Data Sheet for Product

Technical Specification Sheet
Document No. 149-715
February 19, 2018
Siemens Industry, Inc. Page 1 of 2
Series 2200/3200 Communicating Room Sensors
for Use with Siemens Terminal Equipment
Controllers
QxAx2xx.EWSC QxAx2xx.DWSC QxAx2xx.FWSC
Sensing Only with Display Full HMI
Description
These Series 2200/3200 Room Sensors are designed for
use with Siemens Terminal Equipment Controllers
(TECs)*. The sensor and controller communicate using
an RJ-11 cable with plug connections at both ends for
easy and error-free wiring. Installation is quick and
straightforward with all hardware included for mounting
on a standard 2” × 4” electrical box. Screws and anchors
are provided for mounting the sensor directly to a wall.
Matching gaskets and trim rings are also available.
All units include an RJ-11 tool port at the bottoms of the
sensor housings for connection to Siemens
configuration, commissioning and start-up tools.
QAA Series Sensors measure room temperature, while
QFA Series sensors measure both temperature and
relative humidity. The QPA Series Sensors measure
temperature and CO
2
or temperature, CO
2
* and relative
humidity.
QPA Series sensors are designed to help maintain
occupant comfort and are not intended for use in life
safety applications.
The “Eversions have a blank front to prevent
unauthorized adjustments and are ideal for high traffic
areas or remote spaces that are not supervised.
The “D” versions display room temperature and/or room
humidity.
The “F” versions feature a full HMI that can display room
conditions and temperature setpoint. The display is
easily configured to limit the information that is available
to the occupant. Temperature setpoint can be adjusted
using soft touch plus (+) and minus (-) keys, and an
override key enables the user to manually signal to the
controller that the space is occupied.
Specifications
Temperature
Measuring range
Accuracy
QAA2280.EWxC
QAA2280.DWxC
QAA2280.FWxC
QPA2282.EWxC
All others
32°F to 122°F (0°C to 50°C)
± 0.50°F (± 0.28°C)
± 0.9°F (± 0.5°C)
± 0.9°F (± 0.5°C)
± 0.9°F (± 0.5°C)
± 0.54°F (± 0.3°C) @ 77°F (25°C)
Humidity
(QFA and QPA2284)
Measuring Range
Accuracy
Long-Term Stability
Resolution
Repeatability
0 to 100% rh
± 2% between 10 to 90%
<0.5% rh/year
0.03% rh
± 0.1% rh
CO2 (QPA Models)
Technology
Measuring Range
Accuracy*
Field Calibration
CO2 Drift
Dual Beam NDIR
0 to 2000 PPM
± (50 ppm + 2% of MV)
Not required
± 5% of range over 5 years
Setpoint/Override
(“F” versions only)
Setpoint Range 55°F to 95°F (13°C to 35°C)
Input Power
QAA and QFA
QPA
Powered using TEC RJ-11 port
Requires AQM2200
Agency Listing
Color
Dimensions
Shipping Weight
UL
cUL
CE
FCC
RCM
White
4.5” × 2.75” × 1.18”
(115 mm × 70 mm × 30 mm)
6 oz. (170 g)
* Allow up to 96 hours for unit to reach published accuracy.