s Synco™ living Operating Instructions Edition 3.0 Controller series C CE1B2707en 23.08.
Congratulations … … on choosing the Siemens Synco™ living system and thank you for purchasing the central apartment unit! These operating instructions describe how to operate the central apartment unit and other system components. Symbols used The symbols on the central apartment unit’s are explained in section “Symbols on the display” on page 21.
Contents Safety notes..................................................................................................... 9 System overview ........................................................................................... 10 System functions ...................................................................................... 10 Central unit ......................................................................................... 10 Heating / cooling..............................................
Supervision ........................................................................................ 27 Apartment ................................................................................................. 28 Apartment timer function .................................................................... 28 Apartment operating mode................................................................. 28 Operating mode via contact ...............................................................
Stage assignment for smoke.............................................................. 48 Stage assignment for ventilation contact............................................ 48 Switching times .................................................................................. 48 Ventilation stage................................................................................. 49 Reason ............................................................................................... 49 HR bypass.............
Supervision............................................................................................... 65 Supervision delay............................................................................... 65 Release of supervision....................................................................... 66 Windows ...................................................................................... 66 Doors ...........................................................................................
Radio plug adapter........................................................................................ 85 Operation KRF960 (switching).................................................................. 85 Operation KRF961 (dimming)................................................................... 85 Service ........................................................................................................... 86 Monitor batteries ......................................................................
Safety notes Product liability • Use these products only in building services plant and only for the applications described. • Comply with all local safety regulations (installation, etc.). • Do not open the devices. Opening the devices will void warranty by Siemens. • If a device is defective or damaged, disconnect it from power immediately and replace it. • Application-related technical data are only guaranteed in connection with the Siemens Synco™ living system.
System overview System functions The Synco™ living system offers you a host of choices. In addition to room climate and DHW heating control, the system enables you to control a ventilation system, lighting and blinds, to monitor smoke detectors and door / window contacts as well as to release air conditioners. Central unit Central apartment unit QAX910 The heart of the system is the QAX910 central apartment unit.
Room temperature setpoints The room temperature setpoints for heating and cooling can be set individually for each room and for each room operating mode (Comfort, Precomfort, Economy and Protection). The room operating mode can be set or change over automatically based on the respective room time switch. The room time switch influences heating and cooling. Separate time switches are available for ventilation and DHW.
Multi-controller RRV934 Receives the flow temperature setpoints of the assigned room groups from the central apartment unit (radio) and controls the flow temperatures accordingly. To do this, the controller measures the flow temperatures and controls the wired actuators of the respective room group. The precontroller additionally allows for minimum or maximum limitation of the return temperature.
Ventilation control The central apartment unit has a ventilation time switch providing 6 switching points for each day for 7 weekdays and one special day. Each switching point allows for changing over between the ventilation operating modes (Comfort, Precomfort and Economy). Ventilation stage control is carried out via air quality, relative room humidity, current apartment operating mode (Comfort, Precomfort, Economy, Protection) or ventilation stage selection.
Weather station The central apartment unit receives the outside temperature and the atmospheric pressure from the meteo sensor. Meteo sensor QAC910 The meteo sensor acquires the outside temperature and the absolute atmospheric pressure and transmits both via radio signal to the central apartment unit. The current measured values of outside temperature and atmospheric pressure as well as the pressure trend can be shown in the quiescent picture.
Operation of lights and blinds The lights and blinds can be controlled with the central apartment unit’s softkeys. Prerequisite for this operation is that the light and blind actuators used have a binding facility for KNX-RF (KRF960, KRF961, Siemens GAMMA wave or Hager tebis TX radio) or KNX TP1. Supervisory functions The central apartment unit monitors the connected window contacts, door contacts and smoke detectors.
System components The following components can be used in the Synco™ living system or can be combined with it: Synco QAX910 Central apartment unit QAW910 Room unit QAA910 Room temperature sensor QAC910 Meteo sensor RRV912 Heating circuit controller, controls one 3-position or two 2-position actuators RRV918 Heating circuit controller, controls up to eight 2-position actuators RRV934 Multi-controller Controls up to 3 fan speeds and the HR bypass, or controls 2 independent room groups.
GAMMA wave DELTA reflex smoke detector with smoke detector module wave UNI M 255 Door and window contact wave AP260 (wireless) GAMMA wave light and blind actuators, switchable sockets and handheld transmitters can also be used Hager tebis TX radio Light and blind actuators from Hager can be used The central apartment unit can also control light and blind actuators via KNX TP1 (S-Mode). In that case, configuration with the ETS (EIB tool software) is required.
Central apartment unit QAX910 Operating elements All operating elements are located on the front of the unit. The buttons provide the following functions: DHW button, ventilation button The button is used to operate DHW and ventilation. For selecting the DHW operating mode (Auto / Normal / Reduced / Protection), and for manually triggering one-time forced charging of the DHW storage tank (extended pressure on button).
Arrow up button For navigating upward within a menu level, for scrolling backward on the info pages, and for setting (increasing) values. Arrow down button For navigating downward within a menu level, for scrolling forward on the info pages, and for setting (decreasing) values. Esc button For navigating backward to the next higher menu level, for quitting the main menu, and for canceling entry of a value.
Display Backlit display When pressing any of the buttons, the backlit display is switched on for a certain period of time. When pressing the Esc button, the Menu / ok button, the Arrow button or Info button, the backlit display is switched on with no impact on the display itself. The brightness of the backlit display can be adjusted to suit individual needs (refer to page 73). Display The display offers a choice of presentations. The example below shows a menu.
Navigating on the display / information about paths Navigation is made possible with the 2 Arrow buttons, the Menu / ok button and the Esc button (refer to description of the operating elements on page 18). In the description of functions, the location of the function is given in Italics in the form of a path. Example: Main menu > Time of day/date To reach the function from the quiescent picture, press the Menu / ok button first (you reach the main menu).
Supervision Door open Flashing: Supervised door opened Windows / doors Partly monitored Window open Flashing: Supervised window opened Windows / doors All monitored Temperatures, atmospheric pressure and weather trend Room temperature Outside temperature Weather trend: Sunny Weather trend: Partly cloudy Weather trend: Rainy Atmospheric pressure steady Atmospheric pressure rising Atmospheric pressure strongly rising Atmospheric pressure falling Atmospheric pressure strongly falling The symbols used for t
Operation Quiescent picture The display shows the quiescent picture as long as no button is pressed. There are 6 formats of quiescent pictures with different degrees of detail available. The settings required for the desired quiescent picture format are described on page 74 ff. Info pages The info pages give an overview of the plant’s most important data. Values cannot be readjusted on the info pages. The info pages can be called up with the Info button.
Menu level Press the Menu / ok button to go from the quiescent picture or the info page to the menu level (main menu). Press the Esc button to return to the quiescent picture. The menu header “Main menu” and associated symbol are display followed by a list of available menus. Main menu Apartment… Rooms… Ventilation… DHW… Setting principle General rules Values are always readjusted in an additional window on the display (edit popup). The range of action (cursor) always appears inverse.
Selecting options Supervision release Room 1 Room 2 Room 3 On the option list, one or several options can be marked with a cross by pressing the Menu / ok button. When pressing the Esc button, a final dialog appears to store the new value (Menu / ok button) or to cancel the setting (Esc button). Creating / editing text Room 1 Use the Arrow buttons to select the individual characters from the character set and the 4 permanently displayed special fields.
Access levels To select the access level, press the Esc button and the Menu / ok button simultaneously. A pop-up window appears. Press the Arrow buttons to select the required access level and confirm the selection with the Menu / ok button. User level The user level shows the settings most frequently used. Normally, these settings are sufficient for operating the plant. Service level This operating level contains extended settings that are only rarely used.
General Absence If you leave the house for a few hours, you can press the Absence / Supervision button to inform the central apartment unit about your departure. Shortly pressing the Absence / Supervision button opens the presence window which allows you to enter the desired state "Absent" or "Present" via the Arrow buttons or the Absence / Supervision button.
During the set supervision delay, you can close the corresponding doors and windows. After all supervised windows are closed, the constant signal sound turns into a beep whose interval doubles during the last 15 seconds of the set supervision delay. If a supervised window or door is opened during the supervision period, an associated fault message is triggered and other predefined actions are initiated (with an adjustable message delay for doors).
The central apartment unit display shows MAN for manual mode and the symbol for a manually set apartment operating mode. The selected apartment operating mode is valid until reset manually to Auto. The apartment operating mode can also be selected via the following operating line: Main menu > Apartment > Apartment operating mode > Preselection: Auto The room control loops and ventilation maintain their setpoints in accordance with the respective operating modes.
Summer operation of heating Select the point in time your heating system should switch to summer mode. In summer mode, all room operating modes switch to Protection, the valves travel to the position defined for summer operation and DHW heating switches to the electric immersion heater, if installed. In the case of summer changeover via the external switch, this parameter has no impact (hidden). Input function “Summer operation“ must be appropriately configured when commissioning the plant.
Antilime function To prevent valves and pumps from seizing, the controller periodically drives all valves to their fully open positions and activates all connected pumps in a stepwise fashion at predefined points in time.
Rooms 1 – 12 Room operating modes In addition to the operating mode for the entire apartment, each room has its own operating mode which you can select to suit your needs. Main menu > Rooms > Room X > Room operating mode > Preselection: Auto The room is controlled in accordance with the time program and the holiday / special day program. Comfort The room is maintained at the Comfort setpoint. Precomfort The room is maintained at the Precomfort setpoint (for short periods of absence, e.g.
Plant operating mode The individual rooms can be configured merely for heating/cooling operation, or for automatic changeover between the two operating modes. Main menu > Rooms > Room X > Room operating mode > Plant optg mode: Auto The plant operating mode is changed over automatically based on room temperature and mixed outside temperature. Heating The plant is in heating mode. Cooling The plant is in cooling mode.
To change over between the plant operating modes heating and cooling, the preset H/C changeover locking time must be expired. This avoids frequent changeover. The central apartment unit checks the mixed outside air temperature as a second criterion and compares it to the outside temperature heating limit and the outside temperature cooling limit (see page 31).
Room number Room name Factory setting Setting --- 7 8 9 --- --- 10 --- 11 --- 12 --- --- = no impact (according to the time program) = Comfort = Precomfort = Economy = Protection Changeover of the respective room operating mode takes place only if the room operating mode during absence is set to a lower level than the room operating mode for normal operation. Release of air conditioner Set the room operating mode that is to be released for cooling by the air conditioner.
Room temperature setpoints You can adjust the room temperature setpoint for each individual room and for heating and cooling (Comfort, Precomfort, Economy, Protection). The central apartment unit maintains the respective setpoint, depending on the selected apartment / room operating mode and / or time program.
Readjustment of room unit The room temperature setpoint readjustment (+/- 3 K) made on the room unit can be displayed on the central apartment unit for each room: Main menu > Rooms > Room X > Room setpoints > Readjustm room unit: The readjustment made on the room unit only acts on the Comfort and the Precomfort setpoint.
Copying switching times When you scroll to the end of the switching point list, option “Copy to:“ will appear. You can copy the switching times of the respective day to any other weekday (including the special day) or to a number of weekdays (Mo – Fr or Mo – Su). Monday Copy to: Setting new switching points For every weekday and the special day, you can set and define up to 6 switching points where the room temperature setpoint should change.
Monday - - :06:00 -From Comf To delete a switching point, press the Arrow buttons until “- - : - -“ appears (before 00:00 and after 24:00).
Economy increase The state of the Economy increase (Inactive / Active) can be queried for each room: Main menu > Rooms > Room X > Room state > Eco increase: Setpoint limitation This operating line shows if setpoint limitation is active in the room (triggered by the central communication unit via wire bus).
Optimum start / stop control acts between all operating levels, except when switching between Precomfort and Comfort: Comfort mode Precomfort mode Economy mode Protection The optimization time (forward shift) can be limited to a maximum value, separately for optimum start and optimum stop control (optimum start control 48 hours / optimum stop control 06.00 hh.mm). When setting the optimization time to ---- or 00.00, the function is deactivated.
Room number Room name Factory setting Max temp. alarm Min temp. alarm 7 8 9 10 11 12 ---- ---- ---- ---- ---- ---- Window airing function As soon as the central apartment unit detects an open window, the window airing function is activated in the corresponding room. In that case, the radiator control valve is limited to its current travel, even if the room temperature drops. If the window remains open after the set window airing hold time, the room operating mode is lowered to Protection mode.
Silent mode The SSA955 radiator control actuator can also be operated in silent mode when used in noise-sensitive rooms (e.g. in the sleeping room). Silent mode increases the actuator’s power consumption, thus reducing battery life.
Room group This parameter shows the room group to which the corresponding room was assigned during commissioning (additional configuration). Main menu > Rooms > Room X > Room settings > Room group: Room groups States The following paths can be used to display the various states of the room group. Return temperature actual value Shows the current return temperature actual value of the corresponding room group.
Room valve position max Determines the room within the room group whose valve is open the widest. The opening value (calculated value for heat demand without influence of other functions) is displayed in this operating line. Main menu > Room groups > Room group X > State > Room valve pos max: Ventilation Operating mode Stage selection The stage selector allows for either defining automatic stage selection or setting the ventilation plant to a fixed stage.
State Displays the current ventilation operating mode (Comfort, Precomfort, Economy, Protection). Main menu > Ventilation > Operating mode > State: Reason Displays the reason for the current ventilation operating mode (state).
Stage setpoints Stage assignment to operating modes The individual ventilation operating modes can be assigned to the corresponding ventilation stages via stage setpoints. This setting has no influence, if ventilation is controlled by relative humidity or air quality.
Stage assignment for smoke Specify the stage for ventilation when the central apartment unit detects smoke. Main menu > Ventilation > Stage setpoints > Smoke: Factory setting Setting Off Off Stage 1 Stage 2 Stage 3 Stage assignment for ventilation contact Specify the stage for ventilation when the ventilation contact is closed.
Ventilation state Ventilation stage Shows the active ventilation stage (Off, Stage1, Stage2, Stage3). Main menu > Ventilation > Ventilation state > Vent stage: Reason Display the reason for the current ventilation stage. Possible reasons: • • • • • • • • • • • Commissioning No request Operating mode Air quality Ventilation contact Humidity limitation Night cooling Stage selector Window open Smoke Forced ventilation Main menu > Ventilation > Ventilation state > Cause: HR bypass Shows if HR bypass (e.g.
Open fireplace mode Shows if ventilation was switched via external contact to open fireplace operation (Off, On). Main menu > Ventilation > Ventilation state > Fireplace mode: Ventilation contacts Shows the current state of the two ventilation contacts (Off, On). Main menu > Ventilation > Ventilation state > Ventilation contact1: Main menu > Ventilation > Ventilation state > Ventilation contact2: Service Service interval Specify after how many hours (0..99,999) ventilation needs service (e.g.
Indoor air quality control Indoor air quality is controlled to the setpoint of the current ventilation operating mode. The central apartment unit acquires air pollution, compares it to the setpoint and switches between the ventilation stages as needed. The switching between the ventilation stages depends on the number of existing ventilation stages. The current room air pollution (ppm) is displayed on the central apartment unit. The stage selection setting must be set to Auto (see page 45).
Stage setpoint for humidity limitation If the measured humidity exceeds the humidity limit value, ventilation is started at the stage set here. Main menu > Ventilation > Humidity limitation > Stage setpoint: Factory setting Setting Stage 1 Off Stage 1 Stage 2 Stage 3 Humidity limit value Specify the desired humidity limit value (1..99% r.h.). Main menu > Ventilation > Humidity limitation > Humidity limit: Factory setting Setting 85% r.h.
Stage setpoint for night cooling Specify here the stage for the ventilation plant when night cooling is active. Main menu > Ventilation > Night cooling > Stage setpoint: Factory setting Setting Stage 1 Off Stage 1 Stage 2 Stage 3 Precooling time max Night cooling is released only during the set maximum precooling time (0..2880 min). When the setting is 0 min, night cooling is disabled.
Runtime forced ventilation Forced ventilation is active for the runtime set for forced ventilation (0..60 min). After expiration of this time, ventilation returns to the ventilation stage prior to forced ventilation. Main menu > Ventilation > Ventilation settings > Runtime forced vent: Factory setting Setting 30 min Impact of window switches If at least one window is open in one of the set rooms, the ventilation stage is activated as per the setting (see page 47).
Forced DHW charging With a long push on the central apartment unit’s DHW button, one-time forced charging of the DHW storage tank to the Normal setpoint is triggered. During the time forced charging is active, the DHW symbol on the display flashes .
Operating mode via contact Specify the type of DHW operating mode the controller is to change over to when an external operating mode contact is connected (e.g. teleswitch for remote operation by phone). Operating mode changeover via external contact overrides all other operating mode settings. The input function “operating mode contact” must be configured during commissioning. The same operating mode contact is used for heating / cooling, ventilation and DHW.
Actual value of the DHW temperature The actual value of the DHW temperature can be displayed: Main menu > DHW > DHW state > Act val DHW temp: DHW temperature setpoint The current DHW temperature setpoint can be queried: Main menu > DHW > DHW state > DHW temp setpoint: Operating state of charging pump and electric immersion heater The current operating state of the charging pump and the electric immersion heater can be displayed: Main menu > DHW > DHW state > Charging pump: Main menu > DHW > DHW state > El
Changeover to electric immersion heater Select whether in summer operation the DHW should be heated by the electric immersion heater. Yes When the plant switches to summer operation (refer to page 30), the DHW is heated by the electric immersion heater. This means that heat generation can be switched off in the summer. No DHW is heated by the heat source in the summer also. This means that heat generation in the summer remains in operation (emergency operation).
Switching groups Operating the switching groups Switching groups 1 – 4 can be operated via the 4 pairs of softkeys on the central apartment unit. The functions of the switching groups (e.g. switching or dimming lights, opening or closing blinds, calling up info pages or scenes) were defined when the plant was commissioned. Switching groups 5 – 8 have no buttons for direct access.
You operate a switching group defined as Scene under: Main menu > Switching groups > Switching group X > Scene A or B > Trigger scene: The text displays for scenes A and B can be adjusted to suit your needs (refer to page 60). Scenes When commissioning the plant, the softkeys of the central apartment unit (switching groups 1 – 4) can be programmed for triggering scenes (scene symbol appears on the display of the key assignment).
Select the event (or the events) that triggers a switching group configured for Blind: Main menu > Switching groups > Switching group X > Events up cmd: Main menu > Switching groups > Switching group X > Events down cmd: Select the event (or the events) that triggers a switching group configured for Scene: Main menu > Switching groups > Switching group X > Scene A or B > Events scene: The following events are available for triggering switching group functions: Absence ON Execution of command when changing
Time switch release Define for each switching group if the time switch is to be enabled always or only for absence. Main menu > Switching groups > Switching group X > Time switch release: Always The time switch of the switching group is always considered. If absent The time switch of the switching group is considered only for absence.
Activating simulation of presence The effect of presence simulation (release and function) can be set individually for each switching group: Release “Release” allows you to control switching groups in dependence of a time switch or as a combination of time switch and twilight switch.
Example of release according to the time switch and the twilight switch: B2707Z02 On A Off B Off C BR D On DA On Off A B C D A Time program presence simulation (On, Off) B Absence (On, Off) C Twilight (DA = DARK, BR = BRIGHT) D Release of simulation (On, Off) t E FG t Time Function “Function” allows you to control switching groups by at random or constant switch-on of a switching group.
Off Off On On Off On On Off The settings Release and Function become effective as soon as the central apartment unit is set to "Absent" via Absence / Supervision button“: B2707Z04a On A Off 3..30 Min 3..30 Min On B Off On C Off t A Simulation release (On, Off) B Light (On, Off) with function "Random" C Light (On, Off) with Function "Continuously on" t Time The presence simulation is ended as soon as the central apartment unit is set to "Present".
Main menu > Supervision > Volume supervis dly: Factory setting Your setting 15% Setting 0% deactivates the signal sound / beep during supervision delay . Release of supervision Indicate in the central apartment unit the doors and windows that are to be "partly monitored" or "all monitored". These two functions provide for two different types of supervision, e.g. for short absences when you want to keep open some windows for ventilation and thus exclude them from supervision. And for longer absences (e.g.
Doors You can supervise up to two doors. The doors you want to supervise can be selected in the option list. Main menu > Supervision > Doors > Rel "Partly monit": Main menu > Supervision > Doors > Rel "All monit": Supervision type Factory setting Setting Partly monitored --- (no door) Door 1 Door 2 All monitored --- (no door) Door 1 Door 2 Message delay doors If a supervised door is opened, the fault message "Door open" appears only after expiration of a set message delay time.
Event buzzer and status output Decide with which event the buzzer and / or the status output is to be activated (smoke, window / door supervision or fault input 1 – 8).
Every entry can be deleted. Main menu > Holidays/special days > Calendar > Entry X: During holiday periods, the selected apartment operating mode and the holiday DHW operating mode apply. For a description of the apartment operating mode settings required and the DHW operating mode during holidays, refer to page 70. During special days, the special day time program of the respective rooms and of DHW is used.
Holiday operating mode Apartment operating mode during holidays Select the required operating mode for the apartment during the holiday period. The apartment operating mode during holidays applies to heating / cooling and ventilation. To be able to release cooling in holiday mode, the air conditioning release mode shouldn't be set higher than the apartment operating mode during holidays (see page 35).
Faults Error / fault status messages The central apartment unit stores up to 10 current fault status messages according to priority. They can be retrieved at any time. The lowest fault status message number represents the fault with the highest priority. If priorities are equal, the faults are listed in chronological order. Both the central apartment unit’s internal faults and the faults of the other devices contained in the system are taken into consideration.
Inputs / Outputs Inputs Displaying input signals The current input signals can be displayed via the following operating line: Main menu > Inputs / Outputs > Inputs > … The following values – if available – are displayed: • • • • • • • • • Actual value of the outside temperature Outside temperature mixed Outside temperature attenuated Operating mode contact Summer mode H/C changeover Absence Twilight Fault input X (per fault input 1 - 8) Outputs Displaying output states The states of the outputs can be dis
Settings Device Language The unit is supplied with English preselected as the operator’s language. You can select the language you prefer: Main menu > Settings > Device > Language: Then, the path can be reached in the language selected by you. Elevation above sea level To ensure display of accurate weather forecasts in the quiescent picture, the absolute atmospheric pressure acquired by the meteo sensor is converted to pressure at sea level.
Quiescent picture Display format You can select the display format required for the quiescent picture. Main menu > Settings > Quiescent picture > Display format: The following display formats are available: Display format 0 Tuesday Display format 1 14.02.2006 01:32 Tuesday 14.02.2006 1013 hPa 20°C 5°C Display format 2 01:32 Tuesday Display format 3 14.02.2006 1013 hPa 20°C 14.02.2006 1013 hPa 20°C 5°C 5°C Display format 4 01:32 Tuesday 01:32 Tuesday 20°C Display format 5 14.02.
Passwords Password for the service level The unit comes supplied with no password protection on the service level. Password protection is available as an option (1 – 9999). Use the following path to enter your password and confirm it by pressing the Menu / ok button: Main menu > Settings > Passwords > Service: Factory setting Your setting --- For more information about the various access levels, refer to page 26.
With the softkeys defined as info pages, you can select the info pages that should be displayed when pressing the keys.
Main menu > Settings > Faults > Fault input X > Fault text: Main menu > Settings > Faults > Fault input X > Fault priority: Main menu > Settings > Faults > Fault input X > Fault release: Main menu > Settings > Faults > Fault input X > Fault stat mess dly: Main menu > Settings > Faults > Fault input X > Normal position: Fault input FS fault text Fault text FS fault priority Fault priority FS fault release Fault release 1 Fault inp1 FS fault release Fault release 5 Fault inp5 4 Fault inp4 Open Open Close
For each fault output, the following settings can be made: Fault priority: The priority (urgent or Not urgent) with which the relay should be energized can be selected here Fault source: Defines whether the relay should respond only in the case of internal faults or only in the case of external faults (faults transmitted via bus) Maximum one bus fault status message can be handled.
Door names 1 - 2 Assign a meaningful name to the doors, e.g. entry door, garage door, etc. Main menu > Settings > Texts > Doors > Door X: Lamp names 1 – 4 Assign the lamps self-explanatory names, e.g. Living, Eating, etc.: Main menu > Settings > Text > Light state > Lamp X: Name for temperatures 1 - 3 Assign meaningful names to the temperatures, e.g. basement, swimming pool, etc.
Room unit QAW910 Operation All operating elements are arranged on the front of the unit. The function button is located in the battery compartment. The room unit communicates via radio signals and has no connection terminals. The settings made on the room unit only have an impact on the room to which the room unit is assigned. They have no influence on any other rooms. The settings made on the room unit are automatically synchronized with the settings of the central apartment unit.
Overriding by the central apartment unit to maintain the Economy setpoint. Overriding by the central apartment unit to maintain the Protection setpoint. The time program and the special day program are set on the central apartment unit. In the case of overriding by the central apartment unit, the display shows the symbol of the central apartment unit and the symbol of the active operating level.
Readjustment of the room temperature setpoint Room temperature setpoint readjustments by a maximum of +/- 3 K can be made with the setting knob. When turning the knob one step, the display shows the current room temperature setpoint readjustment. Each step represents another readjustment of 0.5 K. The room temperature setpoint adjustment acts on the heating and cooling setpoint. The readjustments made on the individual room units can be displayed on the central apartment unit (refer to page 36).
Possible displays Status display of battery: If the batteries’ capacity is sufficient, the symbol is briefly displayed when pressing the function button. Status display of battery: If the batteries’ capacity drops below a certain level, the symbol is constantly displayed, independent of the unit’s operating state. Summer operation active Room timer function active Display of automatic mode. Current operating level in accordance with the central apartment unit’s time program Display of manual mode.
Error messages Device faults are transmitted to the central apartment unit in the form of error messages and are then displayed with the error symbol. Device faults are communication breakdowns or short-circuits / open-circuits of sensors in the room unit. The error symbol disappears as soon as device errors are no longer present. If communication with the central apartment unit is interrupted, the connection and error symbols are displayed until communication is reestablished.
Radio plug adapter Operation KRF960 (switching) LED display functions: • LED lit: Contact closed • LED off: Contact open.
Service Monitor batteries The battery-powered devices (room unit, room temperature sensor, meteo sensor, radiator control actuator, door / window contact and smoke detector) constantly monitor their batteries’ capacity. If batteries are low, a message is forwarded to the central apartment unit. In that case, the central apartment unit switches from the quiescent picture to info page “Device state“ to show the device with the exhausted batteries (provided there is no more severe fault).
Replace batteries To ensure trouble-free operation of the battery-powered devices, replace the batteries as soon as they are close to exhaustion. Avoid complete discharge of batteries, as otherwise batteries may leak. For this reason, replace the battery as soon as the display tells you to. Room unit QAW910, room sensor QAA910 and meteo sensor QAC910 Remove the battery compartment cover. 2707Z16 Have 2 new Alkaline AA batteries ready for insertion (LR6 / 1.5 V). 2701Z23 Insert the new batteries.
Display after battery change After insertion of the new batteries, the full display appears for 2 seconds. Then, the room unit changes to Normal operation. The room operating mode settings are interrogated by the central apartment unit. Any active room timer function will not be reactivated. After inserting the new batteries, the battery capacity is checked at the room temperature sensor QAA910 and the meteo sensor QAC910 .
Insert the new batteries. Ensure that polarity is correct! Replace the battery compartment cover. b + + + 2707Z29 + + + + 2707Z28 a 2707Z27 Dispose of the old batteries in compliance with environmental regulations. After insertion of the new batteries, the batteries’ capacity is checked. During the check, the green LED lights up for 2 seconds, provided the batteries have sufficient capacity. After the check, the radiator control actuator checks its settings as a master or slave.
Binding tests The binding tests on the individual devices are triggered by briefly pressing the function button (located under the battery compartment cover). On the central apartment unit, every successful binding test is confirmed by 3 short acoustic signals. Also, the display shows an additional window with information about the test just made.
Function button on heating circuit controllers RRV912 / RRV918 and on multi-controller RRV934 The binding test of the heating circuit controllers / multi-controller is made on each channel. With the multi-controller, the test can also be carried out for a channel group. Use the channel selection button to select the channel whose binding should be checked. The LED associated with the selected channel will flash. Then, press briefly the function button. E.g.
Index A absence.............................. 27, 34 button ................................... 18 operating mode ventilation ... 46 absence and holidays .............. 69 access levels................ 22, 26, 75 acknowledging faults................ 71 actual value DHW..................................... 57 flow temp. room group.......... 44 return temp. room group ...... 44 room temperature................. 39 actuator calibration................... 43 air cond release........................
state ..................................... 55 DHW plant operation cause ..... 57 DHW temperature actual value .......................... 57 setpoint........................... 56, 57 supervision ........................... 58 display................................ 20, 83 contrast ................................ 73 faults..................................... 71 format ................................... 74 room unit .............................. 82 symbols .......................... 21, 83 disposal......
L lamp names 1 - 4 ..................... 79 language .................................. 73 lighting...................................... 73 lighting control .......................... 14 limitation DHW charging time .............. 57 room setpoint........................ 40 M M255 .................................. 15, 17 maintenance............................. 91 manual capacity check............. 86 Menu / ok button ...................... 19 menu levels ........................ 22, 24 message delay ....
room temperature actual value .......................... 39 setpoint..................... 11, 36, 39 setpoint readjustment........... 82 supervision ........................... 41 room unit .................................. 86 room valve position .................. 45 RRV912 ............................. 11, 16 RRV918 ............................. 11, 16 RRV934 ....................... 12, 13, 16 runtime forced ventilation......... 54 S safety ......................................... 9 scenes..............
room ..................................... 37 simulation of presence ......... 62 switching groups................... 61 ventilation ............................. 48 timer function................................. 28 influence on rooms ............... 40 trend calculation ....................... 14 U user level.................................. 26 V valve position ........................... 39 ventilation button ................................... 18 contact stage ........................ 48 contacts .....
/ 100 Siemens Building Technologies Synco™ living Operating instructions CE1B2707en 23.08.
/ 100 Siemens Building Technologies Synco™ living Operating instructions CE1B2707en 23.08.
© 2006-2008 Siemens Switzerland Ltd Subject to change Siemens Switzerland Ltd. Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/sbt 0678 7 4 3 1 9 0 5 4 2 0 100 / 100 Siemens Building Technologies Synco™ living 74 319 0542 0c CE1B2707en 23.08.