Front of RRV934 multi-controller
= LED and button for the binding test, communication error, binding
CH = channel selection button
U, X, Q = LEDs for the channels
Connection of the multi-controller takes place per channel or channel group.
Connect a channel
To integrate a multi-controller channel, use the channel selection button (CH)
to select a suitable channel (channels U1..2, X1..4, Q1..4). The LED of the
selected channel blinks. If the selected channel is not yet connected, the
binding LED flashes.
If there is no user intervention for 10 minutes, the multi-controller
returns to normal operation.
Now, press the binding button on the multi-controller. The LED lights up
green. When it starts blinking, you can release the binding button.
After successful binding, the multi-controller is restarted.
Now, the multi-controller is ready again for the connection of another channel
or channel group.
Connect a channel group
Functions requiring more than one channel are integrated as a channel group.
In that case, the connection is made jointly for the entire channel group.
Channel groups can be created with multifunctional outputs Q1..3 and Q4/5.
When, with the channel selection button (CH), you select the first channel of a
channel group that is not yet integrated, all LEDs of the channels available to
that channel group blink, including Q1..Q3, for example. If the channel group
is not yet connected, the binding LED flashes.
If one of the channel groups is already connected, the individual chan-
nels of this channel group can be no longer selected when navigating.
On the other hand, no other channel group can be formed if an indi-
vidual channel has already been connected.
If there is no user intervention for 10 minutes, the multi-controller
returns to normal operation.