User Manual

49 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Configure ventilation
Step selector
These settings define which relays are to be controlled in which order / combi-
nation to put the respective ventilation stages into operation.
This way, the switching order can be matched to the brand-specific connection
diagrams of the ventilation equipment used.
The relays for control of the ventilation stages are located in the RRV934 multi-
controller, which receives coding of the stages from the central apartment unit.
Main menu > Commissioning > Extra configuration
> Ventilation > Step selector > Coding stage 1:
Main menu > Commissioning > Extra configuration
> Ventilation > Step selector > Coding stage 2:
Main menu > Commissioning > Extra configuration
> Ventilation > Step selector > Coding stage 3:
Factory setting Your setting
Stage 1 --- Step relay 1
Step relay 2
Step relay 3
Stage 2 --- Step relay 1
Step relay 2
Step relay 3
Stage 3 --- Step relay 1
Step relay 2
Step relay 3
When coding the stages, several step relays can be activated simulta-
neously. It is thus possible to define any step relay combinations.
Humidity sensor
Using a humidity sensor, the maximum air humidity can be limited to the set
value.
State whether a humidity sensor is installed and from where the central
apartment unit receives the measured value.
--- Inactive – no humidity sensor installed
Via RF / S-Mode Humidity sensor (DC 0..10 V) connected to universal
input Xx of an RRV934 multi-controller
Humidity sensor signal received through S-Mode
object via KNX TP1 *
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with the help of a commissioning tool (ETS).
Main menu > Commissioning > Extra configuration
> Ventilation > Inputs > Humidity sensor:
Factory setting ---
Your setting ---
Via RF / S-Mode