User Manual

Installation
Wiring
A6V11841988_en
--_a
7 | 19
QBM3700.. uses a non-isolated RS485-Interface.
The reference of RS485 transceiver is connected to GND.
All GND pins are on the same potential.
If the Climatix controller and QBM3700.. are connected to the same power
source, take care to avoid incorrect wiring between 24 V input and GND.
The document "Modbus communication" (J3960) provides profound information
on Modbus grounding.
1.4.2 Power supply
Terminal
24V
→, ,24V
Diagram
Note Ground is optional.
1.4.3 Connection terminals
Power supply AC / DC 24 V
GND
Power supply for external devices AC/DC 24 V
Modbus® communication +
Common
Modbus® communication -
Analog output 1
GND
Analog output 2
Analog input 1
GND
Analog input 2
24V
24V
Consequence