User Manual
Commissioning
Address
2
10 | 20 A6V11841988_en--_b
2 Commissioning
2.1 Address
2.1.1 DIP switches (Climatix and other controllers)
Use DIP switches to adjust the Modbus address and for termination.
● The DIP-switches have priority over register 4x0764 (Modbus address).
● The Modbus address (register 4x0764) is valid as soon as all DIP switches are
on '0'.
● Changes to DIP switches are effective after 5 seconds.
Modbus addressing
The DIP switches allow addresses between 1…247 (Modbus specification).
The following example shows Modbus address '3':
Modbus termination
● The termination is done with 120 Ω + 1nF.
● The termination must be done manually, even if the addressing is done with
"On-event addressing (Climatix controllers) [➙ 10]".
2.1.2 On-event addressing (Climatix controllers)
On-event addressing works together with Climatix controllers.
On-event addressing performs several functions that otherwise would have to be
done 'manually':
Workflow
The QBM3700.. sensor is wired and connected to the controller via Modbus.
The DIPs 1…8 (addressing DIPs) are set to '0'.
The on-event addressing functionality is configured in the application.
The necessary functional block is therefore available in the CAS library. The
CAS library online help contains further engineering documentation.