707en 23.08.
We congratulate you … … on the selection of the Siemens Synco™ living system and thank you for purchasing the central apartment unit! The present document describes how to mount and commission the central apartment unit and the other system components. First, please ensure that you become familiar with the operating philosophy of the central apartment unit. Operation itself is covered by the Operating Istructions (B2707en).
Contents Safety notes..................................................................................................... 9 Mounting and installation............................................................................. 10 Mount the central apartment unit .............................................................. 10 Mounting regulations .......................................................................... 10 Mounting location .................................................................
Configure inputs ................................................................................. 39 Operating mode contact .............................................................. 39 Summer operation ....................................................................... 39 Heating / cooling changeover ...................................................... 40 Absence....................................................................................... 41 Twilight....................................
Connect outputs for the step selector .......................................... 64 Connect outputs for the HR bypass ............................................. 64 Connect DHW components................................................................ 65 Connect the input for the DHW sensor ........................................ 65 Connect the output for the DHW pump / valve ............................ 65 Connect the output for the electric immersion heater .................. 66 Connect meteo sensor ..
Function settings .......................................................................................... 87 General..................................................................................................... 87 Buzzer volume ................................................................................... 87 Password expert level ........................................................................ 87 Apartment ...............................................................................
DHW ....................................................................................................... 103 Frost protection setpoint................................................................... 103 Legionella setpoint ........................................................................... 103 Legionella protection frequency ....................................................... 104 Legionella protection time ................................................................
Safety notes Product liability • Use the products only in building services plants and only for the applications described. • Comply with all local safety regulations (installation, etc.) • Do not open the devices. Non-adherence will void any warranty offered by Siemens. • If a device is defective or damaged, immediately disconnect it from power and replace it. • Application-related technical data are only guaranteed in connection with the Siemens Synco™ living system.
Mounting and installation Mount the central apartment unit Mounting regulations • The central apartment unit is designed in compliance with safety class II and must be mounted accordingly. • Power may be applied to the unit only when completely mounted. Otherwise, there is a risk of electric shock by the connection terminals. • The unit must not be exposed to dripping water. • The permissible environmental conditions specified in the technical data must be observed (refer to Data Sheet N2707en).
• The typical range between transmitter and receiver in residential buildings is 30 m, or across 2 floors, or 2 concrete ceilings. But depending on the type of house or building and the materials used, the effective range can be considerably greater or smaller.
Mounting procedure Mounting method / knockout holes The base of the central apartment unit can be mounted directly on the wall or on a recessed conduit box. It has an opening at the rear and 2 knockout holes (one at the top and one at the bottom). If required, the hole(s) must be knocked out before securing the base to the wall. Holes The base must be secured to the wall with at least 3 screws.
Swing the electronics section 45° upward and pull it towards you to remove it. Fit the base Secure the base to the wall using at least 3 fixing screws. Wiring Wiring is described under “Connection terminals / wiring“ (refer to page 14). Replace the electronics section Insert the electronics section at an angle of about 45° in the base (left and right). Then, swing it downward until it engages. The central apartment unit is now ready for commissioning.
Electrical installation of the central apartment unit Installation regulations • • • • Comply with local regulations (installation, etc.). Only qualified staff may carry out electrical installations. Prior to installation, disconnect the central apartment unit from power! The connection terminals for low-voltage and mains voltage are arranged on different sides of the unit. • When wiring the unit, satisfy requirements of safety class II. • Provide cable strain relief.
c d 2707Z24 CEKNX CE+ M B N L Q13 Q14 230 V Detail view e Legend c Mains voltage or protective extra low-voltage Q13, Q14 Potential-free, universal relay output d Mains voltage N Operating voltage, neutral conductor AC 230 V L Operating voltage, live conductor AC 230 V e Protection by extra-low voltage CE-, CE+ M B Connection data bus KNX TP1- and KNX TP1+ Ground for universal input Universal input F Strap for cable ties 15 / 124 Siemens Building Technologies Synco™ living Mounting and install
Commissioning the system Prerequisites Prior to commissioning the system, check to ensure that the following prerequisites are met: • You are familiar with the different operating elements and operating levels of the central apartment unit. • All system components are correctly installed. • Mains-powered components are connected to power. • New batteries are readily available to be inserted in the battery-powered devices *. • Wired devices are connected to the KNX TP1 data bus.
When the central apartment unit is commissioned for the first time, you are prompted to select the language you require, and to set the time of day, the year, and the date. Then, the display changes to the default picture. The language and the time format can also be selected during operation. For description, refer to the Operating Instructions. 01:32 Tuesday 14.02.2006 1013 hPa 20°C 5°C If the central apartment unit was in operation before (e.g.
Select the Commissioning menu From the “Main menu“ of the central apartment unit, select submenu “Commissioning“ and confirm the selection by pressing the Menu/ok button. Caution! Plant stops Commissioning Basic configuration… RF connections… Device list… Bus communication… Then, you are informed that the plant stops. Confirm by pressing the Menu/ok button to shut down the plant and to go to the ”Commissioning“ menu. You are now on the “Commissioning“ menu – the plant has been stopped.
Usually, the standard heating types suffice. Customize settings only in plants with greatly differing control behavior.
Room number 1 Room name Factory setting Your setting --- Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditioner Supervision only --- (inactive) Active Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditi
Room number 4 Room name Factory setting Your setting --- Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditioner Supervision only --- (inactive) Active Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditi
Room number 7 Room name Factory setting Your setting --- Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditioner Supervision only --- (inactive) Active Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditi
Room number 10 Room name Factory setting Your setting --- Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air conditioner Supervision only --- (inactive) Active Heating type --- (inactive) Radiator heating slow Radiator heating fast Floor heating slow Floor heating fast Rad/floor user-defined Air conditioner Cooling type --- (inactive) Release output Air condit
Configure room groups A number of rooms can be combined to one room group. Two independent room groups can be formed. For each room group, the flow temperature can be controlled, a room group pump defined, and the return temperature limited.
Function Define the function required for the room group. A room group may include a primary controller function with or without return temperature limitation.
Room group pumps and DHW charging pump: B1 B2 B3 M2 M1 M3 U2 U1 M1 B1 K E T M2 / M3 B2 / B3 U1 U2 Y1 Y2 DHW pump / diverting valve DHW sensor Electric immersion heater Consumer (radiator or floor heating) Room temperature sensor or room unit Room group pumps 1 and 2 Flow sensors room groups 1 and 2 Mixing valve for room group 1 (radiators) Mixing valve for room group 2 (floor heating) Radiator control actuator Heating circuit valve (2-position) Define whether room group pumps are installed and how
Type of return temperature limitation The return temperature of both room groups can be limited: Minimum or maximum limitation. To provide return temperature limitation, a return sensor is required. The room group’s “function“ must be set to “Primary controller + return sensor“.
Configure DHW charging 2707Z30 If you want DHW charging controlled directly by the central apartment unit, activate the required DHW plant components (DHW sensor, pump / valve, electric immersion heater). If you require external DHW heating controlled remotely via KNX TP1, activate ”Operation external DHW“. If there is a request for DHW, the room group pumps are not put into operation. For this reason – from the hydraulics point of view – DHW must always be installed upstream of the room groups.
DHW temperature sensor State whether a DHW temperature sensor is used and from where the central apartment unit receives the actual value.
Electric immersion heater State whether an electric immersion heater is used and how it is controlled.
Configure ventilation The central apartment unit facilitates control of apartment ventilation via the multi-controller. For the other settings, refer to section “Extra configuration“ and the operating instructions in section “Ventilation“.
Configure the switching groups Lighting and blinds control as well as scenes and info pages are operated via switching groups. 8 switching groups are available. Switching groups 1 – 4 can also be operated via soft key pairs 1 – 4 of the central apartment unit. Switching groups 5 – 8 are always operated via the relevant operating lines.
Main menu > Commissioning > Basic configuration > Switching groups > Switching group X > Function: Switching group 1 2 Factory setting Info Info 3 Info 4 Info 5 --- 6 --- 7 --- 8 --- Your setting --Switch Dim Blind Scene Info --Switch Dim Blind Scene Info --Switch Dim Blind Scene Info --Switch Dim Blind Scene Info --Switch Dim Blind Scene --Switch Dim Blind Scene --Switch Dim Blind Scene --Switch Dim Blind Scene Switching group name ………………… ………………… ………………… ………………… ………………… ………………… ………
The central apartment unit transmits the switching group commands to the switching group actuators – via RF and the wired bus.
Switching group 4 Factory setting --- 5 --- 6 --- 7 --- 8 --- Your setting --- (none) Via RF Q1 (local) --- (none) Via RF Q1 (local) --- (none) Via RF Q1 (local) --- (none) Via RF Q1 (local) --- (none) Via RF Q1 (local) Configure doors The central apartment unit can monitor up to two doors and display their status on the info page. A name can be assigned to each door.
Lamp 1 Factory setting --- 2 --- 3 --- 4 --- Your setting --- (inactive) Active --- (inactive) Active --- (inactive) Active --- (inactive) Active Name of lamp ………………… ………………… ………………… ………………… Info page “Light state“ is displayed only if at least one of the 4 lamps is activated. To indicate the light status, switch or dim actuators of any manufacture can be used which, via S-Mode KNX TP1 *, communicate with the central apartment unit.
Display fault status message bus Define whether only the controller-internal faults lead to fault status messages on the central apartment unit or, in addition, the faults received via bus as well. This setting also impacts any fault output that may be activated.
Fault input 1 Factory setting --- 2 --- 3 --- 4 --- 5 --- 6 --- 7 --- 8 --- Your setting --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) --Via RF / S-Mode B (local) Fault outputs 1 and 2 If system faults occur, they can be forwarded to an external component by closing a fault output.
Configure inputs By closing a contact at the input terminal, the respective input function can be triggered. Activate the respective input function by stating from where the central apartment unit receives the signal of the input terminal (Via RF / S-Mode, B (local)). Operating mode contact When the respective input terminal closes, the current operating mode for the apartment and for DHW changes.
B (local) Summer operation contact connected to universal input B of the central apartment unit * The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode devices on KNX TP1 is made with a commissioning tool (ETS) Main menu > Commissioning > Basic configuration > Inputs > Summer operation: Factory setting Your setting ----Via RF / S-Mode B (local) Heating / cooling changeover When the respective input terminal closes its contact, the system switches from heatin
Absence “Absence“ is triggered when the respective input terminal closes. The room temperature setpoints are switched to the respective absence setpoint (per room) and any activated time program for presence simulation starts via the switching groups. DHW heating, ventilation and cooling also operate according to the operating mode selected for the period of absence. For a detailed description of ”Absence“, refer to the Operating Instructions.
--- Inactive – twilight switch not installed Via RF / S-Mode • Twilight switch connected to universal input B of an RRV91… heating circuit controller or to universal input Xx of an RRV934 multi-controlller • Twilight switch connected to external contact input of a door / window contact wave AP 260 • Twilight signal of an S-Mode object is received via KNX TP1 * B (local) Twilight switch connected to universal input B of the central apartment unit * The connection of the relevant S-Mode objects of the c
Heat demand DC 0..10 V The current heat demand can be transmitted to the heat source in the form of a DC 0..10 V signal. The temperature values corresponding to DC 0 V and 10 V and the threshold value for a valid heat request can be set (refer to page 111). State whether the DC 0..10 V heat demand output is used and how it is controlled. --- Inactive – DC 0..
Status output When the appropriate output terminal closes, the central apartment unit indicates the occurrence of events via an external component (e.g. signal lamp or horn). The events (smoke, window/door supervision, fault inputs 1 - 8) leading to closure of the status output can be defined via parameter “Events status output“. For a description of this parameter, refer to the Operating Instructions, section “Supervision“. State whether a status output is used and how it is controlled.
Main menu > Commissioning > Basic configuration > Outputs > Window/door state: Factory setting Your setting ----Via RF / S-Mode Q1 (local) Exhaust hood To release the exhaust hood, at least one of the windows in the selected rooms must be open, thus making certain that operation of the exhaust hood does not produce underpressure in the room. State whether a relay should be used to release the exhaust hood and how it is controlled.
Configure info pages Windows / doors Define if you want to display open doors / windows (info page). Main menu > Commissioning > Basic configuration > Info pages > Windows/doors: Factory setting Your setting No Yes No Business card State whether the business card (info page) should be displayed.
Main menu > Commissioning > Basic configuration > Miscellaneous > 2-pipe H/C system: Factory setting Your setting No Yes No Extra configuration Extra configuration is used to assign the individual rooms to a room group. In addition, it is possible to define for each room how the cooling release output is controlled. In addition, extra configuration facilitates coding of the ventilation stages and definition of the ventilation inputs and outputs.
Cooling release output State how the cooling release output of the respective room is controlled. --- Inactive – cooling release output not required Via RF / S-Mode Cooling release output via: • Relay output Qx of an RRV91..
Configure ventilation Step selector These settings define which relays are to be controlled in which order / combination to put the respective ventilation stages into operation. This way, the switching order can be matched to the brand-specific connection diagrams of the ventilation equipment used. The relays for control of the ventilation stages are located in the RRV934 multicontroller, which receives coding of the stages from the central apartment unit.
Indoor air quality sensor An indoor air quality sensor facilitates control of the ventilation plant based on the adjusted indoor air quality setpoints. State whether an indoor air quality sensor is installed and from where the central apartment unit receives the measured value --- Inactive – no indoor air quality sensor installed Via RF / S-Mode • Humidity sensor (DC 0..
Ventilation contacts 1 and 2 Using the ventilation contacts, the ventilation plant can be set to a defined stage. Two ventilation contacts are available. As long as at least one of them is closed, the plant operates at the defined stage. State whether ventilation contacts are installed and from where the central apartment unit receives their state.
Connecting RF components Notes RF components are assigned to rooms or functions. On the central apartment unit, the required rooms must be configured beforehand (refer to page 18), the required functions activated and the mode of transmission set to “Via RF“ or ”Via RF / S-Mode“ (refer to page 25 ff.). If, by mistake, a device has been connected twice, the central apartment unit ignores the second connection, delivers an error message and a beep.
Connect QAW910 room unit The room unit is automatically switched on as soon as the batteries are inserted. When the room unit is switched on, the full display appears for 2 seconds. If the batteries are close to exhaustion, exhaustion, the low-battery symbol appears. As long as the room unit is not connected, the display shows the binding symbol and the room temperature. A room unit which had previously been connected changes directly to normal operation after the full display.
Connect the QAA910 room temperature sensor The room temperature sensor is automatically switched on as soon as the batteries are inserted. When switching on (power-up), the batteries’ capacity is tested. If the capacity is sufficient, the green LED is lit for 2 seconds during the test. If the batteries’ capacity is not sufficient for operation, the red LED is lit for 2 seconds – provided capacity is still sufficient. After the battery test, the device changes directly to normal operation.
Now, press the multifunction button on the radiator control actuator. The LED lights up in accordance with the batteries’ capacity (green: Bat. ok, red: Bat. not ok). You can release the binding button when the LED blinks. If the room temperature is acquired with the built-in sensor of a radiator control actuator, the control actuator whose sensor should be used must be connected first. No consideration is given to the sensors of the other radiator control actuators of a room.
If, thus far, none of the heating controller channels has been connected, the binding LED flashes. The other LEDs remain dark. When you press the multifunction button, the status of the individual channels is indicated. The LEDs of the channels already connected light up, those of the channels not connected remain dark. When releasing the button, the heating circuit controllers return to normal operation after 10 seconds.
For detailed information, refer to the documentation covering the GAMMA wave products. The door / window contact is connected by pressing the multifunction button on the door or window contact for at least one second. If the learning telegrams were forwarded, the LED blinks for about 3 seconds. To confirm the successful connection, the central apartment unit delivers a beep. When all devices of the room are connected, close the binding process by pressing the Menu/ok button.
Front of RRV934 multi-controller = LED and button for the binding test, communication error, binding CH = channel selection button U, X, Q = LEDs for the channels Connection of the multi-controller takes place per channel or channel group. Connect a channel To integrate a multi-controller channel, use the channel selection button (CH) to select a suitable channel (channels U1..2, X1..4, Q1..4). The LED of the selected channel blinks. If the selected channel is not yet connected, the binding LED flashes.
If you press the channel selection button again, the channel group selection is reduced by one channel (e.g. from Q1..Q3 to Q1..Q2, etc.). When you reach the channel group size required for the desired function, press the binding button on the multi-controller. The LEDs light up green. When it starts blinking, you can release the binding button. After successful binding, the multi-controller is restarted. Now, the multi-controller is ready again for the connection of another channel or channel group.
Connect room group components The following room group components are assigned the respective inputs or outputs: • • • • Mixing valve Flow sensor Return sensor Room group pump The components can be connected for room groups 1 and 2. On the room group components, the respective input and output functions must be set to "Via RF", enabling an input or output of a heating circuit controller or multi-controller to be assigned to them.
Now, press the binding button on the multi-controller. The LED lights up green. When it starts blinking, you can release the binding button. A successful connection appears on the display of the central apartment unit and confirmed with a beep. Close the binding process by pressing the Menu/ok button.
A successful connection appears on the display of the central apartment unit and confirmed with a beep. Close the binding process by pressing the Menu/ok button.
Connect input for open fireplace mode Inform the central apartment unit that you want to use a universal input B of a heating circuit controller or a universal input Xx of a multi-controller as an input for chimney mode: Main menu > Commissioning > RF connections > Ventilation > Inputs > Open fireplace mode > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are then prompted to press the binding button on the device to be connected.
Connect outputs for the step selector Inform the central apartment unit that you want to use the potential-free relay contacts Q1..Q3 of a multi-controller for connecting the step selector for control of the fan: Main menu > Commissioning > RF connections > Ventilation > Outputs > Step selector > Connect device: Step selectors can only be connected via the universal relay outputs Q1..Q3 of a multi-controller. Confirm subentry “Connect device“ by pressing the Menu/ok button.
Now, press the binding button on the multi-controller. The LED lights up green. When it starts blinking, you can release the binding button. A successful connection appears on the display of the central apartment unit and confirmed with a beep. Close the binding process by pressing the Menu/ok button.
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected. Select a universal relay output Qx with the channel selection button (CH) on the heating circuit controller or multi-controller. The LED of the selected channel blinks. If the selected channel is not yet connected, the binding LED flashes. Now, press the multifunction button on the heating circuit controller or multicontroller.
After the battery test, the device changes directly to normal operation. The LED extinguishes again. Now, press multifunction button F on the meteo sensor. The LED lights up in accordance with the batteries’ capacity (green: Bat. ok, red: Bat. not ok). When the LED starts blinking, you can release the binding button.
Connect GAMMA wave actuator Press the button on the GAMMA wave actuator until the LED on the actuator starts blinking (approx. 10 seconds). A successful connection appears on the display of the central apartment unit and is confirmed with a beep. The LED on the actuator extinguishes again. You can connect all actuators of the same switching group, one after the other, without having to make further entries on the central apartment unit.
Confirm sub item "Connect device" by pressing the Menu/ok button. You are prompted to press the binding button on the device to be connected to establish connection. The door / window contact is connected by pressing the function button on the door / window contact for at least one second. After the learning telegrams are sent, the LED blinks for about 3 seconds. Successful connection is displayed on the central apartment unit and confirmed by a beep.
A successful connection appears on the display of the central apartment unit and is confirmed with a beep. Close the binding process by pressing the Menu/ok button. Connect fault outputs Inform the central apartment unit that you want to use a universal relay output Qx of a heating circuit controller or multi-controller as a fault output: Main menu > Commissioning > RF connections > Faults > Fault output X (1 - 2) > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button.
Connect input for summer operation Inform the central apartment unit that you want to use universal input B of a heating circuit controller or a universal input Xx of a multi-controller for connecting a summer operation contact: Main menu > Commissioning > RF connections > Inputs > Summer operation > Connect device: Confirm subentry “Connect device“ with the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected.
Connect input for absence Inform the central apartment unit that you want to use a universal input B of a heating circuit controller or a universal input Xx of a multi-controller for connecting an absence contact: Main menu > Commissioning > RF connections > Inputs > Absence > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected.
Connect outputs Connect the output for heat demand DC 0..10 V Inform the central apartment unit that you want to use universal output U of the RRV912 heating circuit controller or of the multi-controller as a DC 0..10 V heat demand output: Main menu > Commissioning > RF connections > Outputs > Heat demand DC 0...10 V > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected.
Connect the output for summer operation Inform the central apartment unit that you want to use a universal relay output Qx of a heating circuit controller or multi-controller as a summer operation output: Main menu > Commissioning > RF connections > Outputs > Summer operation > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected.
Connect the window / door state output Inform the central apartment unit that you want to use a universal relay output Qx of a heating circuit controller or a multi-controller as a window / door state output: Main menu > Commissioning > RF connections > Outputs > Window /door state > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected.
Connect Hager tebis devices Hager tebis lighting and blinds actuators can only be assigned to switching groups or lights which, beforehand, were set up for the respective function (refer to ”Configure the switching groups“ on page 32 and “Configure light status indication“ on page 35). The lighting and blinds actuators are switched on as soon as power is applied to them.
Inform the central apartment unit that you want to connect an RF repeater: Main menu > Commissioning > RF connections > RF repeater > RF repeater X > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected. Now, to open the connection, press multifunction button F on the RF repeater. The LED lights up green. When it starts blinking, you can release the binding button.
Main menu > Commissioning > RF connections > RF repeater > Other RF devices > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. To make the connection, you are prompted to press the binding button on the device to be connected. Connecting RF adapter plugs KRF960 and KRF961 Press the button on the RF adapter plug. The LED lights up permanently. When it starts blinking, you can release the button.
Wiring test On completion of the configuration and connection of the devices, it is recommended to make the wiring test with the connected components. The current states of the inputs are displayed: • The current temperature value at the sensor inputs • 0 / 1 with input contacts (0: contact open, 1: contact closed) • 0..100% at DC 0..10 V inputs During the wiring test, each of the outputs can be set to a certain value: • 0..100% (corresponding to DC 0..10 V) for heat demand DC 0..
Faults (fault inputs 1…8, fault outputs 1 and 2): Main menu > Commissioning > Wiring test > Faults > …: Inputs (Operating mode, summer operation, H/C changeover, absence, twilight): Main menu > Commissioning > Wiring test > Inputs: Outputs (heat demand relay, heat demand DC 0..
Main menu > Commissioning > RF connections > Inputs > … > Disconnect device: Main menu > Commissioning > RF connections > Outputs > … > Disconnect device: Main menu > Commissioning > RF connections > RF repeater > RF repeater X > Disconnect device: Main menu > Commissioning > RF connections > RF repeater > Other RF devices > Disconnect device: You are now prompted to press the binding button on the device to be disconnected.
Main menu > Commissioning > RF connections > Outputs > … > Device list: Main menu > Commissioning > RF connections > RF repeater > RF repeater X > Device list: Main menu > Commissioning > RF connections > RF repeater > Other RF devices > Device list: Displaying the device list with all devices All connected devices (max. 64) are included in the device list. The device list shows the device state of every device.
Bus communication Device address KNX TP1 You need to enter an unambiguous device address for the central apartment unit. After entry, the central apartment unit checks whether the address entered has already been assigned. If the address is still free, the display returns to the “Basic settings“ menu. The value has been adopted. Otherwise, you are prompted to enter a new address.
Clock time operation When using setting “Autonomous“, the device does not receive or send the time of day. If the system is to use a common time of day, one of the devices must be defined as the clock time master and the others as slaves. Main menu > Commissioning > Bus communication > Time of day/date > Clock time op: Factory setting Your setting Autonomous Autonomous Slave Master Ensure that only one device in the system is defined as the clock time master.
Main menu > Commissioning > Bus communication > Holidays/special days > Hol/spec day zone: Factory setting Your setting 1 Ensure that only one device per holiday / special day zone is defined as the holiday / special day master. DHW zone Use the following operating line to set the DHW zone for DHW heating (1..31): Main menu > Commissioning > Bus communication > DHW > DHW zone: The DHW zone setting must be unambiguous. For example, only one DHW heating system may have DHW zone 1.
Set the outside temperature zone (1..31) and the heat distribution zone (1..31) and the refrigeration distribution zone (1..31) where the central apartment unit is located. When using setting "---", no data of the respective distribution zone is sent or received via bus.
Function settings General To make function settings, you need to be on the expert level (refer to page 17). Change these settings only if you are fully aware of their impact. Wrong settings can impair or even disable plant operation. Buzzer volume The volume of the buzzer (piezzo loudspeaker) integrated in the central apartment unit can be adjusted to suit individual needs (0..100%).
Apartment Enable setpoint limitation This defines whether setpoint limitation of the room temperatures is basically disabled or enabled. Only when setpoint limitation is enabled does the central apartment unit respond to the setpoint limitation signals received over the wired bus. Main menu > Apartment > Settings > Setpoint limitation: Factory setting Your setting Enabled Disabled Enabled Limitation setpoint This defines the maximum permissible room temperature setpoint (0..
Economy increase The Economy room setpoint for heating all rooms is raised depending on the composite outside temperature. The increase at low outside temperatures (e.g. end point -15 °C) is greater and negated at higher outside temperatures (e.g. starting point -5 °C). This way, long heating up times when changing from Economy to Precomfort or Comfort setpoint can be prevented at low outside temperatures.
If 1 room unit and 2 room temperature sensors are used, the average value of the 2 room temperature sensors is determined first. Then, the actual value of the average room temperature is calculated based on the percentage proportion set for the room unit and the room temperature sensor. When 2 room temperature sensors are used, the average value of the 2 sensors is delivered. The proportion of the individual sensors cannot be changed.
even if the room temperature is sufficiently high. It is accepted that in such cases the room might get overheated. Main menu > Rooms > Room X > Room settings > Min valve pos comf: Factory setting Your setting 0% H/C changeover locking time Changeover locking time prevents heating mode from changing to cooling mode (and vice versa) too quickly and too frequently. This means that when changing over, heating or cooling mode is disabled.
Integral action time Tn The room controller’s integral action time can be set for every room.
Neutral zone For rooms using 3-position actuators, the room controller’s neutral zone (0..20 K) can be set for every room. For your guidance, refer to the default settings: Room type Guide value neutral zone Radiator heating slow 0.1 K Radiator heating fast 0.1 K Floor heating slow 0.1 K Floor heating fast 0.1 K Main menu > Rooms > Room X > Room controller > Neutral zone: Room number Room name Factory setting Setting Neut. 1 2 3 4 5 6 0.1 K 0.1 K 0.1 K 0.1 K 0.1 K 0.
Actuator running time This defines the running time of the actuator used. This is the time the actuator requires to travel from one end position to the other. The setting only acts on 3-position actuators. It has no impact on 2-position actuators and SSA955 radiator control actuators. The actuator running time (1..600 s) can be set separately for every zone valve.
TVL TVLmax TVLmin TVLmin1 TVLmin2 TAgem TAgem1 TAgem2 Flow temperature Flow temperature – maximum limitation Flow temperature – minimum limitation Flow temperature – minimum limitation (curvepoint 1) Flow temperature – minimum limitation (curvepoint 2) Composite (effectively acting) outside temperature Composite outside temperature (curvepoint 1) Composite outside temperature (curvepoint 2) Main menu > Room groups > Room group X > Limitations > Flow temperature min… The curvepoints of the minimum flow tem
Room group 1: [Curvepoint 1] outside temp Factory setting -20 °C [Curvepoint 1] flow temp min 20 °C [Curvepoint 2] outside temp 10 °C [Curvepoint 2] flow temp min 20 °C Your setting …………… °C …………… °C …………… °C …………… °C Room group 2: [Curvepoint 1] outside temp Factory setting -20 °C [Curvepoint 1] flow temp min 20 °C [Curvepoint 2] outside temp 10 °C [Curvepoint 2] flow temp min 20 °C Your setting …………… °C …………… °C …………… °C …………… °C If the minimum flow temperature setpoints at both curvepoi
Main menu > Room groups > Room group X > Limitations > Return temp min: Factory setting Your setting Room group 1 --- Room group 2 --- …………… °C …………… °C Main menu > Room groups > Room group X > Limitations > Return temp max: Factory setting Your setting Room group 1 --- Room group 2 --- …………… °C …………… °C Setpoint increase mixing valve To enable the room group mixing valves to offset the temperature variations of the heat source, the temperature of the main flow must be higher than the flow tempera
Valve position temperature request On / Off If ”Temperature request winter operation“ is set to “Switching“, the central apartment unit checks the averaged valve position of the respective room group. If the averaged valve position lies above the value set for “Valve position temp request On“ (1..30%), the heat request is forwarded to heat generation. If the averaged valve position lies below the value set for “Valve position temp request Off“ (1..30%), the heat request to heat generation is suppressed.
Integral action time Tn You can set the primary controller’s integral action time Tn for each room group depending on demand (0..600 s).
P-band Xp indoor air quality A P-controller is used to ensures that the indoor air quality is maintained at the required setpoint. The controller’s P-band (0..2000 ppm) can be set here. Within this range, all available stages are switched on and off. Main menu > Ventilation > IAQ controller > P-band Xp: Factory setting Your setting 400 ppm Humidity limitation This function monitors the relative humidity of the air and compares it with the set ”Humidity limit value“.
Switching differential of humidity limitation If the ventilation system was switched on because humidity in the room was too high, it is switched off again when humidity drops below the “Humidity limit value“ by the switching differential set here (1..20%). Main menu > Ventilation > Humidity limitation > Switching diff: Factory setting Your setting 5% Running time humidity limitation The humidity limitation interval starts with the running time set here (0..720 min).
Minimum operating time night cooling If all switch-on conditions for night cooling are met, it is switched on for at least the period of time set here (0..720 min). Main menu > Ventilation > Night cooling > Operating time min: Factory setting Your setting 30 min Reference room night cooling To be able to determine the necessary temperature differential, the central apartment unit requires the room temperature plus the outside temperature.
Startup delay The startup delay (00.00..60.00 mm.ss) prevents the individual ventilation stages from switching on too quickly. Each time a stage is switched on, the delay time must elapse before the next stage can be switched on. Main menu > Ventilation > Ventilation settings > Startup delay: Factory setting Your setting 00.00 mm.ss Locking time After switching off, each ventilation stage remains locked for the period of time set here (00.00..60.00 mm.ss).
Main menu > DHW > Legionella function > Legionella setpoint: Guide value Your setting 70 °C Legionella protection frequency Decide and set how often the legionella function should be activated. It can be performed daily or weekly. With the weekly legionella function, the weekday can be selected (Mo..Su). When using setting “Never“, the legionella function is always deactivated.
DHW priority With DHW priority, preference can be given to DHW storage tank charging by reducing the amount of heat delivered to the heating circuits. No priority During DHW heating, there is no restriction with regard to the amount of heat delivered to the heating circuits. The highest temperature request (space heating or DHW) is forwarded to the heat demand controller. Absolute priority During DHW heating, the heating circuits are not allowed to draw any heat.
Forced charging Normally, DHW storage tank charging is started only if the storage tank temperature drops below the switch-on point (DHW storage tank setpoint minus switching differential). Forced charging can enforce storage tank charging, even if this switch-on criterion has not been reached. Starting If forced charging is activated and the storage tank temperature lies at least 1 K below the normal setpoint, forced charging is started. Ending Forced charging is ended when the normal setpoint is reached.
System pump required 3131S59 If the system pump is controlled by a KNX TP1-compatible controller, it can be selected whether the system pump should run during DHW charging (depending on the selected type of plant). A Case A Case B B System pump required for DHW charging (system pump: Yes) System pump not required for DHW charging (syst.
Switching groups Scene number The scenes defined during commissioning automatically is numbered (1..16). To prevent scene numbers from overlapping with other existing scene buttons (e.g. GAMMA wave or Hager tebis), or to provoke them, the scene numbers of the central apartment unit can be changed, if required.
Time of day / date Summer time start / winter time start The change from summer time to winter time, and vice versa, takes place automatically. The earliest changeover date can be adjusted should the relevant standards change. As a result of the dates set for the change from winter time to summer time, or vice versa, the time of day on the first Sunday after that date is brought forward from 02:00 ( winter time) to 03:00 (summer time), or set back from 03:00 (summer time) to 02:00 (winter time).
Inputs / outputs Simulation of outside temperature For test purposes, outside temperatures of between -50 and 50 °C can be simulated on the central apartment unit. In that case, the measured value of the outside sensor is overridden. The simulated outside temperature is also used for the composite and the attenuated outside temperature. During the time simulation is active, fault status message “Outside temperature simulation active“ is displayed. Simulation must be manually reset (setting ---).
Business card title and lines 1 – 4 The electronic business card is displayed in the form of an info page and has one title line and 4 text lines where, for example, information about the company or person responsible for the plant can be entered. Main menu > Settings > Texts > Business card > Title: Main menu > Settings > Texts > Business card > BC line 1 – 4: Temperature request 0..10 V To be able to transmit a temperature request (for space heating and DHW) to a heat demand controller by means of a 0..
Exhaust hood Impact of window switches For operation of the exhaust hood, at least one of the windows in one of the rooms defined here must be open.
System limits System limitations (TP1 bus) 126 Central apartment units QAX910 Limitations per central apartment unit 1 12 2 4 3 64 Meteo sensor Rooms Door contacts (monitored) Light actuators with status indication (only on KNX TP1(S-Mode)) RF repeaters RF devices (total number, including the central apartment unit) In addition to the above mentioned devices, switch, dim and blind actuators can be used in unlimited numbers.
Maintenance / service Peripheral devices Restore factory settings To restore the factory settings of the peripheral devices, press the multifunction or binding button on the device for at least 20 seconds. Then, a restart is made. Now, the factory settings are restored and the device is no longer connected to the central apartment unit.
Index 2 2-pipe H/C system ................... 46 3 3-position output ...................... 60 A absence configure .............................. 41 connect................................. 72 actuator running time primary controller ................. 98 room controller ..................... 94 air humidity DC 0..10 V .......... 101 AP260 .................... 56, 68, 69, 72 assign devices ......................... 77 B backup data ........................... 112 basic configuration ...................
DHW charging time maximum ..... 105 configure............................... 28 conn. electric immers. heat. . 66 connect components ............ 65 connect pump / valve ........... 65 connect sensor ..................... 65 electric immersion heater ..... 30 external................................. 30 forced charging................... 106 frost protection.................... 103 legionella protection ........... 103 priority................................. 105 pump ..............................
connect................................. 64 humidity DC 0..10 V ............... 101 humidity limitation .................. 100 pause time.......................... 101 running time ....................... 101 switching differential........... 101 humidity sensor cofigure ................................ 49 connect................................. 62 I IAQ sensor configure ............... 50 impact window switches exhaust hood ..................... 112 increase Economy ...................
numbering inputs...................... 76 O open fireplace mode................. 50 operating mode contact configure............................... 39 connect................................. 70 operational external DHW configure............................... 30 output ....................................... 42 configure............................... 42 cooling release ............... 48, 59 DHW pump........................... 65 electric immersion heater ..... 66 exhaust hood..................
configure .............................. 24 connect components ............ 60 function................................. 25 name ............................ 24, 110 pump .................................... 25 room temperature sensor......... 69 connect................................. 54 room unit connect .................... 53 room-outside temp delta night cooling ....................... 102 RRV912 ................................... 55 RRV918 ................................... 55 RRV934 ..............
connect................................. 63 ventilation stages locking time ........................ 103 rundown time...................... 103 startup delay....................... 103 volume buzzer.......................... 87 VVS-ID ................................... 112 connect .................................75 windows/doors..........................46 winter operation temperature request .............97 winter time start ......................109 wiring ........................................
/ 124 Siemens Building Technologies Synco™ living CE1C2707en 23.08.
/ 124 Siemens Building Technologies Synco™ living CE1C2707en 23.08.
© 2006-2008 Siemens Switzerland Ltd Subject to change Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Phone +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/sbt 0678 7 4 3 1 9 0 5 3 2 0 124 / 124 Siemens Building Technologies Synco™ living 74 319 0532 0c CE1C2707en 23.08.