User Manual

111 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Business card title and lines 1 – 4
The electronic business card is displayed in the form of an info page and has
one title line and 4 text lines where, for example, information about the com-
pany or person responsible for the plant can be entered.
Main menu > Settings > Texts > Business card > Title:
Main menu > Settings > Texts > Business card > BC line 1 – 4:
Temperature request 0..10 V
To be able to transmit a temperature request (for space heating and DHW) to
a heat demand controller by means of a 0..10 V signal, the temperature set-
point at 0 V and 10 V must be predefined for the central apartment unit. The
values in between are interpolated in a linear way. Temperature requests
below the selected temperature request threshold are not forwarded to the heat
demand controller (0 V).
Main menu > Settings > Heat request > Temp request 0 V:
Main menu > Settings > Heat request > Temp request 10 V:
Main menu > Settings > Heat request > Temp request thresh:
DC 0..10 V
0
2
4
6
8
10
10 20 30 40 50 60
70 80 90
100
110
120
°C
2707Z32
3
2
1
0
c
Value in °C at DC 0 V
d
Value in °C at DC 10 V
e
Threshold value of temperature request (temperatures below this level are interpreted
as “No demand for heat”)
Factory setting Your setting
Temperature request at 0 V 0 °C
Temperature request at 10 V 100 °C
Temperature request threshold 0 °C