Data Sheet for Product

7
Smart Infrastructure
A6V11684000_en
--
_c
2021
-
02
24
Technical data
Power data
Power supply
Operating voltage AC/DC 24 V ±15 %
Frequency 50/60 Hz
Protection class III (SELV / PELV), UL class 2
NOTICE! Limited energy circuit 15 VA or less.
Power consumption <2 VA
Current draw AC max. 25 mA @ AC 24 V
Current draw DC 25 mA @ DC 24 V
24V external power supply for active
sensors
Max current: 80 mA
Function data
Measuring
ranges See "Type overview / order data [ 2]".
Variables Pa, Psi, mmHG, mmH
2
O (configured via application)
Sensing element Piezo resistive
Ceramic bar: Al
2
O
3
(96%)
Diaphragm: Silicon
Accuracy
Accuracy Total measuring accuracy at required installation
position and r.H. 45%
Device 0…500 Pa, at 20°C: ± 1% FS
Device 0…1250 Pa, at 20°C: ± 0.5% FS
Device 0…2500 Pa, at 20°C: ± 0.5% FS
Device 0…500 Pa, at 0…50°C: ± 2% FS
Device 0…1250 Pa, at 0…50°C: ± 1% FS
Device 0…2500 Pa, at 0…50°C: ± 1% FS
(Note: FS = Full scale)
Long-term stability: ± 1.0% FS per DIN EN 60770, resolution
<0,1% FS
Response time <1 s