User Manual

Commissioning
Address
A6V11841988_en
--_a
9 | 19
2 Commissioning
2.1 Address
2.1.1 DIP switches (Climatix and other controllers)
Use DIP switches to adjust the Modbus address and for termination.
The DIP-switches have priority over register 4x0764 (Modbus address).
The Modbus address (register 4x0764) is valid as soon as all DIP switches are
on '0'.
Changes to DIP switches are effective after 5 seconds.
Modbus addressing
The DIP switches allow addresses between 1…247 (Modbus specification).
The following example shows Modbus address '3':
Modbus termination
The termination is done with 120 Ω + 1nF.
The termination must be done manually, even if the addressing is done with
"On-event addressing (Climatix controllers) [ 9]".
2.1.2 On-event addressing (Climatix controllers)
On-event addressing works together with Climatix controllers.
On-event addressing performs several functions that otherwise would have to be
done 'manually':
Workflow
The QBM3700.. sensor is wired and connected to the controller via Modbus.
The DIPs 1…8 (addressing DIPs) are set to '0'.
The on-event addressing functionality is configured in the application.
The necessary functional block is therefore available in the CAS library. The
CAS library online help contains further engineering documentation.