User Manual

97 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Main menu > Room groups > Room group X
> Limitations > Return temp min:
Room group 1 Room group 2
Factory setting --- ---
Your setting
…………… °C
…………… °C
Main menu > Room groups > Room group X
> Limitations > Return temp max:
Room group 1 Room group 2
Factory setting --- ---
Your setting
…………… °C
…………… °C
Setpoint increase mixing valve
To enable the room group mixing valves to offset the temperature variations of
the heat source, the temperature of the main flow must be higher than the flow
temperature required by the respective room group. Using this setting, you
define the required increase
(0..50 K).
Main menu > Room groups > Room group X
> Settings > Setp incr mix valve:
Room group 1 Room group 2
Factory setting 0 K 0 K
Your setting
…………… °C
…………… °C
Temperature request winter operation
This defines the validity of a heat request for room heating from a room group
during winter operation:
Continuously In winter operation, the heat request is constantly valid.
Switching If the averaged valve position falls below a certain level,
the heat request is set invalid.
Main menu > Room groups > Room group X
> Settings > Temp request winter:
Room group 1 Room group 2
Factory setting Switching Switching
Your setting Continuously
Switching
Continuously
Switching