User Manual

Maintenance
Zero reset
A6V11841988_en
--_a
17 | 19
4 Maintenance
4.1 Zero reset
Perform the zero reset without tubes. Afterwards reconnect the tubes
NOTICE
Use cases for the zero reset
As the allowed mounting position is vertical only (see "Mounting [ 4]"), the
sensor does not have to be recalibrated during commissioning in the case of
normal pressure measurement.
Only in case of relative pressure measurement (pressure nipple "-" connected
to ambient atmosphere) a zero point calibration is recommended during
commissioning.
10...20 s
Blue