Limits
Tolerable overload on one side On Px +: 10000 Pa
On Px -: 400 Pa
Rupture pressure At room temperature: 2x overload
At 70 °C: 1.5x overload
Media / Admissible temperature Air and neutral gases / 0...70 °C
Data for volume flow calculation
Permitted k factor range 0...1500
Formula
Measured variables l/s, m
3
/h, m
3
/s
NOTICE
Accuracy of volume flow calculation
The accuracy of the volume flow calculation is proportional to the root of the pressure
measurement accuracy multiplied by the k-factor.
Additional data
Pressure connections
6.2 mm, (for pipe inside
5 mm)
Maintenance Maintenance free