User Manual

18 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Select the Commissioning menu
From the “Main menu“ of the central apartment unit, select submenu “Com-
missioning“ and confirm the selection by pressing the Menu/ok button.
Caution!
Plant stops
Then, you are informed that the plant
stops. Confirm by pressing the
Menu/ok button to shut down the
plant and to go to the ”Commission-
ing“ menu.
Commissioning
Basic configuration…
RF connections…
Device list…
Bus communication…
You are now on the “Commissioning“
menu – the plant has been stopped.
It is switched on again only when
manually quitting the ”Commission-
ing” menu by pressing the Esc button
(no timeout).
Configure rooms
Activate the required rooms by selecting a heating / cooling type other than “---“
or by activating function ”Supervision only“.
Main menu > Commissioning > Basic configuration
> Rooms > Room X > Heating type:
Main menu > Commissioning > Basic configuration
> Rooms > Room X > Cooling type:
Main menu > Commissioning > Basic configuration
> Rooms > Room X > Supervision only:
The following heating types are available:
--- Inactive – all relevant room heating infor-
mation and all operating lines are hidden
Radiator heating slow Radiator heating in buildings with massive
walls, heavy construction
Radiator heating fast Radiator heating in buildings with light
walls, light construction
Floor heating slow Floor heating in buildings with massive
walls, heavy construction and massive
floor construction
Floor heating fast Floor heating in buildings with light walls,
light construction and light floor construc-
tion
Rad/floor user-defined Control parameters can be manually set
Air conditioner For rooms in which an air conditioner is
used for heating